Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2885278
PHOENIX CONTACTNot available

EMD-SL-3V-400-N - Monitoring relay

Monitoring relay for monitoring 3-phase voltages of 280…520 V AC, window, with neutral conductor connection, supply voltage can be selected via power module, 1 changeover contact
Product Code: 2885278
Partner cod.: 2885278
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesProduct type: Voltage monitoring relay
Operating mode: 100% operating factor
Mechanical service life: approx. 2x 107 cycles
Insulation characteristics
Insulation: Basic insulation
Insulation characteristics​
Insulation: Basic insulation
Overvoltage category: III
Pollution degree: 2
Electrical propertiesService life electrical: 2x 105 cycles at ohmic load, 1000 VA
Mains type: 3-phase
Rated insulation voltage: 300 V
Rated surge voltage: 4 kV
Supply
Supply voltage range: 24 VAC ... 230 VAC (see Power modules)
24 VDC (see Power modules)
Nominal power consumption: 2 VA (1.5W)
Input dataInput name: Measuring input
Measured value: AC sine (48 Hz ... 63 Hz)
Nominal input voltage UN: 3 N ~ 400/230 V
Maximum input voltage: 3 N ~ 600/346 V
Input resistance of voltage input: 1 MΩ
Frequency range: 50 Hz ... 60 Hz
Maximum temperature coefficient: < 0.1 %/K
Setting range for response delay: 0.2 s ... 10 s
Min. setting range: -30 % ... 20 % (From UN)
Max. setting range: -20 % ... 30 % (From UN)
Min setting range of the voltage threshold value: 280 VAC ... 480 VAC
Max. setting range of the voltage threshold value: 320 VAC ... 520 VAC
Function: Window, with neutral conductor connection
Basic accuracy: ± 5 % (of scale end value)
Setting accuracy: ≤ 5 % (of scale end value)
Repeat accuracy: ≤ 2 %
Voltage influence: ≤ 0.5 %
Recovery time: 500 ms
Output dataSwitching
Contact switching type: 1 floating changeover contact
Maximum switching voltage: 250 VAC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.: 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse: 5 A (fast-blow)
Connection dataConnection method: Screw connection
Stripping length: 8 mm
Conductor cross section rigid: 0.5 mm² ... 2.5 mm²
Conductor cross section flexible: 0.25 mm² ... 2.5 mm²
Conductor cross section AWG: 20 ... 14
DimensionsWidth: 22.5 mm
Height: 90 mm
Depth: 113 mm
Material specificationsHousing insulation material: Polyamide PA, self-extinguishing
Environmental and real-life conditionsAmbient conditions
Degree of protection (Housing): IP40 (Housing)
Degree of protection (Connection terminal blocks): IP20 (Connection terminal blocks)
Ambient temperature (operation): -25°C ... 55°C
-25°C ... 40°C (corresponds to UL508)
Ambient temperature (storage/transport): -25°C ... 70°C
Climatic class: 3K3 (in acc. with EN 60721)
Permissible humidity (operation): 15 % ... 85 %
ApprovalsCE
Certificate: CE-compliant
UL, USA/Canada
Identification: UL/C-UL Listed UL 508
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive
Noise immunity: EN 61000-6-2
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-3
Standards and regulationsStandards/regulations: EN50178
MountingMounting type: DIN rail mounting
Assembly instructions: on standard DIN rail NS 35 in accordance with EN 60715
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27371801
ECLASS-12.0: 27371801
ECLASS-13.0: 27371801
ETIMETIM 9.0: EC001438
UNSPSCUNSPSC 21.0: 41113600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Data_sheet_03699.pdf

Manufacturer_declaration_01617.pdf

Manufacturer_declaration_04696.pdf

Package_slip_01006.pdf

Technical_drawing_39158.pdf