PHOENIX CONTACT 2906281
PHOENIX CONTACTNot available

VAL-MS-T1/T2 48/12.5/O - Lightning/surge arrester type 1/2

Universal varistor-based plug-in lightning/surge arrester for 1-phase power supply networks with common N and PE (2-conductor system: L1, PEN), with remote indication contact.
Product Code: 2906281
Partner cod.: 2906281
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesIEC test classification: I / II
T1 / T2
I
EN type: T1 / T2
IEC power supply system: DC
Type: DIN rail module, two-section, divisible
Product type: Arrester combination
Product family: VALVETRAB MS
Number of positions: 1
Surge protection fault message: Optical, remote indicator contact
Insulation characteristics
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: Screw connection
Screw thread: M5
Tightening torque: 4.5 Nm
30 lbf-in. (UL)
Stripping length: 16 mm
Conductor cross section flexible: 1.5 mm² ... 25 mm²
Conductor cross section rigid: 1.5 mm² ... 35 mm²
Conductor cross section AWG: 15 ... 2
10 ... 2 (UL)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/fb5aaed635785642b4d0453ad7bee719/-S204x204-FJPG
Width: 17.5 mm
Height: 77.1 mm
Depth: 89.2 mm
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V0
Housing material: PBT
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitMode of protection: L-PEN
(L+) - (L-)
(L-) - PE
(L+) - PE
Direction of action: L-N / L-PEN
Nominal voltage UN: -48 VDC (RRH)
60 VDC
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 75 VAC
100 VDC
Rated load current IL: 80 A
Residual current IPE: ≤ 0.6 mA
Standby power consumption PC: ≤ 45 mVA
Nominal discharge current In (8/20) µs: 12.5 kA
Maximum discharge current Imax (8/20) µs: 30 kA
Impulse discharge current (10/350)µs, charge: 6.25 As
Impulse discharge current (10/350)µs, specific energy: 39 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 12.5 kA
Impulse discharge current (10/350)µs (L-N), charge: 6.25 As
Impulse discharge current (10/350) µs (L-N), specific energy: 39 kJ/Ω
Impulse discharge current (10/350)µs (L-N), peak current value Iimp: 12.5 kA
Short-circuit current rating ISCCR: 25 kA
Voltage protection level Up: ≤ 0.4 kV
Voltage protection level Up (L-N): ≤ 0.4 kV
Voltage protection level Up (L-PEN): ≤ 0.4 kV
Residual voltage Ures: ≤ 0.4 kV (at In)
≤ 0.35 kV (at 10 kA)
≤ 0.3 kV (at 5 kA)
≤ 0.275 kV (at 4 kA)
≤ 0.25 kV (at 3kA)
TOV behavior at UT: 100 VAC (5s / withstand mode)
130 VDC (5s / withstand mode)
Response time tA: ≤ 25 ns
Response time tA (L-N): ≤ 25 ns
Response time tA (L-PEN): ≤ 25 ns
Max. backup fuse with V-type through wiring: 80 A AC (gG - 16 mm²)
Max. backup fuse with branch wiring: 160 A AC (gG)
Additional technical data
Maximum discharge current Imax (8/20) µs: 65 kA
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (only when all terminal points are used)
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: max. 2000 m
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV: 75 VAC
Maximum continuous operating voltage MCOV (L-N): 75 VAC
Maximum continuous operating voltage MCOV (L-G): 75 VAC
Maximum continuous operating voltage MCOV (L+) - (L-): 100 VDC
Maximum continuous operating voltage MCOV (L+/L-) - G: 100 VDC
Voltage protection rating VPR: 400 V
Voltage protection rating VPR (L-N): 400 V
Nominal discharge current In: 20 kA
Nominal discharge current In (L-G): 20 kA
Nominal discharge current In (L+) - (L-): 20 kA
Mode of protection: L-L
L-G
(L+) - (L-)
(L+) - G
(L-) - G
Nominal voltage: 60 VDC
Power distribution system: Single phase
Measured limiting voltage MLV: 1240 V
Measured limiting voltage MLV (L-G): 1240 V
Measured limiting voltage MLV (L+) - (L-): 1230 V
SPD Type: 1CA
UL connection data
Tightening torque: 30 lbf-in.
Conductor cross section AWG: 10 ... 2
Standards and regulationsAir clearances and creepage distances
Standards/regulations: EN61643-11 / UL840
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130802
ECLASS-13.0: 27171201
ETIMETIM 9.0: EC000381
UNSPSCUNSPSC 21.0: 39121600
Description
Universal varistor-based plug-in lightning/surge arrester for 1-phase power supply networks with common N and PE (2-conductor system: L1, PEN), with remote indication contact.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Approvals_01874.pdf

Flyer_00002.pdf

Flyer_00001.pdf

Manufacturer_declaration_00079.pdf

Manufacturer_declaration_02907.pdf

Package_slip_00057.pdf

Technical_drawing_40263.pdf