Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2906996
PHOENIX CONTACT 2906996
PHOENIX CONTACTNot available

QUINT4-UPS/24DC/24DC/5/EC - Uninterruptible power supply

QUINTUSV, IQTechnology, EtherCAT®, DIN rail mounting, Screw connection, input: 24 VDC, output: 24 VDC / 5 A, charging current: 1.5 A
Product Code: 2906996
Partner cod.: 2906996
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Input dataInput voltage: 24 VDC
Input voltage range: 18 VDC ... 30 VDC
18 VDC ... 32 VDC
Electric strength, max.: 35 VDC (Protected against polarity reversal)
Internal input fuse: no
Voltage type of supply voltage: DC
Inrush current: ≤ 7 A (≤4ms)
Reverse polarity protection: yes
Fixed backup threshold: 22 VDC
Dynamic activation threshold: > 1V / 100ms
Switch-on time: max. 3 s
Switch-on time during battery operation (Bat.-Start): 8 s
Voltage drop, input/output: 0.3 VDC
Current consumption IN (UN, IOUT = IN, Icharge = 0): 5.1 A
Current consumption Imax (UN, IOUT = IStat.Boost, Icharge = max): 8.3 A
Current consumption INo-Load(UN, IOUT = 0, Icharge = 0): 105 mA
Current consumption Icharge (UN, IOUT = 0, Icharge = max): 1.9 A
Power consumption PN (UN, IOUT = IN, Icharge = 0): 123 W
Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max): 213 W
Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0): 2.5 W
Power consumption Pcharge (UN, IOUT = 0, Icharge = max): 44 W
Output dataEfficiency: typ. 97 %
Number of outputs: 1
Short-circuit-proof: yes
No-load proof: yes
Switch-over time: 0 ms
UPS connection in parallel: no
UPS connection in series: no
Energy storage device connection in parallel: Yes, 5 (observe line protection)
Energy storage device connection in series: no
Mains operation
Output voltage: 24 VDC (UOUT = UIN - 0.3VDC)
Output voltage range: 18 VDC ... 30 VDC (UOut = UIn - 0.3 V DC)
18 VDC ... 32 VDC
Output current IN: 5 A
Static Boost (IStat.Boost): 6.25 A
Dynamic Boost (IDyn.Boost): 10 A (5 s)
Selective Fuse Breaking (ISFB): 30 A (15 ms)
Output power POUT (UN, IOUT = IN): 120 W
Output power POUT (UN, IOUT = Istat.Boost): 155 W
Output power POUT (UN, IOUT = Idyn.Boost): 240 W (5 s)
Power dissipation No load (UN, IOut = 0, ICharge = 0): 3 W
Power dissipation Nominal load (UN, IOut = IN, ICharge = 0): 4 W
Battery operation
Output voltage: 24 VDC (UOUT = UBAT - 0.3VDC)
Output voltage range: 19 VDC ... 32 VDC (UOUT = UBAT - 0.3VDC)
Output current IN: 5 A
Static Boost (IStat.Boost): 6.25 A
Dynamic Boost (IDyn.Boost): 10 A (5 s)
Selective Fuse Breaking (ISFB): 30 A (15 ms)
Output power POUT (UN, IOUT = IN): 120 W
Output power POUT (UN, IOUT = Istat.Boost): 150 W
Output power POUT (UN, IOUT = Idyn.Boost): 240 W (5 s)
Energy storageEnd-of-charge voltage: 32 VDC
End-of-charge voltage (temperature-compensated): 25 VDC ... 32 VDC
Charging current (configurable): max. 1.5 A
Nominal capacity (without additional charger): 0.8 Ah ... 30 Ah
Max. capacity: 40 Ah
Charging time: 2.5 h (3.4 Ah)
Buffer time: 25 min. (3.4 Ah)
Deep discharge protection (configurable): 19.2 VDC
Battery technology: VRLA, VRLA-WTR, LI-ION
Charge characteristic curve: IU0U
IQ-Technology: yes
Temperature sensor: yes
Temperature compensation (configurable): 42 mV/K
InterfacesInterface: EtherCAT®
Number of interfaces: 2
Connection method: RJ45
Locking: Locking clip
Transmission physics: Twisted-Pair
Features: Autonegotiation
Autocrossing
Half- or full-duplex
automatic recognition
Topology: Ring
Line
Transmission speed: 100 Mbps
Transmission length: max. 100 m
Cycle time: < 100 µs
Access time: ≤ 2 s
Supported protocols: CoE
Chipset: Renesas R-IN32M3
Electrical isolation: yes
Device ID: 2C5B74hex
Vendor ID: 84hex
SignalingLED signaling
Types of signaling: DC OK (green)
Alarm (red)
Bat.-Mode (yellow)
SOC (red, green)
Data (red, green)
