PHOENIX CONTACT 2905629
PHOENIX CONTACTNot available

MINI MCR-2-RPSS-I-2I-PT - Repeater power supply

4-way power supply doubler with plug-in connection technology. HART-transparent, 0(4)mA...20mA input signal, 0(4)mA...20mA output signals. The device can be used in both signal and power supply doubler modes. Push-in connection technology.
Product Code: 2905629
Partner cod.: 2905629
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Product propertiesProduct type: Repeater power supplies
Product family: MINI Analog Pro
No. of channels: 2
Type: Signal conditioner
Configuration: DIP switches
Insulation characteristics: GBStandard
Overvoltage category: II
Pollution degree: 2
Electrical propertiesNo. of channels: 2
Electrical isolation: 4-way isolation
Limit frequency (3 dB): > 1 kHz
Signal transmission behavior: In=Out
Step response (10-90%): < 400 µs
Maximum temperature coefficient: 0.0075 %/K
Maximum transmission error: 0.05 % (of final value)
Electrical isolation Input/output/power supply
Rated insulation voltage: 300 Vrms
Test voltage: 3 kV AC (50Hz, 60s)
Insulation: Reinforced insulation according to IEC/EN61010-1
Supply
Nominal supply voltage: 24 VDC
Supply voltage range: 9.6 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715)
Typical current consumption: 40 mA (For 24VDC and in signal duplicator mode)
65 mA (For 24 V DC and in power supply duplicator mode)
75 mA (For 12 V DC and in signal duplicator mode)
130 mA (For 12 V DC and in power supply duplicator mode)
Power consumption: 1.6 W (at IOUT = 20 mA, 500 Ω load)
Input dataSignal: Current
Description of the input: Sensor circuit
Number of inputs: 1
Current input signal: 0 mA ... 20 mA (Signal duplicator mode)
4 mA ... 20 mA (Power supply and signal duplicator mode)
Input resistance current input: 90 Ω (+1.6V)
Transmitter supply voltage: > 19.5 V
Output dataSignal: Current
Number of outputs: 2
Non-load voltage: < 20 V
Current output signal: 0 mA ... 20 mA (Signal duplicator mode)
4 mA ... 20 mA (Power supply and signal duplicator mode)
Max. current output signal: 25 mA
Load/output load current output: ≤ 500 Ω (per channel)
Ripple: < 20 mVPP (500 Ω)
Connection dataConnection method: Push-in connection
Stripping length: 10 mm
Conductor cross section rigid: 0.2 mm² ... 2.5 mm² (with ferrule)
0.14 mm² ... 2.5 mm² (without ferrule)
Conductor cross section flexible: 0.14 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 12 (flexible)
Ex dataEx installation (EPL): Gc
Div.2
InterfacesData communication (bypass)
HART function: Yes
Limit frequency (3 dB):  1 kHz
SignalingStatus display: Green LED (supply voltage)
DimensionsWidth: 6.2 mm
Height: 109.81 mm
Depth: 119.2 mm
Material specificationsFire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2
Housing material: PBT
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (not assessed by UL)
Ambient temperature (operation): -40°C ... 70°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
ApprovalsCE
Certificate: CE-compliant
ATEX
Identification:  II 3 G Ex ec ic IIC T4 Gc
Certificate: BVS 19 ATEX E 047 X
UKCAEx(UKEX)
Identification:  II 3 G Ex ec ic IIC T4 Gc
Certificate: PxCIF21UKEX2902000X
IECEx
Identification: Ex ec ic IIC T4 Gc
Certificate: IECEx BVS 19.0041X
CCC/China-Ex
Identification: Ex nA ic IIC T4 Gc
UL, USA/Canada
Identification: UL508 Listed
Class I, Div. 2, Groups A, B, C, D T5
Class I, Zone 2, Group IIC T5
Shipbuilding approval
Certificate: DNV GL TAA000021E Rev. 1
EACEx
Identification:  2Ex ec ic IIC T4 Gc
Certificate: BY/112 02.01 TP012 103.01 00081
DNV GL data
Temperature: B
Humidity: B
Vibration: A
EMC: A
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Comments: Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation: Electromagnetic RF field
Standards/regulations: EN61000-4-3
Fast transients (burst)
Designation: Fast transients (burst)
Standards/regulations: EN61000-4-4
Surge current load (surge)
Standards/regulations: EN61000-4-5
Conducted interference
Designation: Conducted interferences
Standards/regulations: EN61000-4-6
Standards and regulationsElectrical isolation: 4-way isolation
GBStandard
Standards/regulations: GB3836.1
GB3836.4
GB3836.8
MountingMounting type: DIN rail mounting
Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail.
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27210120
ECLASS-12.0: 27210120
ECLASS-13.0: 27210120
ETIMETIM 9.0: EC002653
UNSPSCUNSPSC 21.0: 39121000
Description
4-way power supply doubler with plug-in connection technology. HART-transparent, 0(4) mA ... 20 mA input signal, 0(4) mA ... 20 mA output signals. The device can be used in both signal and power supply doubler modes. Push-in connection technology.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00128.pdf

Approvals_00172.pdf

Approvals_00173.pdf

Approvals_01328.pdf

Approvals_01329.pdf

Approvals_01441.pdf

Approvals_01442.pdf

Approvals_01944.pdf

Data_sheet_03877.pdf

Manual_00026.pdf

Manufacturer_declaration_01056.pdf

Manufacturer_declaration_01789.pdf

Manufacturer_declaration_16058.pdf

Manufacturer_declaration_17788.pdf

Package_slip_01622.pdf

Product_information_00033.pdf

Product_information_00057.pdf

Product_information_00675.pdf

Technical_drawing_40161.pdf