Industrial Automation
Notes | General: Separating plate PLC-ATP must be installed for voltages larger than 250V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or FBST 500.... The PLC-ATP separating plate should be installed for safe isolation between adjacent modules The PLC-ATP separating plate is required at the start and end of every PLC terminal strip. The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact. |
Product properties | Product type: Relay Module Product family: PLC-INTERFACE Application: high inrush currents Operating mode: 100% operating factor Mechanical service life: 3x 107 cycles Insulation characteristics Insulation: Safe isolation, reinforced insulation Insulation characteristics: Standards/regulations Insulation: Safe isolation, reinforced insulation Overvoltage category: III Pollution degree: 3 |
Electrical properties | Maximum power dissipation for nominal condition: 0.43 W Test voltage (Winding/contact): 4 kV AC (50Hz, 1min., winding/contact) Standards/regulations Rated insulation voltage: 250 VAC Rated surge voltage: 6 kV |
Input data | Coil side Nominal input voltage UN: 24 VDC Input voltage range: 20.2 VDC ... 33.6 VDC (20°C) Drive and function: monostable Drive (polarity): polarized Typical input current at UN: 18 mA Typical response time: 8 ms Typical release time: 10 ms Coil voltage: 24 VDC Protective circuit: Reverse polarity protection; Polarity protection diode Surge protection; Freewheeling diode Operating voltage display: Yellow LED |
Output data | Switching Contact switching type: 1 N/O contact Type of switch contact: Single contact Contact material: AgSnO Maximum switching voltage: 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) Minimum switching voltage: 12 V (100 mA) Limiting continuous current: 6 A 10 A (the value is permissible if both connections 13, both connections 14 and both connections BB are bridged) Maximum inrush current: 80 A (20ms) 130 A (peak, at capacitive load, 230 V AC, 24 üF) Min. switching current: 100 mA (12V) Interrupting rating (ohmic load) max.: 144 W (at 24 V DC) 58 W (at 48 V DC) 48 W (at 60 V DC) 50 W (at 110 V DC) 80 W 85 W (for 250 V DC) 1500 VA (for 250 V AC) Interrupting rating (ohmic load) max. bridged: 240 W (for 24 V DC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.) 2500 VA (for 250 V AC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.) Switching capacity min.: 1200 mW Switching capacity: 2 A (at 24 V, DC13) 0.2 A (at 110 V, DC13) 0.2 A (at 250 V, DC13) 6 A (at 24 V, AC15) 6 A (at 120 V, AC15) 6 A (at 250 V, AC15) |
Connection data | Connection method: Push-in connection Stripping length: 10 mm Conductor cross section rigid: 0.14 mm² ... 2.5 mm² Conductor cross section flexible: 0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² (Single ferrule) 2x 0.5 mm² ... 1 mm² (TWIN ferrule) Conductor cross section AWG: 26 ... 14 |
Dimensions | Width: 14 mm Height: 80 mm Depth: 94 mm |
Material specifications | Flammability rating according to UL 94: V0 (Housing) |
Environmental and real-life conditions | Ambient conditions Degree of protection (Relay): RT II (Relay) Degree of protection (Relay base): IP20 (Relay base) Degree of protection (Installation location): ⥠IP54 (Installation location) Ambient temperature (operation): -40°C ... 60°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant Shipbuilding approval Certificate: TAE0000196 Corrosive gas test Identification: ISA-S71.04. G3 Harsh Group EN60068-2-60 DNV GL data Temperature: D Humidity: A Vibration: B/C EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive Electromagnetic compatibility: Conformance with EMC directive |
Standards and regulations | Standards/regulations Standards/regulations: IEC 60947-5-1 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: in rows with zero spacing Mounting position: any |
ECLASS | ECLASS-11.0: 27371601 ECLASS-12.0: 27371601 ECLASS-13.0: 27371601 |
ETIM | ETIM 9.0: EC001437 |
UNSPSC | UNSPSC 21.0: 39122300 |