PHOENIX CONTACT 2905871
PHOENIX CONTACT 2905871
PHOENIX CONTACTNot available

FLT-SEC-H-T1-3C-264/25-FM - Type 1+2 combined lightning current and surge arrester

Plug-in lightning current arrester, in accordance with Type 1/Class I, with integrated surge-proof fuse, for 3-phase power supply networks with combined PE and N installed in one conductor (L1, L2, L3, PEN).
Product Code: 2905871
Partner cod.: 2905871
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesGeneral
Note: Max. single impulse: 100 kA (8/20 µs)
SPD according to AS/NZS1768 Cat. C3
Product propertiesIEC test classification: I / II
I
T1 / T2
T1
EN type: T1 / T2
T1
IEC power supply system: TN-C
TT
Type: DIN rail module, two-section, divisible
Distance between live and grounded parts: 1 mm
Product type: Combination type
Product family: SEC Family
Number of positions: 3
Surge protection fault message: Optical, remote indicator contact
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Indicator/remote signaling
Connection name: Remote fault indicator contact
Switching function: Changeover contact
Operating voltage: 12 VAC ... 250 VAC
125 VDC (200 mA DC)
Operating current: 10 mA AC ... 1 A AC
1 ADC (30VDC)
Connection dataConnection method: Screw connection
Fork-type cable lug
Screw thread: M5
Tightening torque: 4.5 Nm
Stripping length: 18 mm
Conductor cross section flexible: 2.5 mm² ... 35 mm²
1.5 mm² ... 16 mm²
Conductor cross section rigid: 2.5 mm² ... 35 mm²
Conductor cross section AWG: 13 ... 2
Remote fault indicator contact
Connection method: Plug-in/screw connection via COMBICON
Screw thread: M2
Tightening torque: 0.25 Nm
Stripping length: 7 mm
Conductor cross section flexible: 0.14 mm² ... 1.5 mm²
Conductor cross section rigid: 0.14 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/00df403ad2b02f48acacde140c7d098a/-S204x204-FJPG
Width: 106.8 mm
Height: 167 mm
Depth: 74.5 mm (incl. DIN rail 7.5mm)
Horizontal pitch: 6 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6-FR 20% GF
PBT-FR
Material group: I
Housing material: PA 6.6-FR 20% GF
PBT-FR
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitMode of protection: L-PEN
Direction of action: 3L-N/PE
Nominal voltage UN: 240/415VAC (TN-C)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 264 VAC
Nominal discharge current In (8/20) µs: 25 kA
Maximum discharge current Imax (8/20) µs: 50 kA
Impulse discharge current (10/350)µs, charge: 12.5 As
Impulse discharge current (10/350)µs, specific energy: 160 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 25 kA
Total discharge current Itotal (10/350)µs: 75 kA
Follow current interrupt rating Ifi: 50 kA
Short-circuit current rating ISCCR: 50 kA
Voltage protection level Up: ≤ 1.5 kV
Residual voltage Ures: ≤ 1.5 kV (at In)
≤ 2.5 kV (at 50kA)
≤ 1.2 kV (at 12.5kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 2.5 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs: ≤ 1.5 kV
TOV behavior at UT: 415 VAC (5s / withstand mode)
460 VAC (120min / withstand mode)
Response time tA: ≤ 100 ns
Additional technical data
Maximum continuous voltage UC: 275 VAC
Short-circuit current rating ISCCR: 100 kA
Follow current interrupt rating Ifi: 100 kA
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (only when all terminal points are used)
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 4000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Standards and regulationsStandards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130802
ECLASS-13.0: 27171201
ETIMETIM 9.0: EC000381
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Flyer_00001.pdf

Flyer_00003.pdf

Flyer_00002.pdf

Manufacturer_declaration_00819.pdf

Manufacturer_declaration_02050.pdf

Package_slip_00297.pdf

Product_information_00033.pdf

Product_information_00680.pdf

Technical_drawing_40197.pdf