Industrial Automation
Product properties | Product type: Extension module MTTF: 1087 Years (SN29500 standard, temperature25°C, operating cycle21%) 523 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 204 Years (SN29500 standard, temperature40°C, operating cycle100%) Insulation characteristics Overvoltage category: II Degree of pollution: 2 |
Electrical properties | Electrical isolation: 300 V (Rated insulation voltage (in each case between the digital outputs //TBUS supply, reinforced insulation in accordance with EN/IEC 61010)) 300 V (Rated insulation voltage (to adjacent devices, basic insulation in accordance with EN/IEC 61010)) Test voltage for digital I/Os: 2.5 kV AC (50Hz, 1min.) Maximum power dissipation for nominal condition: 1.32 W Transient surge protection: Yes Supply Supply voltage range: 19.2 VDC ... 30.5 VDC (DIN rail connector) Max. current consumption: ⤠55 mA (At 24 V DC, at 25°C) |
Output data | Digital Output name: Relay output Number of outputs: 4 Contact switching type: Changeover contact Contact material: AgSnO2 Maximum switching voltage: 250 V AC/DC Min. switching current: ⥠10 mA Max. switching current: 5 A (250VAC) 0.168 A (250VDC) 5 A (24VDC) Mechanical service life: 1x 107 cycles Electrical service life: 1x 105 cycles (At 5 A, 250 VAC, ohmic) 2x 105 cycles (At 2 A, 250 VAC, cosà 0.4) 2x 105 cycles (At 1 A, 24 V DC, L/R = 48 ms) Maximum switching frequency: 2 Hz Switching capacity: 120 W (24VDC) 120 W (30VDC) 20 W (48VDC) 18 W (60VDC) 22 W (110VDC) 40 W (220 VDC) 42 W (250VDC) Behavior of the outputs (adjustable via DIP switch): Hold / Reset |
Connection data | Tightening torque: 0.5 Nm ... 0.6 Nm 5 lbf-in. ... 7 lbf-in. Connection method: Screw connection Stripping length: 7 mm Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 |
Signaling | Status display: Green LED (supply voltage, PWR) Green LED (bus communication, DAT) Red LED (periphery error, ERR) Yellow LED (digital output, DO1) Yellow LED (digital output, DO2) Yellow LED (digital output, DO3) Yellow LED (digital output, DO4) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/2cf50fa12a76e642a87bbf025fee56a1/-S204x204-FJPG Width: 17.5 mm Height: 113 mm Depth: 114.5 mm |
Material specifications | Material: PA 6.6-FR Flammability rating according to UL 94: V0 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C (>55°Cderating, see technical documentation) -40°F ... 158°F (>131°Fderating, see technical documentation) Ambient temperature (storage/transport): -40°C ... 85°C -40°F ... 185°F Altitude: 2000 m Permissible humidity (operation): 20 % ... 85 % Permissible humidity (storage/transport): 20 % ... 85 % Shock: 16g, 11 ms Vibration (operation): in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant ATEX Identification: ï II 3 G Ex ec nC IIC T4 Gc Certificate: IBExU15ATEXB008X Note: Please follow the special installation instructions in the documentation! IECEx Identification: Ex ec nC IIC T4 Gc Certificate: IECExIBE13.0019X EACEx Identification: 2Ex nA nC IIC T4 Gc X Certificate: RU C-DE.HB49.B.00033/20 UL, USA/Canada Identification: 508 Listed Class I, Div. 2, Groups A, B, C, D T4A Class I, Zone 2, IIC T4 CCC/China-Ex Identification: Ex ec nC IIC T4 Gc Certificate: 2022122310115625 KC approval for South Korea Certificate: R-R-PCK-2901536 Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A |
EMC data | Noise immunity: EN 61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 61000-6-4 |
Standards and regulations | Standard designation: EMC Directive 2014/30/EU Ex Directive (ATEX) Ex Directive (ATEX) Standards/specifications: EN61000-6-2 EN61000-6-4 EN60079-0 EN60079-15 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: on standard DIN rail NS 35 in accordance with EN 60715 Mounting position: any |
ECLASS | ECLASS-11.0: 27242604 ECLASS-12.0: 27242604 ECLASS-13.0: 27242604 |
ETIM | ETIM 9.0: EC001599 |
UNSPSC | UNSPSC 21.0: 32151602 |
Description other products