Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Signal duplicator Product family: MINI Analog Pro No. of channels: 2 Type: Signal conditioner Configuration: DIP switches Software App Insulation characteristics: GBStandard Overvoltage category: II Pollution degree: 2 |
System properties | Functionality Configuration: DIP switches Software App |
Electrical properties | No. of channels: 2 Electrical isolation: 4-way isolation Step response (0â99%): 140 ms (15 Hz sample rate) 45 ms (60Hz sample rate) 25 ms (240Hz sample rate, can only be set via software) Maximum temperature coefficient: 0.01 %/K Maximum transmission error: 0.05 % (of final value) Electrical isolation Input/output/power supply Rated insulation voltage: 300 Vrms Test voltage: 3 kV AC (50Hz, 60s) Insulation: Reinforced insulation according to IEC/EN61010-1 Supply Nominal supply voltage: 24 VDC Supply voltage range: 9.6 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715) Typical current consumption: 55 mA (24VDC) 110 mA (12VDC) Power consumption: 1.5 W (at IOUT = 20 mA, 9.6 V DC, 600 é load) |
Input data | Signal: Voltage/current Number of inputs: 1 Configurable/programmable: Yes Voltage input signal: 0 V ... 10 V (via DIP switch) 2 V ... 10 V (via DIP switch) 0 V ... 5 V (via DIP switch) 1 V ... 5 V (via DIP switch) 0 V ... 12 V (can be set via software) Max. voltage input signal: 12 V Current input signal: 0 mA ... 20 mA (via DIP switch) 4 mA ... 20 mA (via DIP switch) 0 mA ... 10 mA (via DIP switch) 20 mA ... 0 mA (via DIP switch) 0 mA ... 24 mA (can be set via software) Max. current input signal: 24 mA Input resistance of voltage input: > 120 ké Input resistance current input: ~ 50 é (+0.7V for test diode) |
Output data | Signal: Voltage/current Number of outputs: 2 Voltage output signal: 0 V ... 10 V (via DIP switch) 2 V ... 10 V (via DIP switch) 0 V ... 5 V (via DIP switch) 1 V ... 5 V (via DIP switch) 0 V ... 10.5 V (can be set via software) Max. voltage output signal: ~ 12.3 V Non-load voltage: ⤠18.5 V Current output signal: 0 mA ... 20 mA (via DIP switch) 4 mA ... 20 mA (via DIP switch) 0 mA ... 10 mA (via DIP switch) 20 mA ... 0 mA (via DIP switch) 0 mA ... 21 mA (can be set via software) Max. current output signal: 24.6 mA Short-circuit current: ⤠25 mA Load/output load voltage output: ⥠10 ké Load/output load current output: ⤠600 é (per channel) Ripple: < 20 mVPP (600é) |
Connection data | Connection method: Screw connection Stripping length: 10 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 1.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule) Conductor cross section flexible: 0.14 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 (flexible) Tightening torque: 0.5 Nm ... 0.6 Nm |
Ex data | Ex installation (EPL): Gc Div.2 |
Interfaces | Data: IFS interface Connection method: Micro USB type B |
Signaling | Status display: Green LED (supply voltage) Error indication: Red LED |
Dimensions | Width: 6.2 mm Height: 109.81 mm Depth: 119.2 mm |
Material specifications | Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2 Housing material: PBT |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (not assessed by UL) Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: BVS 19 ATEX E 083 X UKCAEx(UKEX) Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: PxCIF21UKEX2905026X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx BVS 19.0072X CCC/China-Ex Identification: Ex nA IIC T4 Gc Certificate: NEPSIGYJ20.1318X UL, USA/Canada Identification: UL508 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC T6 Shipbuilding approval Certificate: DNV GL TAA000021E Rev. 1 EACEx Identification: ï 2Ex ec IIC T4 Gc Certificate: BY/112 02.01 TP012 103.01 00081 DNV GL data Temperature: B Humidity: B Vibration: A EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Comments: Safety measures must be taken to prevent electrostatic discharge. Electromagnetic HF field Designation: Electromagnetic RF field Standards/regulations: EN61000-4-3 Typical deviation from the measuring range final value: 0.2 % Fast transients (burst) Designation: Fast transients (burst) Standards/regulations: EN61000-4-4 Typical deviation from the measuring range final value: 0.1 % Surge current load (surge) Standards/regulations: EN61000-4-5 Conducted interference Designation: Conducted interferences Standards/regulations: EN61000-4-6 Typical deviation from the measuring range final value: 2.8 % |
Standards and regulations | Electrical isolation: 4-way isolation GBStandard Standards/regulations: GB3836.1 GB3836.8 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail. Mounting position: any |
ECLASS | ECLASS-11.0: 27210120 ECLASS-12.0: 27210120 ECLASS-13.0: 27210120 |
ETIM | ETIM 9.0: EC002653 |
UNSPSC | UNSPSC 21.0: 39121000 |
Description other products