Input data | Input voltage: 24 VDC Input voltage range: 18 VDC ... 30 VDC 18 VDC ... 32 VDC Electric strength, max.: 35 VDC Internal input fuse: no Voltage type of supply voltage: DC Inrush current: ⤠8 A (â¤4ms) Reverse polarity protection: yes Fixed backup threshold: 22 VDC Dynamic activation threshold: > 1V / 100ms Switch-on time: max. 3 s Switch-on time during battery operation (Bat.-Start): 8 s Voltage drop, input/output: 0.4 VDC Current consumption IN (UN, IOUT = IN, Icharge = 0): 20.1 A Current consumption Imax (UN, IOUT = IStat.Boost, Icharge = max): 31.2 A Current consumption INo-Load(UN, IOUT = 0, Icharge = 0): 50 mA Current consumption Icharge (UN, IOUT = 0, Icharge = max): 6.1 A Power consumption PN (UN, IOUT = IN, Icharge = 0): 474 W Power consumption Pmax (UN, IOUT = IStat.Boost, Icharge = max): 738 W Power consumption PNo-Load (UN, IOUT = 0, Icharge = 0): 1.3 W Power consumption Pcharge (UN, IOUT = 0, Icharge = max): 145 W |
Output data | Efficiency: typ. 98 % Number of outputs: 1 Short-circuit-proof: yes No-load proof: yes Switch-over time: 0 ms UPS connection in parallel: no UPS connection in series: no Energy storage device connection in parallel: Yes, 5 (observe line protection) Energy storage device connection in series: no Mains operation Output voltage: 24 VDC (UOUT = UIN - 0.4VDC) Output voltage range: 18 VDC ... 30 VDC 18 VDC ... 32 VDC Output current IN: 20 A Static Boost (IStat.Boost): 25 A Dynamic Boost (IDyn.Boost): 30 A (5 s) Selective Fuse Breaking (ISFB): 120 A (15 ms) Output power POUT (UN, IOUT = IN): 480 W Output power POUT (UN, IOUT = Istat.Boost): 600 W Battery operation Output voltage: 24 VDC (UOUT = UBAT - 0.4VDC) Output voltage range: 19 VDC ... 32 VDC Output current IN: 20 A Static Boost (IStat.Boost): 25 A Dynamic Boost (IDyn.Boost): 30 A (5 s) Selective Fuse Breaking (ISFB): 120 A (15 ms) Output power POUT (UN, IOUT = IN): 480 W Output power POUT (UN, IOUT = Istat.Boost): 600 W |
Energy storage | End-of-charge voltage: 32 VDC End-of-charge voltage (temperature-compensated): 25 VDC ... 32 VDC Charging current (configurable): 5 A Nominal capacity (without additional charger): 3 Ah ... 100 Ah Max. capacity: 135 Ah Charging time: 202.5 h Buffer time: 19 min. (12Ah) Deep discharge protection: 19.2 VDC Battery technology: VRLA, VRLA-WTR, LI-ION Charge characteristic curve: IU0U IQ-Technology: yes Temperature sensor: yes Temperature compensation (configurable): 42 mV/K |
Interfaces | Communication Slave address: 192 Start bit: 1 Data bits: 8 Parity: even Stop bit: 1 Interface: USB (Modbus/RTU) Number of interfaces: 1 Connection method: MINI-USBTypeB Connection marking: X1 Locking: Screw Transmission physics: USB 2.0 Topology: Point-to-point Transmission speed: 9600 baud ... 115200 baud (Default: 115200 baud) Transmission length: max. 5 m Access time: ⤠2 s Supported protocols: Modbus/RTU Chipset: Silicon Labs CP210x Electrical isolation: Yes, UL approved |
Signaling | LED signaling Types of signaling: DC OK (green) Alarm (red) Bat.-Mode (yellow) SOC (red, green) Data (red, green) |
Product properties | Product type: DC UPS Product family: QUINTUSV MTBF (IEC 61709, SN 29500): > 1405000 h (25°C) > 910000 h (40°C) > 481200 h (60°C) Environmental protection directive: RoHS Directive 2011/65/EU WEEE Reach Insulation characteristics Protection class: III (without PE) Degree of pollution: 2 Life expectancy (electrolytic capacitors) Time: 192072 h |
Dimensions | Item dimensions Width: 40 mm Height: 130 mm Depth: 125 mm 125 mm (Device depth (DIN rail mounting)) Item dimensions with alternative mounting Width: 123 mm Height: 130 mm Depth: 42 mm Installation dimensions Installation distance right/left (active): 5 mm / 5 mm (POutâ¥50%) Installation distance right/left (passive): 0 mm / 0 mm (POutâ¥50%) Installation distance right/left (active, passive): 0 mm / 0 mm (POutâ¤50%) Installation distance top/bottom (active): 50 mm / 50 mm (POutâ¥50%) Installation distance top/bottom (passive): 40 mm / 20 mm (POutâ¥50%) Installation distance top/bottom (active, passive): 40 mm / 20 mm (POutâ¤50%) |
Mounting | Mounting type: DIN rail mounting Mounting position: On horizontal DIN rail NS 35/7.5 and NS 35/15 acc. to EN 60715 |
Material specifications | Flammability rating according to UL94 (housing / terminal blocks): V0 Housing material: Metal Hood version: Stainless steel X6Cr17 Side element version: Aluminum AlMg3 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ⤠4000 m Climatic class: 3K3 (EN60721) Max. permissible relative humidity (operation): ⤠95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): 2.3g |
Standards and regulations | Protective extra-low voltage Standard designation: Protective extra-low voltage Standards/specifications: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) |
Approvals | UL approval Identification: UL/C-UL Listed UL61010-1 UL approvalâ Identification: UL/C-UL Listed UL61010-2-201 UL approvalââ Identification: UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) CSA Identification: CAN/CSA-C22.2 No.61010-1-12 CSAâ Identification: CAN/CSA-IEC 61010-2-201 CSAââ Identification: CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) CB scheme Identification: IEC 61010-1 IEC 61010-2-201 DNV Identification: Class Guideline DNVGL-CG-0339 Note: Location classes: TemperatureD (see Application/Limitation), HumidityB, VibrationA/C, EMCB |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: EN61000-6-3 EN61000-6-4 EMC requirements for noise immunity: EN61000-6-1 EN61000-6-2 Noise immunity: Immunity in accordance with EN61000-6-1 (residential), EN61000-6-2 (industrial), and EN61000-6-5 (power station equipment zone), IEC/EN61850-3 (power supply) Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: 8 kV (Test Level 4) Discharge in air: 15 kV (Test Level 4) Comments: Criterion B Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 6 GHz 1 GHz ... 6 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level 3) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: 4 kV (Test Level 4 - asymmetrical) Output: 4 kV (Test Level 4 - asymmetrical) Signal: 4 kV (Test Level 4 - asymmetrical) Comments: Criterion B Surge voltage load (surge) Standards/regulations: EN61000-4-5 Input: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Output: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion B Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Power frequency magnetic field Standards/regulations: EN61000-4-8 Frequency: 16.67 Hz 50 Hz 60 Hz 50 Hz 60 Hz 0 Hz Test field strength: 100 A/m 1 kA/m 300 A/m Additional text: 60 s 3 s DC, 60s Comments: Criterion A Frequency range: 50 Hz ... 60 Hz Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
ECLASS | ECLASS-11.0: 27040705 ECLASS-12.0: 27040705 ECLASS-13.0: 27040705 |
ETIM | ETIM 9.0: EC000382 |
UNSPSC | UNSPSC 21.0: 39121000 |