Product properties | Product type: Front adapter |
Electrical properties | Operating voltage (DC): ⤠30 VDC Nominal operating mode: 100% operating factor Current (Per path): ⤠500 mA (uncoiled) Supported controller YOKOGAWA CS3000 CentumVP Suitable I/O card: AAI543 AAI141 AAI143 AAI835 AAI841 AAI135 AAR181 AAT141 AAV141 AAV142 AAB841 AAV542 Supported controller YOKOGAWA STARDOM Suitable I/O card: NFAI543 NFAI141 NFAI143 NFAI835 NFAI841 NFAI135 NFAV141 NFAV142 NFAB841 NFAV542 Supported controller YOKOGAWA ProSafe-RS Suitable I/O card: SAI143 SAV144 SAI533 |
Connection data | Connection 1 Connection in acc. with standard: based on IEC 60603-13 Connection method: Yokogawa, I/O cards compatible Number of connections: 1 Number of positions: 40 Tightening torque: 0.5 Nm (Screw connection) Insertion/withdrawal cycles: > 50 Pitch: 2.54 mm Connection 2 Connection in acc. with standard: based on IEC 60603-13 Connection method: Yokogawa, KS compatible Number of connections: 1 Number of positions: 40 Tightening torque: 0.5 Nm (Screw connection) Insertion/withdrawal cycles: > 50 Pitch: 2.54 mm |
Dimensions | Cable Length: 30 m |
Cable/line | Number of positions: 40 Shielded: yes Conductor type: Assembled, shielded, halogen-free round cable Conductor structure signal line: 7x 0.16 mm AWG signal line: 26 Conductor cross section: 40x 0.14 mm² Wire diameter incl. insulation: 1 mm ±0.03mm External cable diameter: 9.8 mm ±0.4mm Outer sheath, material: Halogen-free sheath External sheath, color: gray Conductor material: Tin-plated Cu litz wires Cable resistance: ⤠145 é/km Insulation resistance: ⥠20 Mé*km Smallest bending radius, fixed installation: 102 mm Smallest bending radius, movable installation: 184 mm Max. bending cycles: 5000 Halogen-free: yes Flame resistance: IEC 60332-1-2 (raw cable) VDE0842, Part332-1-2 (raw cable) IEC 60332-3-22 (raw cable) Resistance to oil: can withstand occasional splashes (raw cable) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Degree of protection (Installation location): ⥠IP54 (Installation location) Ambient temperature (operation): -40°C ... 70°C (fixed installation) -10°C ... 70°C (flexible installation) Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m |
Approvals | UKCA Certificate: UKCA-compliant |
Mounting | Mounting position: any |
Notes | General: For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
ECLASS | ECLASS-11.0: 27242292 ECLASS-13.0: 27242292 ECLASS-12.0: 27242292 |
ETIM | ETIM 9.0: EC002584 |
UNSPSC | UNSPSC 21.0: 32151600 |