PLT-T3-IT-230-P - Type 3 surge protection plug

Replacement plug for device protection in IT systems from the PLUGTRAB product series. 230 V nominal voltage.
Product Code: 2906451
Partner cod.: 2906451
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC power supply system: IT
Type: Male
Product type: Replacement plug
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
IEC test classification: III
T3
EN type: T3
Number of ports: One
Connection dataConnection method: pluggable
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/ccdf98a6bdd749498f6c4126115c9c5f/-S204x204-FJPG
Width: 17.7 mm
Height: 45 mm
Depth: 52 mm
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6
Housing material: PA 6.6
Protective circuitMode of protection: L-L
L-PE
Direction of action: 1L-N & N-PE
Nominal voltage UN: 230VAC(IT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous operating voltage UC (L-L): 275 VAC
Maximum continuous operating voltage UC (L-N): 275 VAC
Maximum continuous operating voltage UC (L-PE): 440 VAC
Rated load current IL: 16 A (60°C)
Residual current IPE: ≤ 1 µA
Standby power consumption PC: ≤ 340 mVA
Reference test voltage UREF: 255 VAC
Nominal discharge current In (8/20) µs: 3 kA
Maximum discharge current Imax (8/20) µs: 8 kA
Combination wave UOC: 6 kV
Voltage protection level Up (L-L): ≤ 1.2 kV
Voltage protection level Up (L-N): ≤ 1.2 kV
Voltage protection level Up (L-PE): ≤ 1.5 kV
Residual voltage at Iamax, (L-PE): ≤ 1 kV (at 1 kA)
≤ 1.5 kV (at UOC)
TOV behavior at UT (L-PE): 440 VAC (120min / withstand mode)
1455 VAC (200ms / safe failure mode)
Response time tA (L-N): ≤ 25 ns
Response time tA (L-PE): ≤ 100 ns
Max. required back-up fuse: 16 A (MCB B)
Short-circuit current rating ISCCR: 1.5 kA AC
Max. backup fuse with branch wiring: 16 A (MCB B)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 70°C
Ambient temperature (storage/transport): -40°C ... 70°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Standards and regulationsStandards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2012
MountingMounting type: on base element
Technical Specs
ECLASSECLASS-11.0: 27130890
ECLASS-13.0: 27171292
ETIMETIM 9.0: EC002496