Industrial Automation
Product properties | Product type: Relay Module Product family: RIFLINEcomplete Application: Forcibly guided contacts Operating mode: 100% operating factor Mechanical service life: approx. 107 cycles B10d: 600000 Cycles (AC1; 250V/6A; 1 NO) 900000 Cycles (AC1; 250V/3A; 1NO) 1800000 Cycles (AC1; 250V/1,5A; 1NO) 300000 Cycles (DC13; 24V/3A; 1NO) 1000000 Cycles (DC13; 24V/1,5A; 1NO) 3000000 Cycles (DC13; 24V/0,75A; 1NO) Insulation characteristics: Air clearances and creepage distances between the power circuits Insulation: Safe isolation between input and output Basic insulation between the changeover contacts Overvoltage category: III Pollution degree: 2 |
Electrical properties | Maximum power dissipation for nominal condition: 0.72 W Test voltage (Winding/contact): 4 kVrms (50Hz, 60s) Test voltage (): 1.5 kVrms (50Hz, 60s) Test voltage (Changeover contact/changeover contact): 2.5 kVrms (50Hz, 60s) Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 VAC (Input/output) Rated surge voltage: 6 kV (Input/output) 4 kV (between the changeover contacts) Short-circuit protection device Current: 10 A (RT28-32) Voltage: 500 V (SCPD) Short-circuit current: 1 kA (conditional short-circuit current) |
Input data | Coil side Nominal operating voltage UN: 24 VDC Input voltage range: 20.4 VDC ... 28.8 VDC (20°C) Input voltage range in reference to UN: see diagram Drive and function: monostable Drive (polarity): polarized Typical input current at UN: 30 mA Typical response time: 15 ms Typical release time: 10 ms Coil voltage: 24 VDC Protective circuit: Freewheeling diode Operating voltage display: Yellow LED |
Output data | Switching Contact switching type: 2 changeover contacts, forcibly actuated Type of switch contact: Single contact Contact material: AgSnO Maximum switching voltage: 250 V AC/DC Limiting continuous current: 6 A Interrupting rating (ohmic load) max.: 144 W (24VDC) 58 W (48VDC) 54 W (60VDC) 55 W (110VDC) 55 W (220VDC) 1500 VA (250VAC) Utilization category CB Scheme (IEC 60947-5-1): AC15, 3 A/240 V (N/O contact) |
Connection data | Connection method: Screw connection Stripping length: 8 mm Conductor cross section rigid: 0.5 mm² ... 4 mm² Conductor cross-section rigid (2 conductors with same cross section): 0.5 mm² ... 2.5 mm² Conductor cross section flexible: 0.5 mm² ... 4 mm² 0.5 mm² ... 4 mm² (Ferrule with plastic sleeve) Conductor cross section flexible (2 conductors with same cross section): 0.5 mm² ... 2.5 mm² 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) Conductor cross section AWG: 20 ... 10 (solid) 20 ... 12 (flexible) Tightening torque: 0.5 Nm ... 0.6 Nm |
Dimensions | Width: 16 mm Height: 90 mm Depth: 75 mm |
Material specifications | Flammability rating according to UL 94: V2 (Housing) |
Environmental and real-life conditions | Ambient conditions Degree of protection (Relay base): IP20 (Relay base) Degree of protection (Relay): RT I (Relay) Ambient temperature (operation): -25°C ... 60°C Ambient temperature (storage/transport): -25°C ... 85°C Altitude: ⤠2000 m |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant Corrosive gas test Identification: ISA-S71.04. G3 Harsh Group EN60068-2-60 |
Standards and regulations | All specifications in accordance with the standard Standards/regulations: IEC 60947-5-1 IEC 61810-3 Air clearances and creepage distances between the power circuits Standards/regulations: DINEN60947-5-1 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: in rows with zero spacing Mounting position: any |
ECLASS | ECLASS-11.0: 27371601 ECLASS-12.0: 27371601 ECLASS-13.0: 27371601 |
ETIM | ETIM 9.0: EC001437 |
UNSPSC | UNSPSC 21.0: 39122300 |
Description other products