Industrial Automation
TC-D37SUB-DO16-PS-P-UNI - Module carrier
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | General: For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Product properties | Product type: Module carrier Insulation characteristics: Air clearances and creepage distances Overvoltage category: II Pollution degree: 2 |
Electrical properties | Max. permissible current: ± 1 A (per signal path) Nominal voltage UN: < 50 VDC (Per signal/channel) Supported controller universal Suitable I/O card: universal Supply Designation: Device supply Fuse: 2x 2.5 A (designed for redundancy operation) Input voltage range: 19.2 VDC ... 30 VDC Input current: ⤠2 A |
Connection data | Voltage supply X20 Connection method: Screw connection Stripping length: 7 mm Number of connections: 1 Number of positions: 6 Conductor cross section rigid: 0.14 mm² ... 2.5 mm² Conductor cross section flexible: 0.14 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 Controller X1 Connection method: D-SUB pin strip Number of connections: 1 Number of positions: 37 CH1...CH16 cable sets Connection method: PTSM connector Number of positions: 4 |
Dimensions | Width: 147 mm Height: 170 mm Depth: 159.5 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP00 Ambient temperature (operation): -20°C ... 60°C (Please observe module specifications) Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (Above sea level) Permissible humidity (operation): 5 % ... 95 % (non-condensing) Shock: 15g, according to IECý60068-2-27 Vibration (operation): 2g, according to IEC 60068-2-6 |
Approvals | UL, USA/Canada Identification: UL 61010 Listed Class I, Div. 2, Groups A, B, C, D T4 Class I, Zone 2, Group IIC |
Standards and regulations | Air clearances and creepage distances Standards/regulations: DINEN60664-1:2008 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: No end clamp Mounting position: any |
ECLASS | ECLASS-11.0: 27141152 ECLASS-12.0: 27141152 ECLASS-13.0: 27141152 |
ETIM | ETIM 8.0: EC002780 |
UNSPSC | UNSPSC 21.0: 39121400 |
Description other products