Industrial Automation
VAL-US-120/65-P - Type 1 surge protection plug
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | General: Used in: |
Product properties | IEC test classification: I / II T1 / T2 EN type: T1 / T2 Type: Male Product type: Replacement plug Product family: VALVETRAB MS Number of positions: 1 Surge protection fault message: optical Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) |
Connection data | Connection method: VALVETRAB plug-in system |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/244085b8304de74e95f3135ca62ba23a/-S204x204-FJPG Width: 17.5 mm Height: 47 mm Depth: 67.3 mm Horizontal pitch: 1 Div. |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA 6.6/PBT Material group: I Housing material: PA 6.6 PBT |
Protective circuit | Mode of protection: L-N L-PEN N-PE Direction of action: L-N / L-PEN Nominal voltage UN: 120/208VAC 120/240VAC Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 175 VAC Residual current IPE: ⤠800 µA Standby power consumption PC: ⤠140 mVA Nominal discharge current In (8/20) µs: 12.5 kA Maximum discharge current Imax (8/20) µs: 65 kA Short-circuit current rating ISCCR: 25 kA Voltage protection level Up: ⤠0.8 kV Residual voltage Ures: ⤠0.8 kV (at In) ⤠0.7 kV (at 10 kA) ⤠0.6 kV (at 5 kA) ⤠0.5 kV (at 3kA) TOV behavior at UT: 208 VAC (5s / withstand mode) 229 VAC (120min / withstand mode) Max. backup fuse with branch wiring: 125 A (gG) Additional technical data Maximum discharge current Imax (8/20) µs: 65 kA |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
Approvals | UL specifications Maximum continuous operating voltage MCOV: 175 VAC Short-circuit current rating (SCCR): 200 kA Voltage protection rating VPR: 700 V UL type: type 1 Nominal discharge current In: 20 kA Maximum Surge Current per Phase: 65 kA (acc. IEC61643-1) 80 kA (acc. NEMA LS1) Mode of protection: L-N L-G N-G Nominal voltage: 120/240VAC Power distribution system: Single phase Nominal frequency: 50/60 Hz SPD Type: 1CA |
Standards and regulations | Air clearances and creepage distances Standards/regulations: EN60664-1 / EN61643-11 Standards/specifications: IEC 61643-11 EN61643-11 Note: 2011 2012 |
Mounting | Mounting type: on base element |
ECLASS | ECLASS-11.0: 27130890 ECLASS-13.0: 27171292 |
ETIM | ETIM 8.0: EC002496 |
UNSPSC | UNSPSC 21.0: 39121600 |
Description other products