Product propertiesProduct type: DC UPS
Product family: QUINTUSV
MTBF (IEC 61709, SN 29500): > 1189000 h (25°C)
> 736900 h (40°C)
> 372700 h (60°C)
Environmental protection directive: RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class: III (without PE)
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Time: 224011 h
DimensionsItem dimensions
Width: 35 mm
Height: 130 mm
Depth: 125 mm
125 mm (Device depth (DIN rail mounting))
Item dimensions with alternative mounting
Width: 123 mm
Height: 130 mm
Depth: 37 mm
Installation dimensions
Installation distance right/left (active): 5 mm / 5 mm (POut≥50%)
Installation distance right/left (passive): 0 mm / 0 mm (POut≥50%)
Installation distance right/left (active, passive): 0 mm / 0 mm (POut≤50%)
Installation distance top/bottom (active): 50 mm / 50 mm (POut≥50%)
Installation distance top/bottom (passive): 40 mm / 20 mm (POut≥50%)
Installation distance top/bottom (active, passive): 40 mm / 20 mm (POut≤50%)
MountingMounting type: DIN rail mounting
Mounting position: On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715
Material specificationsFlammability rating according to UL94 (housing / terminal blocks): V0
Housing material: Metal
Hood version: Stainless steel X6Cr17
Side element version: Aluminum AlMg3
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 4000 m
Climatic class: 3K3 (EN60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): 2.3g
Standards and regulationsOvervoltage category
EN 61010-1: II(≤4000m)
EN61010-2-201: II(≤4000m)
Protective extra-low voltage
Standard designation: Protective extra-low voltage
Standards/specifications: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
ApprovalsUL
Identification: UL/C-UL Listed UL61010-1
UL​
Identification: UL/C-UL Listed UL61010-2-201
UL​​
Identification: UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
CSA
Identification: CAN/CSA-C22.2 No.61010-1-12
CSA​
Identification: CAN/CSA-IEC 61010-2-201
CSA​​
Identification: CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
CB scheme
Identification: IEC 61010-1
CB scheme​
Identification: IEC 61010-2-201
DNV
Identification: Class Guideline DNVGL-CG-0339
Note: Location classes: TemperatureD (see Application/Limitation), HumidityB, VibrationA/C, EMCB
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Noise immunity: Immunity in accordance with EN61000-6-1 (residential), EN61000-6-2 (industrial), and EN61000-6-5 (power station equipment zone), IEC/EN61850-3 (power supply)
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion B
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
1 GHz ... 6 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 4 kV (Test Level 4 - asymmetrical)
Signal: 4 kV (Test Level 4 - asymmetrical)
Comments: Criterion B
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations: EN61000-4-8
Frequency: 16.67 Hz
50 Hz
60 Hz
50 Hz
60 Hz
0 Hz
Test field strength: 100 A/m
1 kA/m
300 A/m
Additional text: 60 s
3 s
DC, 60s
Comments: Criterion A
Frequency range: 50 Hz ... 60 Hz
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
NotesGeneral: EtherCAT® is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
Technical Specs
ECLASSECLASS-11.0: 27040705
ECLASS-12.0: 27040705
ECLASS-13.0: 27040705
ETIMETIM 9.0: EC000382
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00110.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00951.pdf

Approvals_00952.pdf

Approvals_00953.pdf

Approvals_00963.pdf

Approvals_01501.pdf

Approvals_01529.pdf

Approvals_01855.pdf

Data_sheet_03895.pdf

Manufacturer_declaration_03116.pdf

Manufacturer_declaration_04829.pdf

Manufacturer_declaration_05510.pdf

Manufacturer_declaration_16214.pdf

Package_slip_02164.pdf

Technical_drawing_40409.pdf

Various_00027.pdf

Various_00006.pdf