Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2909908
PHOENIX CONTACT 2909908
PHOENIX CONTACTNot available

PTCB E1 24DC/6A NO - Electronic circuit breaker

1-channel, electronic circuit breaker for protecting loads at 24 V DC against overload and short circuit. Easy potential distribution with components from the CLIPLINE complete terminal block system. With fixed nominal current. For installation on DIN rails.
Product Code: 2909908
Partner cod.: 2909908
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesGeneral
Note: EN50121-3-2: Railway applications - Electromagnetic compatibility - Part 3-2: Rolling stock – Apparatus
Connection for signal line tested in accordance with EN61000-4-4 with 1 kV; if necessary, customer must provide appropriate protective measures
Repeated hard short circuits can reduce the melting integral of the integrated backup fuse.
Product propertiesType: DIN rail module, one-piece
Product type: Device circuit breakers
Product family: PTCB
Number of positions: 1
No. of channels: 1
Insulation characteristics
Protection class: III
Pollution degree: 2
Electrical propertiesNo. of channels: 1
General
Operating voltage: 18 VDC ... 30 VDC
Rated voltage: 24 VDC
Rated current IN: 24 ADC (Total current input)
6 ADC (Rated current output)
Rated current (pre-adjusted): 6 A
Rated surge voltage: 0.5 kV
Tripping method: E (electronic)
Feedback resistance: max. 35 VDC
Required backup fuse: Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element.
Short-circuit switching capacity: 300 A
Dielectric strength: max. 35 VDC (Load circuit)
Fuse: electronic
Efficiency: > 99 %
Closed circuit current I0: typ. 12 mA
Power dissipation: typ. 0.3 W (No-load operation)
< 1.2 W (Nominal operation)
Module initialization time: < 0.55 s
Waiting time after switch off of a channel: 5 s (at overload / short circuit)
Measuring tolerance I: ± 15 %
Temperature derating: 21 A (Total current at 60°C)
24 A (Total current at 50°C)
6 A (Channel current at 60°C)
6 A (Channel current at 50°C)
MTBF (IEC 61709, SN 29500): 27777777 h (at 25°C with 21% load)
12658227 h (at40°C with 34.25%load)
1414427 h (at60°C with 100%load)
Voltage drop: 0.1 V (at 6 A)
Fail-safe element: 15 ADC
Load circuit
Shutdown time: ≤ 10 ms (for short circuit > 2.0 x IN)
1 s (1.2...2.0 x IN)
Undervoltage switch-off: ≤ 17.8 VDC (active)
≥ 18.8 VDC (inactive)
Overvoltage switch-off: ≥ 30.5 VDC (active)
≤ 29.5 VDC (inactive)
Max. capacitive load: 24000 µF (Depending on the available short-circuit current)
Indicator/remote signaling
Connection name: Remote indication circuit
Switching function: N/O contact
Operating voltage: 0 VDC ... 30 VDC
Operating current: 100 mA DC
Connection dataMain circuit IN+
Connection method: Push-in connection
Stripping length: 8 mm
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section rigid: 0.2 mm² ... 4 mm²
Conductor cross section AWG: 24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm²
Main circuit IN-
Connection method: Push-in connection
Stripping length: 8 mm
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section rigid: 0.2 mm² ... 4 mm²
Conductor cross section AWG: 24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm²
Main circuit OUT
Connection method: Push-in connection
Stripping length: 8 mm
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section rigid: 0.2 mm² ... 4 mm²
Conductor cross section AWG: 24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm²
Remote indication circuit
Connection method: Push-in connection
Stripping length: 10 mm
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section rigid: 0.2 mm² ... 4 mm²
Conductor cross section AWG: 24 ... 14
Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm²
SignalingChannel LED off: off (Channel switched off)
Channel LED yellow: lit (Channel switched on, channel load>80%)
flashing (Programming mode active)
Channel LED green: lit (Channel switched on)
Channel LED red: lit (Channel switched off, over- or undervoltage active)
ON temporarily (Channel switched off, 5s cool-down phase, overload or short-circuit release)
flashing (Channel switched off, ready to be switched back on, overload or short-circuit release)
flashing quickly (Channel switched off, external voltage at the output, possible installation error)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/91339568b73b714292afb2d2f0fc1b11/-S204x204-FJPG
Width: 6.2 mm
Height: 105.8 mm
Depth: 55.6 mm (incl. DIN rail 7.5mm)
Material specificationsMaterial: PBT
Flammability rating according to UL 94: V-0
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -30°C ... 60°C
Ambient temperature (storage/transport): -40°C ... 70°C
Altitude: ≤ 3000 m up to52°C (amsl)
≤ 4000 m up to46°C (amsl)
Humidity test: 96h, 95%RH, 40°C
Shock (operation): 30g (IEC 60068-2-27, Test Ea)
Vibration (operation): 10Hz...59.6Hz (Amplitude±0.35mm; in accordance with IEC 60068-2-6, Test Fc)
59.6Hz…150Hz (Acceleration5g; in accordance with IEC 60068-2-6, Test Fc)
5Hz…100Hz (Resonance search4g; resonance frequency4g; 90minin accordance with DNV GL Class B)
ApprovalsUL approval
Identification: UL/C-UL Listed UL 508
UL Recognized UL 2367
UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D; T4 (Hazardous Location)
Shipbuilding approval
Identification: DNV GL
DNV GL data
Temperature: D
Humidity: B
Vibration: B
EMC: B
Enclosure: A
Standards and regulationsStandards/specifications: EN61000-6-2
EN61000-6-3
EN60068-2-78
EN50178
EN60068-2-6
EN60068-2-27
EN60068-2-30
EN61373
EN45545-2
Note: EMC – Immunity for industrial areas
EMC – Emission for residential, business and commercial properties and small operations
Environmental influences – Moisture and heat, constant
Equipping power installations with electronic equipment
Environmental influences – Vibrations (sinusoidal)
Environmental influences – Shocks
Environmental influences – Part 2–30: Tests – Test Db: Damp heat, cyclical
Railway applications - Rolling stock equipment - Shock and vibration tests
Railway applications - Fire protection on railway vehicles - Part 2: Requirements for fire behavior of materials and components
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27140401
ECLASS-13.0: 27140401
ECLASS-12.0: 27140401
ETIMETIM 9.0: EC003538
UNSPSCUNSPSC 21.0: 39121400
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00231.pdf

Approvals_01634.pdf

Approvals_01635.pdf

Approvals_01636.pdf

Approvals_01637.pdf

Approvals_01639.pdf

Approvals_01747.pdf

Flyer_00006.pdf

Manufacturer_declaration_01040.pdf

Manufacturer_declaration_01300.pdf

Manufacturer_declaration_02245.pdf

Manufacturer_declaration_05496.pdf

Manufacturer_declaration_16485.pdf

Package_slip_00427.pdf

Product_information_00033.pdf

Product_information_00751.pdf

Technical_drawing_40879.pdf

Various_00001.pdf