Industrial Automation
VAL-US 60/2+0/1U/FM - Type 2 surge protection device
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | General Note: For installation into a touch protected cabinet. For applications with UC > 500 V distances at the side and distances at the connection area must be minimum of 5 mm between different active parts including earthed parts. |
Product properties | IEC test classification: II T2 EN type: T2 IEC power supply system: TN-S Type: DIN rail module, two-section, divisible Product type: Surge protection for NEMA power supply units Product family: VALVETRAB MS Surge protection fault message: Optical, remote indicator contact Insulation characteristics Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) Indicator/remote signaling Connection name: Remote fault indicator contact Switching function: Changeover contact Operating voltage: 5 VAC ... 250 VAC 125 VAC (UL) 125 VDC (200 mA DC) Operating current: 5 mA AC ... 1.5 A 1 A (UL) 1 A (30VDC) |
Connection data | Connection method: Screw connection Screw thread: M5 Tightening torque: 2.5 Nm ... 3 Nm 22 lbf-in. ... 26.5 lbf-in. (UL) Stripping length: 16 mm Conductor cross section flexible min.: 1.5 mm² Conductor cross section flexible max.: 25 mm² Conductor cross section, rigid min.: 1.5 mm² Conductor cross section, rigid max.: 35 mm² Conductor cross section AWG: 15 ... 2 10 ... 2 (UL) Remote fault indicator contact Connection method: Push-in spring connection Stripping length: 6 mm Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 0.5 mm² Conductor cross section, rigid min.: 0.14 mm² Conductor cross section, rigid max.: 0.5 mm² Conductor cross section AWG: 24 ... 20 (UL) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/64a70df0834b47408345383b84052679/-S204x204-FJPG Width: 70.6 mm Height: 40.6 mm Height unit: 1 U Depth: 85.6 mm |
Material specifications | Flammability rating according to UL 94: V-0 Housing material: PA 6.6 PBT |
Protective circuit | Mode of protection: L-PE N-PE Direction of action: N-PE L-PE Nominal voltage UN: 60VAC ±10% (TN-S) 60 VDC ±10% -48 VDC ±10% (RRH) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 75 VAC 100 VDC Rated load current IL: 80 A Residual current IPE: ⤠0.45 mA Standby power consumption PC: ⤠35 mVA Nominal discharge current In (8/20) µs: 15 kA Maximum discharge current Imax (8/20) µs: 40 kA Short-circuit current rating ISCCR: 25 kA Voltage protection level Up: ⤠0.55 kV Residual voltage Ures: ⤠0.55 kV (at In) ⤠0.425 kV (at 10 kA) ⤠0.325 kV (at 5 kA) ⤠0.275 kV (at 3kA) TOV behavior at UT: 100 VAC (5s / withstand mode) Response time tA: ⤠25 ns Max. backup fuse with V-type through wiring: 80 A AC (gG - 16 mm²) Max. backup fuse with branch wiring: 160 A AC (gG) Additional technical data Maximum discharge current Imax (8/20) µs: 40 kA |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (only when all terminal points are used) Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
Approvals | UL specifications Maximum continuous operating voltage MCOV (L-N): 75 VAC 100 VDC Mode of protection: N-G L-G (L+) - (L-) (L+) - G (L-) - G Nominal voltage: 60 VDC Power distribution system: DC SPD Type: 4CA UL indicator/remote signaling Operating voltage: 125 VAC AC operating current: 1 A AC UL connection data Tightening torque: 30 lbf-in. Conductor cross section AWG: 10 ... 2 |
Mounting | Mounting type: Panel mount |
ECLASS | ECLASS-11.0: 27130805 ECLASS-13.0: 27171202 |
ETIM | ETIM 8.0: EC000941 |
UNSPSC | UNSPSC 21.0: 39121600 |