PHOENIX CONTACT 2910342
PHOENIX CONTACT 2910342
PHOENIX CONTACTNot available

GDT-US-NG/40-P - Type 1 surge protection plug

UL Recognized type 1 SPD and IEC type 2 surge protection plug with a gas discharge tube and thermal disconnect for use with VAL-US base elements, mechanical and visual fault warning
Product Code: 2910342
Partner cod.: 2910342
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
NotesGeneral: Used in:
Product propertiesIEC test classification: II
T2
EN type: T2
Type: Male
Product type: Replacement plug
Product family: VALVETRAB MS
Number of positions: 1
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: VALVETRAB plug-in system
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3e02d9b64ee0a341a2e312513f1ad825/-S204x204-FJPG
Width: 17.5 mm
Height: 52.4 mm
Depth: 55.3 mm
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6/PBT
Material group: I
Housing material: PA 6.6
PBT
Protective circuitMode of protection: N-PE
Direction of action: N-PE
Nominal voltage UN: 277/480VAC (TN-S)
277/480VAC (TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 305 VAC
Residual current IPE: ≤ 5 µA
Standby power consumption PC: ≤ 1.5 mVA
Nominal discharge current In (8/20) µs: 20 kA
Maximum discharge current Imax (8/20) µs: 40 kA
Follow current interrupt rating Ifi: 100 A (260V)
Voltage protection level Up: ≤ 1.5 kV
Residual voltage Ures: ≤ 0.4 kV (at In)
≤ 0.25 kV (at 10 kA)
≤ 0.15 kV (at 5 kA)
≤ 0.1 kV (at 3kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs: ≤ 1.5 kV
TOV behavior at UT: 1200 VAC (200ms / withstand mode)
Response time tA: ≤ 100 ns
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV: 305 VAC
Voltage protection rating VPR: 1200 V
UL type: type 1
Nominal discharge current In: 20 kA
Maximum Surge Current per Phase: 40 kA
Mode of protection: N-G
Nominal voltage: 277VAC
Power distribution system: Single phase
Nominal frequency: 50/60 Hz
SPD Type: 1CA
Standards and regulationsStandards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2012
MountingMounting type: on base element
Technical Specs
ECLASSECLASS-11.0: 27130890
ECLASS-13.0: 27171292
ETIMETIM 9.0: EC002496
UNSPSCUNSPSC 21.0: 39121600
Description
UL Recognized type 1 SPD and IEC type 2 surge protection plug with a gas discharge tube and thermal disconnect for use with VAL-US base elements, mechanical and visual fault warning
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Manufacturer_declaration_00147.pdf

Manufacturer_declaration_02935.pdf

Package_slip_00122.pdf

Technical_drawing_40925.pdf