Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Limit value switch Product family: MINI Analog Pro No. of channels: 1 Type: Signal conditioner Configuration: DIP switches Software App Insulation characteristics: GBStandard Overvoltage category: II Pollution degree: 2 |
System properties | Functionality Configuration: DIP switches Software App |
Electrical properties | No. of channels: 1 Switching point accuracy: < 0.1 % Step response (0â99%): 300 ms 570 ms 380 ms 300 ms 570 ms Maximum temperature coefficient: 0.01 %/K Electrical isolation Input/output/power supply Rated insulation voltage: 300 Vrms Test voltage: 3 kV AC (50Hz, 60s) Insulation: Reinforced insulation according to IEC/EN61010-1 Supply Nominal supply voltage: 24 VDC Supply voltage range: 9.6 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715) Typical current consumption: 44 mA (12VDC) 22 mA (24VDC) Power consumption: 570 mW |
Input data | Signal Number of inputs: 1 Measurement Number of inputs: 1 Configurable/programmable: Yes Sensor types (RTD) that can be used: Pt, Ni, Cu sensors Sensor types that can be used (TC): B, E, J, K, N, R, S, T, L, U, A-1, A-2, A-3, M, L Available input sources: Resistance thermometers Thermocouples Temperature measuring range: -250°C ... 2500°C (RTD) ⥠20 K (RTD) Sensor type:: 500°C ... 1820°C -230°C ... 1000°C -210°C ... 1200°C -250°C ... 1372°C -200°C ... 1300°C -50°C ... 1768°C -50°C ... 1768°C -200°C ... 400°C -200°C ... 900°C -200°C ... 600°C 0°C ... 2500°C 0°C ... 1800°C 0°C ... 1800°C -200°C ... 100°C -200°C ... 800°C Sensor input current: ï» 200 µA (RTD) Max. permissible overall conductor resistance: ⤠25 é (Per line, RTD in 3- or 4-conductor technology) ⤠50 é (adjustable, RTD in 2-conductor technology) Linear resistance measuring range: 0 é ... 4000 é (RTD) Linear mV signal range: -500 mV ... 500 mV (RTD) Connection technology: 2-, 3-, 4-conductor |
Output data | Switching: Relay Number of outputs: 1 Contact switching type: 1 N/O contact Contact material: AgSnO2, hard gold-plated Maximum switching voltage: 250 VAC 30 VDC 240 VAC (UL) Limiting continuous current: 6 A AC 4 ADC Min. switching current: 100 mA (12VDC) Max. switching current: 6 A AC (250VAC) 4 ADC (30VDC) Mechanical service life: 2x 107 cycles Setting range of the response delay: 0 s ... 10 s (can be set freely via software) Internal hysteresis: can be set freely via software |
Connection data | Connection method: Push-in connection Stripping length: 10 mm Conductor cross section rigid: 0.2 mm² ... 2.5 mm² (with ferrule) 0.14 mm² ... 2.5 mm² (without ferrule) Conductor cross section flexible: 0.14 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 (flexible) |
Ex data | Ex installation (EPL): Gc Div.2 |
Interfaces | Data: IFS interface Connection method: Micro USB type B |
Signaling | Status display: Green LED (supply voltage) Yellow LED (switching output) Error indication: Red LED |
Dimensions | Width: 6.2 mm Height: 109.81 mm Depth: 119.2 mm |
Material specifications | Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2 Housing material: PBT |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (not assessed by UL) Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3G Ex ec ic nC IIC T4 Gc Certificate: BVS 18 ATEX E 071 X UKCAEx(UKEX) Identification: ï II 3 G Ex ec ic IIC T4 Gc Certificate: PxCIF21UKEX2905632X IECEx Identification: Ex ec ic nC IIC T4 Gc Certificate: IECEx BVS 18.0060X CCC/China-Ex Identification: Ex ic nA nC IIC T4 Gc UL, USA/Canada Identification: UL508 Listed Class I, Div. 2, Groups A, B, C, D T4A Class I, Zone 2, Group IIC T4A Shipbuilding approval Certificate: DNV GL TAA000021E Rev. 1 EACEx Identification: ï 2Ex ec ic nC IIC T4 Gc Certificate: BY/112 02.01 TP012 103.01 00081 DNV GL data Temperature: B Humidity: B Vibration: A EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 |
Standards and regulations | GBStandard Standards/regulations: GB3836.1 GB3836.4 GB3836.8 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail. Mounting position: any |
ECLASS | ECLASS-11.0: 27210120 ECLASS-12.0: 27210120 ECLASS-13.0: 27210120 |
ETIM | ETIM 9.0: EC002653 |
UNSPSC | UNSPSC 21.0: 39121000 |