Industrial Automation
Input data | Input voltage: 24 VDC Nominal input voltage range: 24 VDC Input voltage range: 18 VDC ... 32 VDC Wide-range input: yes Input voltage range DC: 18 VDC ... 32 VDC Voltage type of supply voltage: DC Inrush current: < 20 A (typical) Inrush current integral (I2t): 0.3 A2s Frequency range DC: 0 Hz Mains buffering time: > 3 ms (24VDC) Current consumption: typ. 11.4 A (24V) Protective circuit: Transient surge protection; Varistor Typical response time: < 1 s Input fuse: 25 A (slow-blow, internal) |
Output data | Efficiency: > 88 % Nominal output voltage: 24 VDC ±1% Setting range of the output voltage (USet): 22.5 VDC ... 28.5 VDC (> 24 VDC, constant capacity restricted) Nominal output current (IN): 10 A (-25°C...60°C) Derating: 60°C ... 70°C (2.5%/K) Feedback voltage resistance: 35 VDC Protection against overvoltage at the output (OVP): < 35 VDC Max. capacitive load: unlimited Active current limitation: Approx. 18 A Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 2 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ±10 %) Residual ripple: < 60 mVPP Output power: 240 W Maximum no-load power dissipation: < 2 W Power loss nominal load max.: < 28 W Rise time: < 2 ms (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK active Output description: UOUT > 21.5 V: High signal Maximum switching voltage: ⤠24 VDC Output voltage: + 24 VDC Continuous load current: ⤠40 mA Signal: DC OK floating Output description: UOUT > 21.5 V: Contact closed Maximum switching voltage: ⤠30 V AC/DC Continuous load current: ⤠1 A |
Connection data | Input Connection method: Pluggable screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 7 mm Screw thread: M3 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Output Connection method: Pluggable screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Stripping length: 7 mm Screw thread: M3 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Signal Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Screw thread: M3 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm |
Signaling | Types of signaling: LED Active switching output Operating voltage display: Green LED Signal output: DC OK active Status display: "DC OK" LED green Signal output: DC OK floating Status display: "DC OK" LED green |
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 1 kV (routine test) 1.5 kV (type test) |
Product properties | Product type: DC/DC converters MTBF (IEC 61709, SN 29500): > 500000 h Insulation characteristics Protection class: III Degree of pollution: 2 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/43003ef938a2ca46b8d73f515a6d762f/-S204x204-FJPG Width: 80 mm Height: 130 mm Depth: 125 mm Installation dimensions Installation distance right/left: 0 mm / 0 mm (⤠70°C) Installation distance right/left (active): 15 mm / 15 mm (⤠70°C) Installation distance top/bottom: 50 mm / 50 mm (⤠70°C) Installation distance top/bottom (active): 50 mm / 50 mm (⤠70°C) Alternative assembly Width: 122 mm Height: 130 mm Depth: 83 mm |
Mounting | Assembly instructions: alignable: horizontally 0mm, vertically 50mm Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No |
Material specifications | Housing material: Metal Type of housing: AluNox (AlMg1) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K) Ambient temperature (storage/transport): -40°C ... 85°C Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and regulations | Standard â Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV) Standard - Electrical safety: EN60950-1/VDE0805 (SELV) Standard â Protection against shock currents, basic requirements for protective separation in electrical equipment: EN50178 Standard â Safety extra-low voltage: EN60950-1 (SELV) EN60204 (PELV) Standard - Safe isolation: DINVDE0100-410 Standard - Safety of transformers: EN61558-2-17 |
Approvals | Shipbuilding approval: DNVGL (EMCA), ABS UL approvals: UL/C-UL listed UL508 UL/C-UL Recognized UL60950-1 UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D |
EMC data | Noise immunity: EN 61000-6-2:2005 Electromagnetic compatibility: Conformance with EMC directive 89/336/EC Electrostatic discharge Standards/regulations: EN61000-4-2 Housing: Level 3 Electrostatic dischargeâ Contact discharge: 8 kV Discharge in air: 8 kV Comments: Criterion B Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 2 GHz Test field strength: 10 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: 2 kV (Level 3 - asymmetrical) Output: 2 kV (Level 3 - asymmetrical) Signal: 1 kV (Level 2 - asymmetrical) Surge voltage load (surge) Standards/regulations: EN61000-4-5 Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ I/O/S: Level 3 - asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V Voltage dips Standards/regulations: EN61000-4-11 Emitted interference Standards/regulations: EN61000-6-3 Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential |
ECLASS | ECLASS-11.0: 27040701 ECLASS-12.0: 27040701 ECLASS-13.0: 27040701 |
ETIM | ETIM 9.0: EC002540 |
UNSPSC | UNSPSC 21.0: 39121000 |
Description other products