Industrial Automation
Input data | Control input (configurable) Rem: Output power ON/OFF (SLEEP MODE) Default: Output power ON (>40kâ¦/24 V DC/open bridge between Rem and SGnd) AC operation Network type: Star network Nominal input voltage range: 100 VAC ... 240 VAC Input voltage range: 100 VAC ... 240 VAC -15%...+10% Derating: < 100 VAC (1%/V) Electric strength, max.: 300 VAC 60 s Typical national grid voltage: 120 VAC 230 VAC Voltage type of supply voltage: AC/DC Inrush current: typ. 12 A (at 25°C) Inrush current integral (I2t): < 0.7 A2s Inrush current limitation: 12 A (after 1ms) AC frequency range: 50 Hz ... 60 Hz -10%...+10% Frequency range (fN): 50 Hz ... 60 Hz -10%...+10% 16.7 Hz (acc. to EN50163) Mains buffering time: typ. 42 ms (120VAC) typ. 44 ms (230 VAC) Current consumption: 3.4 A (100VAC) 2.8 A (120VAC) 1.5 A (230 V AC) 1.5 A (240VAC) Nominal power consumption: 274 VA Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester Power factor (cos phi): 0.94 Switch-on time: < 1 s Typical response time: 300 ms (from SLEEP MODE) Input fuse: 8 A (slow-blow, internal) Recommended breaker for input protection: 10 A ... 16 A (Characteristic B, C, D, K or comparable) Discharge current to PE: < 3.5 mA 0.7 mA (264VAC, 60Hz) DC operation Nominal input voltage range: 110 VDC ... 250 VDC Input voltage range: 110 VDC ... 250 VDC -18%...+40% Derating: < 110 VDC (1%/V) Voltage type of supply voltage: DC Current consumption: 3 A (110VDC) 1.3 A (250VDC) |
Output data | Efficiency: typ. 92.5 % (120VAC) typ. 93.4 % (230 V AC) Output characteristic: U/I Advanced Smart HICCUP FUSE MODE Nominal output voltage: 24 VDC Setting range of the output voltage (USet): 24 VDC ... 29.5 VDC (constant capacity) Nominal output current (IN): 10 A Static Boost (IStat.Boost): 12.5 A Dynamic Boost (IDyn.Boost): 20 A (5 s) Selective Fuse Breaking (ISFB): 60 A (15 ms) Magnetic circuit breaker tripping: A1...A6 / B2...B6 / C1...C3 / Z1...Z6 Derating: > 60°C (2.5%/K) Feedback voltage resistance: ⤠35 VDC Protection against overvoltage at the output (OVP): ⤠32 VDC Control deviation: < 0.5 % (Static load change 10% ... 90%) < 4 % (Dynamic load change 10% ... 90%, (10 Hz)) < 0.25 % (change in input voltage ±10 %) Residual ripple: < 80 mVPP (with nominal values) Short-circuit-proof: yes No-load proof: yes Output power: 240 W 300 W 480 W Apparent power: 336 VA (120V, UOUT = 24V, IOUT = stat. Boost) 345 VA (230V, UOUT = 24V, IOUT = stat. Boost) Maximum no-load power dissipation: < 3 W (120VAC) < 3 W (230 V AC) Power loss nominal load max.: < 20 W (120VAC) < 17 W (230 V AC) Power dissipation SLEEP MODE: < 3 W (120VAC) < 3 W (230 V AC) Crest factor: typ. 1.50 (120VAC) typ. 1.67 (230 V AC) Rise time: < 1 s (UOut=10%...90%) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal Signal ground SGnd: Reference potential for Out1, Out2, and Rem Signal Out 1 (configurable) Digital: 24 VDC 20 mA Default: 24 VDC 20 mA 24VDC for UOut >0.9xUSet Signal Out 2 (configurable) Digital: 24 VDC 20 mA Analog: 4 mA ... 20 mA ±5% (Load â¤400é) Default: 24 VDC 20 mA 24VDC for POut<PN Signal relay 13/14 (configurable) Default: closed (Uout > 0.9 USet) Digital: 24 VDC 1 A 30 V AC/DC 0.5 A |
Connection data | Input Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 Stripping length: 6.5 mm Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Output Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 Stripping length: 6.5 mm Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Signal Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 1 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 1.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 0.75 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 1.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 16 Stripping length: 8 mm |
