VAL-US 60/O-FM - Type 2 surge protection device
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Product properties | IEC test classification: II T2 EN type: T2 Type: DIN rail module, two-section, divisible Product type: Surge protection for NEMA power supply units Product family: VALVETRAB MS Number of positions: 1 Surge protection fault message: Optical, remote indicator contact Insulation characteristics Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) Indicator/remote signaling Connection name: Remote fault indicator contact Switching function: Changeover contact Operating voltage: 5 VAC ... 250 VAC 125 VAC (UL) 125 VDC (200 mA DC) Operating current: 5 mA AC ... 1.5 A 1 A (UL) 1 A (30VDC) |
Connection data | Connection method: Biconnect terminal blocks Screw connection Screw thread: M5 Tightening torque: 3 Nm ... 4.5 Nm (UL) 27 lbf-in. ... 40 lbf-in. (UL) 4.5 Nm 30 lbf-in. (UL) Stripping length: 16 mm Conductor cross section flexible min.: 1.5 mm² Conductor cross section flexible max.: 25 mm² Conductor cross section, rigid min.: 1.5 mm² Conductor cross section, rigid max.: 35 mm² Conductor cross section AWG: 15 ... 2 (IEC) 14 ... 2 (UL) 15 ... 2 14 ... 2 (UL) Remote fault indicator contact Connection method: Screw connection Screw thread: M2 Tightening torque: 0.25 Nm Stripping length: 7 mm Conductor cross section flexible min.: 0.14 mm² Conductor cross section flexible max.: 1.5 mm² Conductor cross section, rigid min.: 0.14 mm² Conductor cross section, rigid max.: 1.5 mm² Conductor cross section AWG: 28 ... 16 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/223151a3e00d8f4a91f665d463f321ae/-S204x204-FJPG Width: 17.6 mm Height: 77.1 mm Depth: 89.2 mm |
Material specifications | Flammability rating according to UL 94: V0 Housing material: PBT |
Protective circuit | Mode of protection: L-PEN (L+) - (L-) (L-) - PE (L+) - PE Direction of action: L-N / L-PEN Nominal voltage UN: 60 VDC -48 VDC (RRH) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 75 VAC 100 VDC Maximum continuous operating voltage UC (L-N): 75 VAC 100 VDC Maximum continuous operating voltage UC (L-PEN): 75 VAC 100 VDC Rated load current IL: 80 A Residual current IPE: ⤠0.45 mA Standby power consumption PC: ⤠35 mVA Nominal discharge current In (8/20) µs: 15 kA Nominal discharge current In (8/20) µs (L-N): 15 kA Nominal discharge current In (8/20) µs (L-PEN): 15 kA Maximum discharge current Imax (8/20) µs: 40 kA Maximum discharge current Imax (8/20) µs (L-N): 40 kA Maximum discharge current Imax (8/20) µs (L-PEN): 40 kA Short-circuit current rating ISCCR: 25 kA Voltage protection level Up: ⤠0.55 kV Voltage protection level Up (L-N): ⤠0.55 kV Voltage protection level Up (L-PEN): ⤠0.55 kV Residual voltage Ures: ⤠0.55 kV (at In) ⤠0.425 kV (at 10 kA) ⤠0.325 kV (at 5 kA) ⤠0.275 kV (at 3kA) TOV behavior at UT: 100 VAC (5s / withstand mode) TOV behavior at UT (L-N): 100 VAC (5s / withstand mode) TOV behavior at UT (L-PEN): 100 VAC (5s / withstand mode) Response time tA: ⤠25 ns Response time tA (L-N): ⤠25 ns Response time tA (L-PEN): ⤠25 ns Max. backup fuse with V-type through wiring: 80 A AC (gG) Max. backup fuse with branch wiring: 125 A AC (gG) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (only when all terminal points are used) Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: max. 2000 m Permissible humidity (operation): 5 % ... 95 % Shock (operation): 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
Approvals | UL specifications Maximum continuous operating voltage MCOV: 75 VAC Maximum continuous operating voltage MCOV (L-N): 75 VAC Maximum continuous operating voltage MCOV (L-G): 75 VAC Maximum continuous operating voltage MCOV (L+) - (L-): 100 VDC Maximum continuous operating voltage MCOV (L+/L-) - G: 100 VDC Voltage protection rating VPR: 500 V Voltage protection rating VPR (L-N): 0.5 kV Voltage protection rating VPR (L+) - (L-): 0.33 kV Voltage protection rating VPR (L+/L-) -G: 0.33 kV Nominal discharge current In: 10 kA Nominal discharge current In (L-N): 10 kA Nominal discharge current In (L+) - (L-): 10 kA Nominal discharge current In (L+/L-) - G: 10 kA Mode of protection: L-L L-G (L+) - (L-) (L+) - G (L-) - G Nominal voltage: 60 VDC Power distribution system: Single phase Measured limiting voltage MLV: 630 V Measured limiting voltage MLV (L-N): 630 V SPD Type: 4CA UL indicator/remote signaling Operating voltage: 125 VAC AC operating current: 1 A AC UL connection data Tightening torque: 30 lbf-in. Conductor cross section AWG: 14 ... 2 |
Standards and regulations | Air clearances and creepage distances Standards/regulations: EN61643-11 / UL840 Standards/specifications: EN61643-11/A11 Note: 2007 |
Mounting | Mounting type: DIN rail: 35 mm |
ECLASS | ECLASS-11.0: 27130805 ECLASS-13.0: 27171202 |
ETIM | ETIM 8.0: EC000941 |
UNSPSC | UNSPSC 21.0: 39121600 |