Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2924207
PHOENIX CONTACTNot available

MACX MCR-SL-RPSSI-I-SP - Power/input isolating amplifier

Repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4 … 20mA signals to a load (active or passive). 3-way electrical isolation, SIL2 in accordance with IEC61508.
Product Code: 2924207
Partner cod.: 2924207
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesProduct type: Repeater power supplies
Product family: MACX Analog
Application: Analog IN
No. of channels: 1
Type: Signal conditioners with SIL functional safety
Electrical propertiesNo. of channels: 1
Electrical isolation: 3-way isolation
Electrical isolation between input and output: yes
Signal transmission behavior: In=Out
Step response (10-90%): < 200 µs (for jump 4 mA ... 20mA, load 600 Ω)
< 600 µs (for jump 0 mA ... 20mA, load 600 Ω)
Maximum temperature coefficient: < 0.01 %/K
Maximum transmission error: < 0.1 % (of final value)
Transmission error, typical: < 0.05 % (of final value)
Electrical isolation​
Test voltage: 2.5 kV AC (50Hz, 60s)
Overvoltage category: II
Pollution degree: 2
Electrical isolation Input/output/power supply IEC/EN61010-1
Standards/regulations: IEC/EN61010-1
Rated insulation voltage: 300 Vrms
Insulation: Safe isolation
Electrical isolation Input/output IEC/EN60079-11
Standards/regulations: IEC/EN60079-11
Rated insulation voltage: 265 Vrms
Electrical isolation Input/power supply IEC/EN60079-11
Standards/regulations: IEC/EN60079-11
Rated insulation voltage: 265 Vrms
Electrical isolation Output/supply IEC/EN60079-7
Standards/regulations: IEC/EN60079-7
Rated insulation voltage: 265 Vrms
Supply
Designation: Repeater power supply operation
Nominal supply voltage: 24 VDC -20%...+25%
Supply voltage range: 19.2 VDC ... 30 VDC
Max. current consumption: < 76 mA (24VDC / 20mA / 1000Ω)
< 55 mA (24VDC / 20mA / 250Ω)
Power dissipation: < 1.1 W (24VDC / 20mA / 1000Ω)
< 0.95 W (24VDC / 20mA / 250Ω)
< 1.2 W (24VDC / 20mA / 0Ω)
Power consumption: < 1.8 W (20mA / 1000Ω)
< 1.3 W (20mA / 250Ω)
Supply​
Designation: Signal conditioner operation
Nominal supply voltage: 24 VDC -20%...+25%
Supply voltage range: 19.2 VDC ... 30 VDC
Max. current consumption: < 44 mA (24VDC / 20mA / 1000Ω)
< 27 mA (24VDC / 20mA / 250Ω)
Power dissipation: < 0.75 W (24VDC / 20mA / 1000Ω)
< 0.65 W (24VDC / 20mA / 250Ω)
< 0.95 W (24VDC / 20mA / 0Ω)
Input dataSignal: Repeater power supply operation
Description of the input: Active current input
Number of inputs: 1
Input signal: Current
Current input signal: 4 mA ... 20 mA
Current limitation: 25 mA
Transmitter supply voltage: > 21.5 V (20mA)
> 20.8 V (24mA)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Description of the input: Passive current input
Current input signal: 0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop: < 3.5 V (in input isolating amplifier operation)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Output dataSignal: Repeater power supply operation
Output description: Current output (active and passive)
Number of outputs: 1
Current output signal: 4 mA ... 20 mA (active)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/output load current output: < 1000 Ω (20mA)
< 825 Ω (24mA)
Output ripple: < 20 mVrms
Output behavior in the event of an error: 0 mA (Cable break in the input)
≥ 22.5 mA (Cable short-circuit in the input)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Output description: Current output (active and passive)
Current output signal: 0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
0 mA ... 20 mA (14 ... 26 V ext. source voltage)
4 mA ... 20 mA (14 ... 26 V ext. source voltage)
Load/output load current output: < 1000 Ω (20mA)
< 825 Ω (24mA)
Output ripple: < 20 mVrms
Output behavior in the event of an error: 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Connection dataConnection method: Push-in connection