Signaling | Types of signaling: LED Floating signal contact Active signal output Out1 (digital, configurable) Active signal output Out2 (analog, configurable) Remote contact Signal ground SGnd Signal output POut: > 100% (LED lights up yellow, output power > 240W) > 75% (LED lights up green, output power > 180W) > 50% (LED lights up green, output power > 120W) UOut: > 0.9xUSet (LED lights up green) < 0.9xUSet (LED flashes green) |
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 4 kV AC (type test) 2 kV AC (routine test) Insulation voltage output / PE: 0.5 kV DC (type test) 0.5 kV DC (routine test) Insulation voltage input / PE: 3.5 kV AC (type test) 2.4 kV AC (routine test) Switching frequency: 90 kHz ... 110 kHz (Auxiliary converter stage) 50 kHz ... 245 kHz (Main converter stage) 35 kHz ... 700 kHz (PFC stage) |
Product properties | Product type: Power supply Product family: QUINT POWER MTBF (IEC 61709, SN 29500): > 1251000 h (25°C) > 783000 h (40°C) > 377000 h (60°C) Environmental protection directive: RoHS Directive 2011/65/EU WEEE Reach Insulation characteristics Protection class: I Degree of pollution: 2 Life expectancy (electrolytic capacitors) Current: 5 A Temperature: 40°C Time: 286000 h Additional text: 120VAC Life expectancy (electrolytic capacitors)â Current: 5 A Temperature: 40°C Time: 283000 h Additional text: 230VAC Life expectancy (electrolytic capacitors)ââ Current: 10 A Temperature: 25°C Time: 377000 h Additional text: 120VAC Life expectancy (electrolytic capacitors)âââ Current: 10 A Temperature: 25°C Time: 454000 h Additional text: 230VAC Life expectancy (electrolytic capacitors)ââââ Current: 10 A Temperature: 40°C Time: 133000 h Additional text: 120VAC Life expectancy (electrolytic capacitors)âââââ Current: 10 A Temperature: 40°C Time: 160000 h Additional text: 230VAC |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/a76863372d930940919e6d619f67b592/-S204x204-FJPG Width: 50 mm Height: 130 mm Depth: 125 mm Installation dimensions Installation distance right/left: 5 mm / 5 mm Installation distance top/bottom: 50 mm / 50 mm Alternative assembly Width: 122 mm Height: 130 mm Depth: 53 mm |
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: PN â¥50%, 5mm horizontally, 15mm next to active components, 50mm vertically alignable: PN <50%, 0mm horizontally, 40mm vertically top, 20 mm vertically bottom Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: yes |
Material specifications | Flammability rating according to UL94 (housing / terminal blocks): V0 Housing material: Metal Hood version: Stainless steel X6Cr17 Side element version: Aluminum |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ⤠5000 m (> 2000 m, observe derating) Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ⤠100 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): 5Hz ... 100Hz resonance search 2.3g, 90min., resonance frequency 2.3g, 90min. (according to DNV GL Class C) |
Standards and regulations | Rail applications: EN50121-3-2 EN50121-4 EN50121-5 EN50163 IEC 62236-3-2 IEC 62236-4 IEC 62236-5 HART FSK Physical Layer Test Specification Compliance: Output voltage UOut compliant Standard â Limitation of mains harmonic currents: EN61000-3-2 Standard - Electrical safety: IEC 61010-2-201(SELV) Standard â Safety extra-low voltage: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation: IEC 61558-2-16 IEC 61010-2-201 Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1 Standard - Safety of transformers: EN61558-2-16 Battery charging: DIN41773-1 Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMIF47-0706, EN61000-4-11 Overvoltage category EN 61010-1: II(â¤5000m) EN 62477-1: III(â¤2000m) |
