PHOENIX CONTACT 2909596
PHOENIX CONTACTNot available

VAL-SEC-T2-350VF-P - Type 2 surge protection plug

Replacement plug free of leakage current for surge protective devices from the VALVETRAB SEC product range for L-N and L-PEN paths.
Product Code: 2909596
Partner cod.: 2909596
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: II
T2
EN type: T2
IEC power supply system: TN
TT
Type: Male
Product type: Replacement plug
Product family: SEC Family
Number of positions: 1
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: pluggable
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/e7cb446bdeab77498a0d023a1cee84c2/-S204x204-FJPG
Width: 11.7 mm
Height: 46.4 mm
Depth: 59.4 mm
Horizontal pitch: 0.6 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA6.6-FR 20% GF
PBT-FR
Material group: I
Housing material: PA 6.6-FR 20% GF
PBT-FR
Protective circuitMode of protection: L-N
L-PEN
Direction of action: L-N / L-PEN
Nominal voltage UN: 240VAC (TN)
240VAC (TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 350 VAC
Nominal discharge current In (8/20) µs: 10 kA
Maximum discharge current Imax (8/20) µs: 20 kA
Short-circuit current rating ISCCR: 50 kA
Voltage protection level Up: ≤ 1.5 kV
Residual voltage Ures: ≤ 1.35 kV (at In)
≤ 1.1 kV (at 5 kA)
≤ 0.95 kV (at 2 kA)
≤ 0.9 kV (at 1 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs: ≤ 1.5 kV
TOV behavior at UT: 457 VAC (5s / withstand mode)
457 VAC (120min / withstand mode)
Response time tA: ≤ 100 ns
Max. backup fuse with branch wiring: 200 A (gG)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Standards and regulationsStandards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2012
MountingMounting type: on base element
Technical Specs
ECLASSECLASS-11.0: 27130890
ECLASS-13.0: 27171292
ETIMETIM 9.0: EC002496
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01875.pdf

Flyer_00001.pdf

Flyer_00003.pdf

Flyer_00002.pdf

Manufacturer_declaration_00786.pdf

Manufacturer_declaration_02098.pdf

Package_slip_00560.pdf

Technical_drawing_40802.pdf