PHOENIX CONTACT 2866378
PHOENIX CONTACTNot available

QUINT-PS- 24DC/24DC/10 - DC/DC converter

QUINT DC/DC converter, primary-switched, input: 24 V DC, output: 24 V DC/10 A
Product Code: 2866378
Partner cod.: 2866378
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Input dataInput voltage: 24 VDC
Nominal input voltage range: 24 VDC
Input voltage range: 18 VDC ... 32 VDC
Wide-range input: yes
Input voltage range DC: 18 VDC ... 32 VDC
Voltage type of supply voltage: DC
Inrush current: < 20 A (typical)
Inrush current integral (I2t): 0.3 A2s
Frequency range DC: 0 Hz
Mains buffering time: > 3 ms (24VDC)
Current consumption: typ. 11.4 A (24V)
Protective circuit: Transient surge protection; Varistor
Typical response time: < 1 s
Input fuse: 25 A (slow-blow, internal)
Output dataEfficiency: > 88 %
Nominal output voltage: 24 VDC ±1%
Setting range of the output voltage (USet): 22.5 VDC ... 28.5 VDC (> 24 VDC, constant capacity restricted)
Nominal output current (IN): 10 A (-25°C...60°C)
Derating: 60°C ... 70°C (2.5%/K)
Feedback voltage resistance: 35 VDC
Protection against overvoltage at the output (OVP): < 35 VDC
Max. capacitive load: unlimited
Active current limitation: Approx. 18 A
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 60 mVPP
Output power: 240 W
Maximum no-load power dissipation: < 2 W
Power loss nominal load max.: < 28 W
Rise time: < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal: DC OK active
Output description: UOUT > 21.5 V: High signal
Maximum switching voltage: ≤ 24 VDC
Output voltage: + 24 VDC
Continuous load current: ≤ 40 mA
Signal: DC OK floating
Output description: UOUT > 21.5 V: Contact closed
Maximum switching voltage: ≤ 30 V AC/DC
Continuous load current: ≤ 1 A
Connection dataInput
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Pluggable screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Signal
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
SignalingTypes of signaling: LED
Active switching output
Operating voltage display: Green LED
Signal output: DC OK active
Status display: "DC OK" LED green
Signal output: DC OK floating
Status display: "DC OK" LED green
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 1 kV (routine test)
1.5 kV (type test)
Product propertiesProduct type: DC/DC converters
MTBF (IEC 61709, SN 29500): > 500000 h
Insulation characteristics
Protection class: III
Degree of pollution: 2
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/43003ef938a2ca46b8d73f515a6d762f/-S204x204-FJPG
Width: 80 mm
Height: 130 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 0 mm / 0 mm (≤ 70°C)
Installation distance right/left (active): 15 mm / 15 mm (≤ 70°C)
Installation distance top/bottom: 50 mm / 50 mm (≤ 70°C)
Installation distance top/bottom (active): 50 mm / 50 mm (≤ 70°C)
Alternative assembly
Width: 122 mm
Height: 130 mm
Depth: 83 mm
MountingAssembly instructions: alignable: horizontally 0mm, vertically 50mm
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsHousing material: Metal
Type of housing: AluNox (AlMg1)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsStandard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV)
Standard - Electrical safety: EN60950-1/VDE0805 (SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment: EN50178
Standard – Safety extra-low voltage: EN60950-1 (SELV)
EN60204 (PELV)
Standard - Safe isolation: DINVDE0100-410
Standard - Safety of transformers: EN61558-2-17
ApprovalsShipbuilding approval: DNVGL (EMCA), ABS
UL approvals: UL/C-UL listed UL508
UL/C-UL Recognized UL60950-1
UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
EMC dataNoise immunity: EN 61000-6-2:2005
Electromagnetic compatibility: Conformance with EMC directive 89/336/EC
Electrostatic discharge
Standards/regulations: EN61000-4-2
Housing: Level 3
Electrostatic discharge​
Contact discharge: 8 kV
Discharge in air: 8 kV
Comments: Criterion B
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 2 GHz
Test field strength: 10 V/m
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 2 kV (Level 3 - asymmetrical)
Output: 2 kV (Level 3 - asymmetrical)
Signal: 1 kV (Level 2 - asymmetrical)
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
I/O/S: Level 3 - asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V
Voltage dips
Standards/regulations: EN61000-4-11
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Technical Specs
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_01369.pdf

Data_sheet_03635.pdf

Manual_00213.pdf

Manufacturer_declaration_03211.pdf

Manufacturer_declaration_04705.pdf

Manufacturer_declaration_05499.pdf

Manufacturer_declaration_15310.pdf

Package_slip_02073.pdf

Technical_drawing_39041.pdf

Various_00080.pdf

Various_00006.pdf