Approvals | CSA: CAN/CSA-C22.2 No.60950-1-07 CSA-C22.2 No.107.1-01 Shipbuilding approval: DNV GL, PRS, BV, LR, ABS SIQ: BG (type approved) CB-Scheme (IEC 61010-1, IEC 61010-2-201, IEC 60950-1) UL approvals: UL Listed UL508 UL/C-UL Recognized UL60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: EN61000-6-3 EN61000-6-4 EMC requirements for noise immunity: EN61000-6-1 EN61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU EMC requirements, power plant: IEC 61850-3 EN61000-6-5 Conducted noise emission: EN55016 EN61000-6-3 (Class B) Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) EN55016 EN61000-6-3 (Class B) DNVGL conducted interference: ClassA Additional text: Area power distribution Bridge and deck area DNVGL noise radiation: ClassB Harmonic currents Standards/regulations: EN61000-3-2 EN61000-3-2 (Class A) Frequency range: 0 kHz ... 2 kHz Flicker Standards/regulations: EN61000-3-3 Frequency range: 0 kHz ... 2 kHz Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: 8 kV (Test Level 4) Discharge in air: 15 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 6 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: 4 kV (Test Level 4 - asymmetrical) Output: 4 kV (Test Level 4 - asymmetrical) Signal: 4 kV (Test Level 4 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: EN61000-4-5 Input: typ. 3 kV (Test Level 4 - symmetrical) typ. 6 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 4 kV (Test Level 4 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Power frequency magnetic field Standards/regulations: EN61000-4-8 Frequency: 16.7 Hz 50 Hz 60 Hz 50 Hz 60 Hz 0 Hz Test field strength: 100 A/m 1 kA/m 300 A/m Additional text: 60 s 3 s DC, 60s Comments: Criterion A Frequency range: 50 Hz ... 60 Hz Voltage dips Standards/regulations: EN61000-4-11 Voltage: 230 VAC Frequency: 50 Hz Voltage dip: 70 % 40 % 0 % Number of periods: 0.5 / 1 / 25 / 30 periods 5 / 10 / 50 periods 0,5 / 1 / 5 / 50 / 250 periods Additional text: Test Level 2 Comments: Criterion A: 0.5 / 1 / 25 / 30 periods Criterion A Criterion A: 0.5 / 1 period Criterion B: 5 / 50 / 250 periods Pulse-shape magnetic field Standards/regulations: EN61000-4-9 Test field strength: 1000 A/m Comments: Criterion A Attenuated sinusoidal oscillations (ring wave) Standards/regulations: EN61000-4-12 Input: 2 kV (Test Level 4 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Comments: Criterion A Asymmetrical conducted disturbance variables Standards/regulations: EN61000-4-16 Test level 1: 15 Hz 150 Hz (Test Level 4) Voltage: 30 V 3 V 3 V 3 V 30 V 30 V 30 V (5 s) 300 V (1 s) Test level 2: 150 Hz 1.5 kHz (Test Level 4) Test level 3: 1.5 kHz 15 kHz (Test Level 4) Test level 4: 15 kHz 150 kHz (Test Level 4) Test level 5: 16.7 Hz 50 Hz 60 Hz (Test Level 4) Test level 6: 16.7 Hz 50 Hz 60 Hz (Test Level 4) Comments: Criterion A Attenuated oscillating wave Standards/regulations: EN61000-4-18 Input, output (test level1): 100 kHz 1 MHz (Test Level 3 - symmetrical) Voltage: 1 kV 2.5 kV 1 kV 2.5 kV Input, output (test level2): 100 kHz 1 MHz (Test Level 3 - asymmetrical) Input, output (test level3): Test Level 3 - asymmetrical Signals (test level1): 100 kHz 1 MHz (Test Level 3 - symmetrical) Signals (test level2): 100 kHz 1 MHz (Test Level 3 - asymmetrical) Comments: Criterion A Attenuated oscillating magnetic field Standards/regulations: EN61000-4-10 Test field strength: 100 A/m Test level 1: 100 kHz Test level 2: 1 MHz Comments: Criterion A Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
ECLASS | ECLASS-11.0: 27040701 ECLASS-13.0: 27040701 ECLASS-12.0: 27040701 |
ETIM | ETIM 9.0: EC002540 |
UNSPSC | UNSPSC 21.0: 39121000 |
Description other products