Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2882381
PHOENIX CONTACTNot available

MNT-TAE D - Type 3 surge protection device

Socket attachment plug with surge protection for the power supply and signal connection of an end device with analog or digital telecommunications interface (VDSL up to 50 Mbps, on short paths (< 300 m) up to 80 Mbps). Cable is included.
Product Code: 2882381
Partner cod.: 2882381
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: C1
C2
C3
D1
IEC power supply system: TN
TT
Type: Attachment plug
Product type: Device protection
Product family: MAINTRAB
Number of positions: 2
For country-specific use in: D
Surge protection fault message: optical
Wire pairs per module: 1
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
IEC test classification: III
T3
EN type: T3
Number of ports: One
Connection dataConnection method: RJ12-/TAE 6
Grounding plug/socket
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/2a79442ffe4a3a45b2dacbf352718a81/-S204x204-FJPG
Width: 63 mm
Height: 103 mm
Depth: 78 mm
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 400
600
Insulating material: PA 6
Housing material: PA 6
Protective circuitPower supplies
Direction of action: L/N-PE & Signal Line-Earth Ground
Nominal voltage UN: 230/400VAC(TN/TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous operating voltage UC (L-N): 275 VAC
Maximum continuous operating voltage UC (L-PE): 360 VAC
Maximum continuous operating voltage UC (N-PE): 360 VAC
Rated load current IL: 16 A (30°C)
Residual current IPE: ≤ 5 µA
Standby power consumption PC: ≤ 1 VA
Reference test voltage UREF: 255 VAC
Combination wave UOC: 6 kV
Voltage protection level Up: ≤ 1.5 kV
TOV behavior at UT (L-N): 460 VAC (5s / withstand mode)
460 VAC (120min / safe failure mode)
TOV behavior at UT (L-PE): 460 VAC (5s / withstand mode)
460 VAC (120min / withstand mode)
1455 VAC (200ms / safe failure mode)
TOV behavior at UT (N-PE): 1200 VAC (200ms / safe failure mode)
Response time tA (L-N): ≤ 25 ns
Response time tA (L-PE): ≤ 100 ns
Response time tA (N-PE): ≤ 100 ns
Max. required back-up fuse: 16 A (gG / B / C)
Short-circuit current rating ISCCR: 1.5 kA AC
Information technology
Maximum continuous voltage UC: 200 VDC
Rated current: 150 mA (25°C)
Operating effective current IC at UC: ≤ 150 µA
Standby power consumption PC: ≤ 1 VA
Residual current IPE: ≤ 2 µA
Insulation resistance Riso: ≥ 1 MΩ
≥ 1 GΩ
Nominal discharge current In (8/20) µs (line-line): 1 kA
Nominal discharge current In (8/20) µs (line-ground): 2.5 kA
Total discharge current Itotal (8/20)µs: 10 kA
Max. discharge current Imax (8/20) µs: 2.5 kA
Nominal pulse current Ian (10/1000) µs (line-line): 35 A
Nominal pulse current Ian (10/1000) µs (line-earth): 200 A
Output voltage limitation at 1 kV/µs (line-line) spike: ≤ 360 V
Output voltage limitation at 1 kV/µs (line-earth) spike: ≤ 900 V
Output voltage limitation at 1 kV/µs (line-line) static: ≤ 360 V
Residual voltage at In (conductor-conductor): ≤ 500 V
Residual voltage at In (conductor-ground): ≤ 30 V
Residual voltage with Ian (10/1000) µs (line-line): ≤ 35 V
Residual voltage with Ian (10/1000) µs (line-earth): ≤ 35 V
Voltage protection level Up (line-line): ≤ 460 V (C2 - 1 kA)
≤ 350 V (C3 - 25A)
Voltage protection level Up (line-earth): ≤ 900 V (C2 - 2 kA)
≤ 900 V (C3 - 100A)
Response time tA (line-line): ≤ 25 ns
Response time tA (line-earth): ≤ 100 ns
Cut-off frequency fg (3dB), sym. in 100Ω system: typ. 4 MHz
Cut-off frequency fg (3dB), sym. in 150Ω system: typ. 3 MHz
Cut-off frequency fg (3dB), sym. in 600Ω system: typ. 700 kHz
Capacity (Core-Core): typ. 1 nF
Capacity (Core-Earth): typ. 5 pF
Alternating current carrying capacity (line-line): 250mA - 1s
Alternating current carrying capacity (line-earth): 10A - 1s
Pulse reset time (line-line): ≤ 15ms
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (Child-proofing)
Ambient temperature (operation): -25°C ... 75°C
Ambient temperature (storage/transport): -25°C ... 75°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Standards and regulationsStandards/specifications: IEC 61643-11
EN61643-11
EN61643-21
IEC 61643-21
Note: 2011
2019
A2:2013
A2:2012
MountingMounting type: Plugging into the mains socket
Technical Specs
ECLASSECLASS-11.0: 27130810
ECLASS-13.0: 27171602
ETIMETIM 9.0: EC001473
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Certification_00348.pdf

Flyer_00002.pdf

Flyer_00001.pdf

Manufacturer_declaration_01357.pdf

Manufacturer_declaration_02315.pdf

Manufacturer_declaration_15397.pdf

Package_slip_00339.pdf