Industrial Automation
UNO-PS/1AC/24DC/ 60W - Power supply unit


Input data | AC operation Nominal input voltage range: 100 VÃAC ... 240 VÃAC Input voltage range: 85 VÃAC ... 264 VÃAC Input voltage range AC: 85 VÃAC ... 264 VÃAC Voltage type of supply voltage: AC Inrush current: < 30 A (typ.) Inrush current integral (I2t): < 0.5 A2s (typ.) AC frequency range: 50 Hz ... 60 Hz Frequency range (fN): 50 Hz ... 60 Hz ñ10Ã% Mains buffering time: > 20 ms (120ÃVÃAC) > 85 ms (230 V AC) Current consumption: typ. 1.3 A (100ÃVÃAC) typ. 0.6 A (240ÃVÃAC) Nominal power consumption: 135.5 VA Protective circuit: Transient surge protection; Varistor Power factor (cos phi): 0.49 Typical response time: < 1 s Input fuse: 2.5 A (slow-blow, internal) Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K) |
Output data | Efficiency: typ. 88 % (120ÃVÃAC) typ. 90 % (230 V AC) Output characteristic: HICCUP Nominal output voltage: 24 VÃDC ñ1Ã% Nominal output current (IN): 2.5 A (-25ðCÃ...Ã55ðC) Derating: 55°C ... 70°C (2.5%/K) Feedback voltage resistance: < 35 VÃDC Protection against overvoltage at the output (OVP): ââ°¤ 35 VÃDC Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 2 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 0.1 % (change in input voltage ñ10 %) Residual ripple: < 30 mVPP (with nominal values) Short-circuit-proof: yes Output power: 60 W Maximum no-load power dissipation: < 0.3 W Power loss nominal load max.: < 7 W Rise time: < 0.5 s (UOUT (10 % ... 90 %)) Response time: < 2 ms Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes |
Connection data | Input Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 Stripping length: 8 mm Screw thread: M3 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Output Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 Stripping length: 8 mm Screw thread: M3 Tightening torque, min: 0.6 Nm Tightening torque max: 0.8 Nm |
Signaling | Types of signaling: LED |
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 4 kV AC (type test) 3 kV AC (routine test) |
Product properties | Product type: Power supply Product family: UNO POWER MTBF (IEC 61709, SN 29500): > 785000 h (40ðC) Insulation characteristics Protection class: II (in closed control cabinet) Degree of pollution: 2 |
Dimensions | Width: 35 mm Height: 90 mm Depth: 84 mm Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 30 mm / 30 mm |
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: 0Ãmm horizontally, 30Ãmm vertically Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No |
Material specifications | Flammability rating according to ULÃ94 (housing / terminal blocks): V0 Housing material: Plastic Polycarbonate Type of housing: Polycarbonate Foot latch material: POM (Polyoxymethylene) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (> 55°C Derating: 2.5 %/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Climatic class: 3K22 (in accordance with ENÃ60721-3-3) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ñ2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and regulations | Standard ââ¬Ã¢ Electronic equipment for use in electrical power installations and their assembly into electrical power installations: ENÃ50178/VDEÃ0160 (PELV) Standard ââ¬Ã¢ Limitation of mains harmonic currents: ENÃ61000-3-2 Standard - Electrical safety: IEC 62368-1Ã(SELV) Standard ââ¬Ã¢ Safety extra-low voltage: IEC 62368-1 (SELV) und ENÃ60204-1 (PELV) Standard - Safe isolation: DINÃVDEÃ0100-410 Standard - Safety of transformers: ENÃ61558-2-16 Approval - requirement of the semiconductor industry with regard to mains voltage dips: ENÃ61000-4-11 |
Approvals | CSA: CAN/CSA-C22.2 No.Ã60950-1-07 CSA-C22.2 No.Ã107.1-01 CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4A (Hazardous Location) UL approvals: UL/C-UL listed ULÃ508 NEC Class 2 as per UL 1310 UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4A (Hazardous Location) UL/C-UL Recognized ULÃ60950-1 Conformity/Approvals SIL in accordance with IEC 61508: 0 |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 6 kV (Test Level 3) Discharge in air: 8 kV (Test Level 3) Comments: Criterion B Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 6 GHz Test field strength: 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 2 kV (Test Level 3 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ Input/Output: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Voltage dips Standards/regulations: ENÃ61000-4-11 Voltage: 230 VÃAC Frequency: 50 Hz Voltage dip: 70 % 40 % 0 % Number of periods: 25 periods 10 periods 1 period Additional text: ClassÃ3 Comments: Criterion A Emitted interference Standards/regulations: ENÃ61000-6-3 Radio interference voltage in acc. with EN 55011: ENÃ55011 (ENÃ55022) ClassÃB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |