Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Signal conditioner Product family: MINI Analog Pro No. of channels: 1 Type: Signal conditioner Insulation characteristics: GBStandard Overvoltage category: II Pollution degree: 2 |
Electrical properties | No. of channels: 1 Electrical isolation: 2-way isolation Electrical isolation between input and output: yes Limit frequency (3 dB): 100 Hz Signal transmission behavior: In=Out Maximum temperature coefficient: ⤠0.002 %/K (of measured value / 100 é load) Maximum transmission error: ⤠0.1 % (of final value) Additional error, load-dependent: < 0.075 % (of measured value / 100 é load) Electrical isolation Input/output Rated insulation voltage: 300 Vrms Test voltage: 3 kV AC (50Hz, 60s) Insulation: Reinforced insulation according to IEC/EN61010-1 Supply Supply voltage range: 9.6 VDC ... 30 VDC (loop-powered, no external supply necessary) Power consumption: 600 mW |
Input data | Signal: Current Number of inputs: 1 Configurable/programmable: no Current input signal: 0 mA ... 20 mA 4 mA ... 20 mA Response current: approx. 200 µA Input voltage limitation: 30 V Voltage dissipation: 3.1 V (I = 20 mA) |
Output data | Signal: Current Number of outputs: 1 Configurable/programmable: no Current output signal: 0 mA ... 20 mA 4 mA ... 20 mA Load/output load current output: < 600 é (at I = 20 mA output signal) |
Connection data | Connection method: Push-in connection Stripping length: 10 mm Conductor cross section rigid: 0.2 mm² ... 2.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule) Conductor cross section flexible: 0.14 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 (flexible) |
Ex data | Ex installation (EPL): Gc Div.2 |
Dimensions | Width: 6.2 mm Height: 109.81 mm Depth: 119.2 mm |
Material specifications | Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2 Housing material: PBT |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (not assessed by UL) Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: < 2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: BVS 19 ATEX E 079 X UKCAEx(UKEX) Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: PxCIF21UKEX2901994X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx BVS 19.0068X CCC/China-Ex Identification: Ex nA IIC T4 Gc UL, USA/Canada Identification: UL508 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC T6 EACEx Identification: ï 2Ex ec IIC T4 Gc Certificate: BY/112 02.01 TP012 103.01 00079 |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 |
Standards and regulations | Electrical isolation: 2-way isolation GBStandard Standards/regulations: GB3836.1 GB3836.8 |
Mounting | Mounting type: DIN rail mounting Mounting position: any |
Description other products