Industrial Automation
PLC-ASC-UI-OUT - Analog module
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | General: For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Product properties | Product type: Extension module Product family: PLC logic Operating mode: 100% operating factor Insulation characteristics Insulation: Basic insulation Insulation characteristics: Air clearances and creepage distances Insulation: Basic insulation Overvoltage category: III Pollution degree: 2 |
Electrical properties | Air clearances and creepage distances Rated insulation voltage: 50 V Rated surge voltage: 0.5 kV Supply Rated control circuit supply voltage US: 24 VDC Rated control supply voltage range with reference to US: 0.8 ... 1.1 Rated control supply current IS: ⤠28 mA Protective circuit: Reverse polarity protection Surge protection |
Input data | Digital input Rated actuating voltage UC: 24 VDC Rated actuating current IC: ⤠1 mA |
Output data | Analog Output name: Analog voltage output Number of outputs: 1 Voltage output signal: 0 V ... 10 V 2 V ... 10 V Maximum output voltage: 12.3 V Ripple: < 20 mVPP Load/output load voltage output: 10 ké Surge voltage protection: > 33 V Maximum transmission error: 1 % Resolution: 10 bit (scaled to 0 to 1000) Protective circuit: Surge protection Analogâ Output name: Analog output for current Number of outputs: 1 Current output signal: 0 mA ... 20 mA 4 mA ... 20 mA Maximum output current: 24.6 mA Load/output load current output: 500 é (20mA) Surge voltage protection: > 33 V Maximum transmission error: 1 % Resolution: 10 bit Protective circuit: Surge protection |
Connection data | Connection method: Screw connection Stripping length: 8 mm Screw thread: M3 Conductor cross section rigid: 0.14 mm² ... 2.5 mm² Conductor cross section flexible: 0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² (Single ferrule) 2x 0.5 mm² ... 1.5 mm² (TWIN ferrule) Conductor cross section AWG: 26 ... 14 Tightening torque: 0.45 Nm ... 0.55 Nm (Usually these terminal blocks must be supported during conductor connection (held by one hand, supported on the housing)) |
Signaling | Operating voltage display: Green LED Error indication: Red LED |
Dimensions | Width: 6.2 mm Height: 80 mm Depth: 86 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 50°C Ambient temperature (storage/transport): -20°C ... 70°C |
Approvals | CE Certificate: CE-compliant UL, USA/Canada Identification: UL508 Listed |
Standards and regulations | Air clearances and creepage distances Standards/regulations: DINEN50178 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: in rows with zero spacing Mounting position: any |
ECLASS | ECLASS-11.0: 27242201 ECLASS-13.0: 27242201 ECLASS-12.0: 27242201 |
ETIM | ETIM 9.0: EC001420 |
UNSPSC | UNSPSC 21.0: 32151600 |