Industrial Automation
Product properties | Product type: Signal conditioner Product family: MACX Analog No. of channels: 2 Type: Signal conditioners with SIL functional safety Insulation characteristics Overvoltage category: II Pollution degree: 2 |
Electrical properties | No. of channels: 2 Electrical isolation: 2-way isolation Signal transmission behavior: In=Out Maximum temperature coefficient: ⤠0.002 %/K (of measured value / 100 é load) Transmission error, typical: 0.08 % (of final value) Electrical isolation Input/output/power supply Rated insulation voltage: 300 Vrms Test voltage: 2.5 kV AC (50Hz, 60s) Insulation: Safe isolation in accordance with IEC/EN61010-1 Supply Supply voltage range: loop-powered, no external supply necessary |
Input data | Signal: Current Number of inputs: 2 Configurable/programmable: no Max. voltage input signal: < 30.5 V Current input signal: 0 mA ... 20 mA 4 mA ... 20 mA Input voltage limitation: 30.5 V Voltage dissipation: 2.9 V (I = 20 mA) Step response (10-90%): 5 ms (500 é load) Additional error, load-dependent: 0.022 % (of measured value / 100 é load) Response current: approx. 50 µA |
Output data | Signal: Current Number of outputs: 2 Configurable/programmable: no Max. voltage output signal: 27.5 V Current output signal: 0 mA ... 20 mA 4 mA ... 20 mA Load/output load current output: ⤠1375 é (I = 20 mA) Residual ripple: < 10 mVrms (500 é load) |
Connection data | Connection method: Push-in connection Stripping length: 8 mm Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Test socket Max. diameter: 2.3 mm |
Ex data | Ex installation (EPL): Gc Div.2 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/d4485e18fd60154ba93005f91a55c68d/-S204x204-FJPG Width: 12.5 mm Height: 116 mm Depth: 113.7 mm Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715) |
Material specifications | Flammability rating according to UL 94: V0 (Housing) Housing material: PA 6.6-FR |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (not assessed by UL) Ambient temperature (operation): -40°C ... 85°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: < 2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant Note: and EN61326-1 ATEX Identification: ï II 3 G Ex nA IIC T4 Gc X UKCAEx(UKEX) Identification: ï II 3 G Ex nA IIC T4 Gc X Certificate: PxCIF21UKEX2905278X UL, USA/Canada Identification: UL 61010 Listed Class I, Div. 2, Groups A, B, C, D T4 Class I, Zone 2, Group IIC T4 Safety Integrity Level (SIL, IEC 61508) Identification: 3 Certificate: 968/FSP1200.01/21 |
EMC data | Noise immunity: EN 61326-1 Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 |
Standards and regulations | Electrical isolation: 2-way isolation |
Mounting | Mounting type: DIN rail mounting |
Description other products