PHOENIX CONTACT 2907916
PHOENIX CONTACTNot available

PLT-SEC-T3-24-FM-UT - Type 3 surge protection device

Type3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote signaling for single-phase power supply networks. Nominal voltage: 24VAC/DC
Product Code: 2907916
Partner cod.: 2907916
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC power supply system: TN-S
Type: DIN rail module, two-section, divisible
Product type: Device protection
Product family: SEC Family
Number of positions: 2
Surge protection fault message: Optical, remote indicator contact
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
IEC test classification: III
T3
EN type: T3
Number of ports: One
Electrical propertiesIndicator/remote signaling
Connection name: Remote fault indicator contact
Switching function: Changeover contact
Operating voltage: 250 VAC
125 VDC (200 mA DC)
Operating current: 0.5 A AC
0.5 ADC (75VDC)
Connection dataConnection method: Screw connection
Screw thread: M3
Tightening torque: 0.5 Nm
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section rigid: 0.2 mm² ... 4 mm²
Conductor cross section AWG: 24 ... 12
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/6c0aeca69c09d34d813d8a1d38285f5c/-S204x204-FJPG
Width: 17.7 mm
Height: 93.4 mm
Depth: 74.5 mm (incl. DIN rail 7.5mm)
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6-FR 20 % GF
PA 6.6-FR
Housing material: PA 6.6-FR 20% GF
PA 6.6-FR
Protective circuitMode of protection: L-N
L-PE
N-PE
Direction of action: 1L-N & N-PE
Nominal voltage UN: 24VAC(TN-S)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 34 VAC
Rated load current IL: 26 A (at 30°C)
Residual current IPE: ≤ 5 µA
Standby power consumption PC: ≤ 2.7 mVA (at UREF)
≤ 4.8 mVA (at UC)
Reference test voltage UREF: 27 VAC
Nominal discharge current In (8/20) µs: 1 kA
Combination wave UOC: 2 kV
Voltage protection level Up (L-N): ≤ 0.2 kV
Voltage protection level Up (L-PE): ≤ 0.6 kV
Voltage protection level Up (N-PE): ≤ 0.6 kV
TOV behavior at UT (L-N): 50 VAC (120min / withstand mode)
TOV behavior at UT (L-PE): 50 VAC (120min / withstand mode)
Response time tA (L-N): ≤ 25 ns
Response time tA (L-PE): ≤ 100 ns
Response time tA (N-PE): ≤ 100 ns
Short-circuit current rating ISCCR: 10 kA AC
Max. backup fuse with branch wiring: 32 A (gG / B / C)
Additional technical data
Short-circuit current rating ISCCR: 0.25 kA DC (Without additional backup fuse in the DC branch wiring)
5 kA DC (for 20 A gG / B backup fuse)
Maximum discharge current Imax (8/20) µs: 4 kA
Nominal discharge current In (8/20) µs: 3 kA
Residual voltage Ures (L-N): ≤ 0.16 kV (at 0.5kA)
≤ 0.2 kV (at 1 kA)
Residual voltage Ures (L-PE): ≤ 0.35 kV (at 0.5kA)
≤ 0.4 kV (at 1 kA)
Residual voltage Ures (N-PE): ≤ 0.35 kV (at 0.5kA)
≤ 0.4 kV (at 1 kA)
Maximum continuous voltage UC: 44 VDC
Mode of protection: (DC+) - (DC-)
(DC+/DC-) - PE
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (operating voltage remote contact ≤ 250 V)
≤ 6000 m (operating voltage remote contact ≤ 150 V)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (5 ... 500 Hz / 2.5 h / X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV: 34 VAC
34 VDC
Nominal discharge current In: 1 kA
Mode of protection: L-N
L-G
N-G
(DC+) - (DC-)
(DC+) - G
(DC-) - G
Nominal voltage: 34 VDC
Rated load current IL: 20 A
Power distribution system: Single phase
DC
Nominal frequency: 50/60 Hz
Measured limiting voltage MLV (L-N): 200 V
Measured limiting voltage MLV (L-G): 510 V
Measured limiting voltage MLV (N-G): 510 V
SPD Type: 4CA
UL indicator/remote signaling
Operating voltage: 250 VAC (0.5A)
DC operating voltage: 12 VDC (4A)
24 VDC (2A)
48 VDC (1A)
UL connection data
Tightening torque: 4.4 lbf-in.
Conductor cross section AWG: 16 ... 12
Standards and regulationsStandards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130806
ECLASS-13.0: 27171203
ETIMETIM 9.0: EC000942
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Approvals_00203.pdf

Approvals_01766.pdf

Approvals_01867.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Flyer_00003.pdf

Manufacturer_declaration_00814.pdf

Manufacturer_declaration_01305.pdf

Manufacturer_declaration_02094.pdf

Package_slip_00344.pdf

Product_information_00033.pdf

Product_information_00999.pdf

Product_information_01023.pdf

Technical_drawing_40542.pdf