PHOENIX CONTACT 2905472
PHOENIX CONTACTNot available

FLT-SEC-P-T1-N/PE-350/100-FM - Type 1+2 combined lightning current and surge arrester

Plug-in lightning current arrester, in accordance with Type 1/Class I, for use in power supply networks between N and PE.
Product Code: 2905472
Partner cod.: 2905472
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesIEC test classification: I / II
I
T1 / T2
T1
EN type: T1 / T2
T1
IEC power supply system: TN-S
TT
Type: DIN rail module, two-section, divisible
Product type: Combination type
Product family: SEC Family
Number of positions: 1
Surge protection fault message: Optical, remote indicator contact
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Indicator/remote signaling
Connection name: Remote fault indicator contact
Switching function: Changeover contact
Operating voltage: 12 VAC ... 250 VAC
125 VDC (200 mA DC)
Operating current: 10 mA AC ... 1 A AC
1 ADC (30VDC)
Connection dataConnection method: Screw connection
Fork-type cable lug
Screw thread: M5
Tightening torque: 4.5 Nm
Stripping length: 18 mm
Conductor cross section flexible: 2.5 mm² ... 35 mm²
1.5 mm² ... 16 mm²
Conductor cross section rigid: 2.5 mm² ... 35 mm²
Conductor cross section AWG: 13 ... 2
Remote fault indicator contact
Connection method: Plug-in/screw connection via COMBICON
Screw thread: M2
Tightening torque: 0.25 Nm
Stripping length: 7 mm
Conductor cross section flexible: 0.14 mm² ... 1.5 mm²
Conductor cross section rigid: 0.14 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/0c0666275718bf49a28c6b753cc8bc7c/-S204x204-FJPG
Width: 35.6 mm
Height: 95.2 mm
Depth: 74.5 mm (incl. DIN rail 7.5mm)
Horizontal pitch: 2 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA6.6-FR 20% GF
PBT-FR
Material group: I
Housing material: PA 6.6-FR 20% GF
PBT-FR
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitMode of protection: N-PE
Direction of action: N-PE
Nominal voltage UN: 240VAC (TN - only N-PE)
240VAC (TT - only N-PE)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 350 VAC
Rated load current IL: 125 A (< 55°C)
Residual current IPE: ≤ 0.01 mA
Nominal discharge current In (8/20) µs: 100 kA
Impulse discharge current (10/350)µs, charge: 50 As
Impulse discharge current (10/350)µs, specific energy: 2500 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 100 kA
Follow current interrupt rating Ifi: 100 A
Voltage protection level Up: ≤ 1.5 kV
Residual voltage Ures: ≤ 1.5 kV (at In)
≤ 1 kV (at 10 kA)
≤ 0.9 kV (at 5 kA)
≤ 0.8 kV (at 3kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs: ≤ 1.5 kV
TOV behavior at UT: 1200 VAC (200ms / withstand mode)
Response time tA: ≤ 100 ns
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (only when all terminal points are used)
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (5 - 500 Hz/2.5 h/X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV: 350 VAC
Voltage protection rating VPR: 1200 V
Nominal discharge current In: 20 kA
Mode of protection: N-G
Nominal voltage: 240VAC
Power distribution system: Single phase
Nominal frequency: 50/60 Hz
SPD Type: 2CA
UL indicator/remote signaling
Operating voltage: 125 VAC
AC operating current: 1 A AC
UL connection data
Tightening torque: 40 lbf-in.
Conductor cross section AWG: 3 ... 2
Standards and regulationsStandards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130802
ECLASS-13.0: 27171201
ETIMETIM 9.0: EC000381
UNSPSCUNSPSC 21.0: 39121600
Description
Plug-in lightning current arrester, in accordance with Type 1/Class I, for use in power supply networks between N and PE.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Approvals_01864.pdf

Flyer_00002.pdf

Flyer_00001.pdf

Flyer_00003.pdf

Manufacturer_declaration_00788.pdf

Manufacturer_declaration_02049.pdf

Manufacturer_declaration_16046.pdf

Package_slip_00315.pdf

Product_information_00033.pdf

Product_information_00672.pdf

Technical_drawing_40149.pdf