Product properties | IEC test classification: I / II I T1 / T2 T1 EN type: T1 / T2 T1 IEC power supply system: TN-S TT Type: DIN rail module, two-section, divisible Product type: Combination type Product family: SEC Family Number of positions: 1 Surge protection fault message: Optical, remote indicator contact Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) Indicator/remote signaling Connection name: Remote fault indicator contact Switching function: Changeover contact Operating voltage: 12 VAC ... 250 VAC 125 VDC (200 mA DC) Operating current: 10 mA AC ... 1 A AC 1 ADC (30VDC) |
Connection data | Connection method: Screw connection Fork-type cable lug Screw thread: M5 Tightening torque: 4.5 Nm Stripping length: 18 mm Conductor cross section flexible: 2.5 mm² ... 35 mm² 1.5 mm² ... 16 mm² Conductor cross section rigid: 2.5 mm² ... 35 mm² Conductor cross section AWG: 13 ... 2 Remote fault indicator contact Connection method: Plug-in/screw connection via COMBICON Screw thread: M2 Tightening torque: 0.25 Nm Stripping length: 7 mm Conductor cross section flexible: 0.14 mm² ... 1.5 mm² Conductor cross section rigid: 0.14 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/0c0666275718bf49a28c6b753cc8bc7c/-S204x204-FJPG Width: 35.6 mm Height: 95.2 mm Depth: 74.5 mm (incl. DIN rail 7.5mm) Horizontal pitch: 2 Div. |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA6.6-FR 20% GF PBT-FR Material group: I Housing material: PA 6.6-FR 20% GF PBT-FR |
Mechanical properties | Mechanical data Open side panel: No |
Protective circuit | Mode of protection: N-PE Direction of action: N-PE Nominal voltage UN: 240VAC (TN - only N-PE) 240VAC (TT - only N-PE) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 350 VAC Rated load current IL: 125 A (< 55°C) Residual current IPE: ⤠0.01 mA Nominal discharge current In (8/20) µs: 100 kA Impulse discharge current (10/350)µs, charge: 50 As Impulse discharge current (10/350)µs, specific energy: 2500 kJ/é Impulse discharge current (10/350)µs, peak value limp: 100 kA Follow current interrupt rating Ifi: 100 A Voltage protection level Up: ⤠1.5 kV Residual voltage Ures: ⤠1.5 kV (at In) ⤠1 kV (at 10 kA) ⤠0.9 kV (at 5 kA) ⤠0.8 kV (at 3kA) Front of wave sparkover voltage at 6 kV (1.2/50) µs: ⤠1.5 kV TOV behavior at UT: 1200 VAC (200ms / withstand mode) Response time tA: ⤠100 ns |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (only when all terminal points are used) Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
Approvals | UL specifications Maximum continuous operating voltage MCOV: 350 VAC Voltage protection rating VPR: 1200 V Nominal discharge current In: 20 kA Mode of protection: N-G Nominal voltage: 240VAC Power distribution system: Single phase Nominal frequency: 50/60 Hz SPD Type: 2CA UL indicator/remote signaling Operating voltage: 125 VAC AC operating current: 1 A AC UL connection data Tightening torque: 40 lbf-in. Conductor cross section AWG: 3 ... 2 |
Standards and regulations | Standards/specifications: IEC 61643-11 Note: 2011 EN 61643-11 Standards/specifications: EN61643-11 Note: 2012 |
Mounting | Mounting type: DIN rail: 35 mm |
ECLASS | ECLASS-11.0: 27130802 ECLASS-13.0: 27171201 |
ETIM | ETIM 9.0: EC000381 |