Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2910337
PHOENIX CONTACTNot available

VAL-US-240D/40-P - Type 1 surge protection plug

UL Recognized type 1 SPD and IEC type 2 surge protection plug with a varistor and thermal disconnect for use with VAL-US base elements, mechanical and visual fault warning
Product Code: 2910337
Partner cod.: 2910337
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
NotesGeneral: Used in:
Product propertiesIEC test classification: II
T2
EN type: T2
Type: Male
Product type: Replacement plug
Product family: VALVETRAB MS
Number of positions: 1
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: VALVETRAB plug-in system
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3e02d9b64ee0a341a2e312513f1ad825/-S204x204-FJPG
Width: 17.5 mm
Height: 52.4 mm
Depth: 55.3 mm
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6/PBT
Material group: I
Housing material: PA 6.6
PBT
Protective circuitMode of protection: L-L
L-PEN
Direction of action: 1L-N/PE
Nominal voltage UN: 240/415VAC
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 275 VAC
Residual current IPE: ≤ 450 µA
Standby power consumption PC: ≤ 120 mVA
Nominal discharge current In (8/20) µs: 20 kA
Maximum discharge current Imax (8/20) µs: 40 kA
Short-circuit current rating ISCCR: 25 kA
Voltage protection level Up: ≤ 1.35 kV
Residual voltage Ures: ≤ 1.35 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3kA)
TOV behavior at UT: 335 VAC (5s / withstand mode)
440 VAC (120min / safe failure mode)
Max. backup fuse with branch wiring: 100 A (gG)
Additional technical data
Maximum discharge current Imax (8/20) µs: 40 kA
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV: 275 VAC
Short-circuit current rating (SCCR): 200 kA
Voltage protection rating VPR: 1000 V
UL type: type 1
Nominal discharge current In: 20 kA
Maximum Surge Current per Phase: 40 kA
Mode of protection: L-L
L-G
Nominal voltage: 240VAC (Delta)
Power distribution system: Single phase
Nominal frequency: 50/60 Hz
SPD Type: 1CA
Standards and regulationsAir clearances and creepage distances
Standards/regulations: EN60664-1 / EN61643-11
Standards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2012
MountingMounting type: on base element
Technical Specs
ECLASSECLASS-11.0: 27130890
ECLASS-13.0: 27171292
ETIMETIM 8.0: EC002496
UNSPSCUNSPSC 21.0: 39121600
Description
UL Recognized type 1 SPD and IEC type 2 surge protection plug with a varistor and thermal disconnect for use with VAL-US base elements, mechanical and visual fault warning
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Manufacturer_declaration_00147.pdf

Manufacturer_declaration_02935.pdf

Package_slip_00116.pdf

Technical_drawing_40920.pdf