Stripping length: 10 mm
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible (2 conductors with same cross section): 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve)
0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve)
Conductor cross section AWG: 24 ... 14
24 ... 22 (TWIN ferrule without plastic sleeve)
20 ... 16 (TWIN ferrule with plastic sleeve)
Ex dataEx installation (EPL): Gc
Div.2
InterfacesData communication (bypass)
HART function: Yes
Protocols supported: HART-transparent
SignalingStatus display: Green LED (supply voltage)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3edd36290ae8094db8e0add7aa964a6f/-S204x204-FJPG
Width: 12.5 mm
Height: 107.9 mm
Depth: 113.7 mm
Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715)
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Housing material: PA 6.6-FR
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (not assessed by UL)
Ambient temperature (operation): -40°C ... 60°C (Any mounting position)
-40°C ... 70°C (Derating)
Ambient temperature (storage/transport): -40°C ... 80°C
Permissible humidity (operation): 10 % ... 95 % (non-condensing)
Altitude range (≤ 2000 m)
Altitude: ≤ 2000 m (The technical data refers to altitudes ≤2000m above mean sea level. For altitudes >2000m above mean sea level, refer to the data sheet.)
Ambient temperature (operation): -40°C ... 60°C
-40°C ... 70°C (Derating)
Rated insulation voltage: 375 VPP (Power supply, input / output)
Altitude range (≤ 3000 m)
Height range: > 2000 m ... 3000 m
Ambient temperature (operation): -40°C ... 54°C
-40°C ... 63°C (Derating)
Rated insulation voltage: 190 VAC (Power supply, input / output)
110 VDC (Power supply, input / output)
Altitude range (≤ 4000 m)
Height range: > 3000 m ... 4000 m
Ambient temperature (operation): -40°C ... 48°C
-40°C ... 56°C (Derating)
Rated insulation voltage: 60 V AC/DC (Power supply, input / output)
Altitude range (≤ 5000 m)
Height range: > 4000 m ... 5000 m
Ambient temperature (operation): -40°C ... 42°C
-40°C ... 49°C (Derating)
Rated insulation voltage: 60 V AC/DC (Power supply, input / output)
ApprovalsCE
Certificate: CE-compliant
Note: and EN61326
ATEX
Identification:  II 3 G Ex ec IIC T4 Gc
Certificate: PxCIF08ATEX2865955X
UKCAEx(UKEX)
Identification:  II 3 G Ex nA IIC T4 Gc X
Certificate: PxCIF21UKEX2865955X
IECEx
Identification: Ex ec IIC T4 Gc
Certificate: IECEx BVS 08.0016X
CCC/China-Ex
Identification: Ex ec IIC T4 Gc
Certificate: 2022122304115127
UL, USA/Canada
Identification: UL 61010 Listed
UL508 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
Shipbuilding approval
Certificate: DNV GL TAA000020C
Safety Integrity Level (SIL, IEC 61508)
Identification: 2
Certificate: IN-AT-AS-MRL-2300149
Systematic Capability
Identification: 3
INMETRO
Identification: Ex ec IIC T4 Gc
Certificate: DNV 18.0136 X
DNV GL data
Temperature: B
Humidity: B
Vibration: A
EMC: A
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Standards and regulationsElectrical isolation: 3-way isolation
GBStandard
Standards/regulations: GB/T3836.1
GB/T3836.3
MountingMounting type: DIN rail mounting
Technical Specs
ECLASSECLASS-11.0: 27210120
ECLASS-12.0: 27210120
ECLASS-13.0: 27210120
ETIMETIM 9.0: EC002653
UNSPSCUNSPSC 21.0: 39121000
Description
Repeater power supply and input isolating amplifier, HART. Transfers supplied or active 0/4 - 20 mA signals to a load (active or passive). 3-way electrical isolation, SIL 2 according to IEC 61508.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00369.pdf

Approvals_01143.pdf

Approvals_01550.pdf

Data_sheet_03613.pdf

Manual_00026.pdf

Manufacturer_declaration_00538.pdf

Manufacturer_declaration_01576.pdf

Manufacturer_declaration_16580.pdf

Manufacturer_declaration_17787.pdf

Package_slip_01568.pdf

Technical_drawing_41111.pdf