Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2905196
PHOENIX CONTACTNot available

UM-D37M/16RSC-24DC/DO/C300/R - Active module

VARIOFACE 16-channel module intended for use with Honeywell® Experion C300 24V digital IOTA, right-hand version, 3 A, 120 V
Product Code: 2905196
Partner cod.: 2905196
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesProduct type: Interface module
Product family: VARIOFACE
No. of channels: 16
Operating mode: 100% operating factor
Mechanical service life: 2x 107 cycles
With components: yes
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
Electrical propertiesNo. of channels: 16
Supported controller HONEYWELL Experion PKS C300/C-Series
Suitable I/O card: TDOB01 (non-redundant)
TDOB11 (redundant)
TDOB51 (non-redundant)
TDOB61 (redundant)
Input dataNominal input voltage UN: 24 VDC
Input voltage range in reference to UN: 0.8 ... 1.1
Input voltage range: 19.2 VDC ... 26.4 VDC
Typical input current at UN: 7 mA
Typical response time: 5 ms
Typical release time: 15 ms
Protective circuit: Freewheeling diode; Freewheeling diode
Output dataSwitching
Contact switching type: 1changeover contact
Contact material: AgSnO
Maximum switching voltage: 120 V AC/DC
Minimum switching voltage: 12 V
Limiting continuous current: 3 A (fuse limited)
Min. switching current: 10 mA
Interrupting rating (ohmic load) max.: 72 W (24VDC)
20 W (48VDC)
18 W (60VDC)
23 W (110VDC)
360 VA (120VAC)
Error detection (line break / short-circuit): no
Connection dataController level
Connection method: D-SUB connector
Number of connections: 1
Number of positions: 37
Field level
Connection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Number of connections: 32
Conductor cross section rigid: 0.2 mm² ... 4 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 12
SignalingStatus display present: Yes, if the fuse fails
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/4024f08e621df1478259dfdf7f7e8bfb/-S204x204-FJPG
Width: 184 mm
Height: 142.3 mm
Depth: 64.7 mm
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 70°C
Ambient temperature (storage/transport): -40°C ... 75°C
Altitude: < 2000 m
Permissible humidity (operation): 90 %
Permissible humidity (storage/transport): 90 %
MountingMounting type: DIN rail mounting
NotesGeneral: Standard or halogen-free cables
For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met.
Technical Specs
ECLASSECLASS-11.0: 27141152
ECLASS-13.0: 27141152
ECLASS-12.0: 27141152
ETIMETIM 9.0: EC002780
UNSPSCUNSPSC 21.0: 39121400
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00005.pdf

Approvals_01560.pdf

Approvals_01561.pdf

Manufacturer_declaration_03295.pdf

Manufacturer_declaration_16007.pdf

Technical_drawing_40086.pdf