PHOENIX CONTACT 2905008
PHOENIX CONTACTNot available

QUINT-PS/48DC/48DC/5 - DC/DC converter

Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (selective fuse breaking) technology, input: 48VDC, output: 48VDC/5A
Product Code: 2905008
Partner cod.: 2905008
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Input dataDC operation
Nominal input voltage range: 48 VDC
Input voltage range: 30 VDC ... 60 VDC
Wide-range input: no
Input voltage range DC: 30 VDC ... 60 VDC
Voltage type of supply voltage: DC
Inrush current: < 6 A (typical)
Inrush current integral (I2t): 0.3 A2s
Mains buffering time: typ. 10 ms (48VDC)
Current consumption: 7 A (48 V, IBOOST)
Reverse polarity protection: ≤ 30 VDC
Protective circuit: Transient surge protection; Varistor
Input fuse: 15 A (internal (device protection))
Output dataEfficiency: > 93 %
Output characteristic: U/I
Nominal output voltage: 48 VDC ±1%
Setting range of the output voltage (USet): 30 VDC ... 56 VDC (> 48VDC, constant capacity restricted)
Nominal output current (IN): 5 A (-25°C...60°C)
POWER BOOST (IBoost): 6.25 A (-25°C...40°C permanent, UOUT = 48VDC )
Selective Fuse Breaking (ISFB): 30 A (12ms)
Magnetic circuit breaker tripping: B2 / B4 / C2
Derating: 60°C ... 70°C (2.5%/K)
Feedback voltage resistance: 60 VDC
Protection against overvoltage at the output (OVP): < 60 VDC
Max. capacitive load: unlimited
Active current limitation: 7A
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 20 mVPP
Output power: 240 W
Peak switching voltages nominal load: < 10 mVPP (20MHz)
Maximum no-load power dissipation: 2.7 W
Power loss nominal load max.: 20 W
Rise time: < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal: DC OK active
Output description: UOUT > 0.9 x UN: High signal
Switching voltage range: 18 VDC ... 24 VDC
Maximum inrush current: < 20 mA (short-circuit-proof)
Signal: POWER BOOST, active
Output description: IOUT < IN: High signal
Switching voltage range: 18 VDC ... 24 VDC
Maximum inrush current: < 20 mA (short-circuit-proof)
Signal: U
Output description: UIN > 38.4 V: high signal
Switching voltage range: 18 VDC ... 24 VDC
Maximum inrush current: ≤ 20 mA (short-circuit-proof)
Connection dataInput
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Stripping length: 8 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Signal
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
SignalingTypes of signaling: LED
Active switching output
Relay contact
Signal output: DC OK active
Status display: "DC OK" LED green
Signal output: POWER BOOST, active
Status display: "BOOST" LED yellow/IOUT > IN :LED on
Signal output: U
Status display: LED "UIN < 38.4 V" yellow/UIN < 38.4 V DC: LED on
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 1.5 kV (type test)
1 kV (routine test)
1 kV (type test)
Product propertiesProduct type: DC/DC converters
MTBF (IEC 61709, SN 29500): > 872000 h (40°C)
Insulation characteristics
Protection class: III
Degree of pollution: 2
DimensionsWidth: 48 mm
Height: 130 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 0 mm / 0 mm (≤ 70°C)
Installation distance right/left (active): 15 mm / 15 mm (≤ 70°C)
Installation distance top/bottom: 50 mm / 50 mm (≤ 70°C)
Installation distance top/bottom (active): 50 mm / 50 mm (≤ 70°C)
Alternative assembly
Width: 122 mm
Height: 130 mm
Depth: 51 mm
MountingMounting type: DIN rail: 35 mm
Assembly instructions: alignable: PN ≥50%, 5mm horizontally, 15mm next to active components, 50mm vertically
alignable: PN <50%, 0mm horizontally, 40mm vertically top, 20 mm vertically bottom
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsHousing material: Metal
Type of housing: Aluminum (AlMg3)
Hood version: Galvanized sheet steel, free from chrome (VI)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsRail applications: EN50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV)
Standard - Electrical safety: EN60950-1/VDE0805 (SELV)
Standard – Safety extra-low voltage: EN60950-1 (SELV)
EN60204 (PELV)
Standard - Safe isolation: DINVDE0100-410
ApprovalsUL approvals: UL/C-UL listed UL508
UL/C-UL Recognized UL60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC dataEMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 2 kV (Test Level 3 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 2 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 1 kV (Test Level 3 - asymmetrical)
2 kV (Test Level 3 - asymmetrical)
Output: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
I/O/S: asymmetrical
Frequency range: 0.1 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Technical Specs
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Description
Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (selective fuse breaking) technology, input: 48 V DC, output: 48 V DC/5 A
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00041.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Data_sheet_03862.pdf

Manufacturer_declaration_03210.pdf

Manufacturer_declaration_04815.pdf

Manufacturer_declaration_05497.pdf

Manufacturer_declaration_15983.pdf

Package_slip_02086.pdf

Technical_drawing_40053.pdf

Various_00080.pdf

Various_00006.pdf