Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2924838
PHOENIX CONTACTNot available

MACX MCR-SL-RPSSI-2I-SP - Repeater power supply

Measuring transducer repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active0/4mA…20mA electrically isolated signals from the field to two loads. 4-way electrical isolation, Push-in connection, SIL, PL.
Product Code: 2924838
Partner cod.: 2924838
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesProduct type: Repeater power supplies
Product family: MACX Analog
No. of channels: 1
Type: Signal conditioners with SIL and PL Functional Safety
Electrical propertiesNo. of channels: 1
Electrical isolation: 3-way isolation
Electrical isolation between input and output: yes
Maximum power dissipation for nominal condition: 1.45 W (24VDC / 20mA)
Signal transmission behavior: In=Out
Step response (10-90%): 1.3 ms (for jump 4mA...20mA, typical)
Maximum temperature coefficient: < 0.01 %/K
Maximum transmission error: < 0.1 % (of final value)
Transmission error, typical: < 0.05 % (of final value)
Electrical isolation​
Overvoltage category: II
Pollution degree: 2
Electrical isolation Input/output/power supply IEC/EN61010-1
Standards/regulations: IEC/EN61010-1
Rated insulation voltage: 300 Vrms
Test voltage: 2.5 kV AC (50Hz, 60s)
Insulation: Safe isolation
Electrical isolation Output 1/output 2
Test voltage: 1.5 kV AC (50Hz, 60s)
Supply
Designation: Repeater power supply operation
Nominal supply voltage: 24 VDC -20%...+25%
Supply voltage range: 19.2 VDC ... 30 VDC
Max. current consumption: < 75 mA (24VDC / 20mA)
Power dissipation: < 1.45 W (24VDC / 20mA)
Power consumption: ≤ 1.8 W
Supply​
Designation: Signal conditioner operation
Nominal supply voltage: 24 VDC -20%...+25%
Supply voltage range: 19.2 VDC ... 30 VDC
Max. current consumption: < 46 mA (24VDC / 20mA)
Power dissipation: < 1.2 W (24VDC / 20mA)
Input dataSignal: Repeater power supply operation
Description of the input: Repeater power supply operation
Number of inputs: 1
Current input signal: 4 mA ... 20 mA
Transmitter supply voltage: > 21.5 V (20mA)
> 21 V (23mA)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Description of the input: Signal conditioner operation
Current input signal: 0 mA ... 20 mA
4 mA ... 20 mA
Voltage drop: < 3.9 V (in input isolating amplifier operation)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Output dataSignal: Repeater power supply operation
Output description: Repeater power supply operation
Number of outputs: 2
Current output signal: 4 mA ... 20 mA (active)
0 mA ... 20 mA
Load/output load current output: < 450 Ω (20mA)
< 380 Ω (23mA)
Output ripple: < 20 mVrms
Output behavior in the event of an error: 0 mA (Cable break in the input)
≥ 23 mA (Cable short-circuit in the input)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Signal: Signal conditioner operation
Output description: Signal conditioner operation
Current output signal: 0 mA ... 20 mA (active)
4 mA ... 20 mA (active)
Load/output load current output: < 450 Ω (20mA)
< 380 Ω (23mA)
Output ripple: < 20 mVrms
Output behavior in the event of an error: 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Underload/overload signal range: 0 mA ... 24 mA (Extended transmission range for diagnostics)
Connection dataConnection method: Push-in connection
Stripping length: 10 mm
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible (2 conductors with same cross section): 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve)
0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve)
Conductor cross section AWG: 24 ... 14
24 ... 22 (TWIN ferrule without plastic sleeve)
20 ... 16 (TWIN ferrule with plastic sleeve)
Ex dataEx installation (EPL): Gc
Div.2
InterfacesData communication (bypass)
HART function: Yes
Protocols supported: HART-transparent
SignalingStatus display: Green LED (supply voltage)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3edd36290ae8094db8e0add7aa964a6f/-S204x204-FJPG
Width: 12.5 mm
Height: 107.9 mm
Depth: 113.7 mm
Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715)
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Housing material: PA 6.6-FR
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (not assessed by UL)
Ambient temperature (operation): -40°C ... 60°C (Any mounting position)
-40°C ... 70°C (Derating)
Ambient temperature (storage/transport): -40°C ... 80°C
Permissible humidity (operation): 10 % ... 95 % (non-condensing)
Altitude range (≤ 2000 m)
Altitude: ≤ 2000 m (The technical data refers to altitudes ≤2000m above mean sea level. For altitudes >2000m above mean sea level, refer to the data sheet.)
Ambient temperature (operation): -40°C ... 60°C
-40°C ... 70°C (Derating)
Rated insulation voltage: 375 VPP (Power supply, input / output)
Altitude range (≤ 3000 m)
Height range: > 2000 m ... 3000 m
Ambient temperature (operation): -40°C ... 54°C
-40°C ... 63°C (Derating)
Rated insulation voltage: 190 VAC (Power supply, input / output)
110 VDC (Power supply, input / output)
Altitude range (≤ 4000 m)
Height range: > 3000 m ... 4000 m
Ambient temperature (operation): -40°C ... 48°C
-40°C ... 56°C (Derating)
Rated insulation voltage: 60 V AC/DC (Power supply, input / output)
Altitude range (≤ 5000 m)
Height range: > 4000 m ... 5000 m
Ambient temperature (operation): -40°C ... 42°C
-40°C ... 49°C (Derating)
Rated insulation voltage: 60 V AC/DC (Power supply, input / output)
ApprovalsCE
Certificate: CE-compliant
Note: and EN61326-1
ATEX
Identification: ï˜ II 3 G Ex ec IIC T4 Gc X
Certificate: PxCCIF11ATEX2924825
UKCAEx(UKEX)
Identification: ï˜ II 3 G Ex nA IIC T4 Gc
Certificate: PxCIF21UKEX2924825X
IECEx
Identification: Ex ec IIC T4 Gc
Certificate: IECEx BVS 10.0097X
CCC/China-Ex
Identification: Ex ec IIC T4 Gc
Certificate: 2022122316115971
UL, USA/Canada
Identification: UL508 Listed
UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Groups IIC, IIB, IIA T4
UL, USA/Canada​
Identification: UL 61010 Listed
Class I, Div. 2, Groups A, B, C, D T4
Class I, Zone 2, Group IIC T4
Shipbuilding approval
Certificate: DNV GL TAA000020C
Safety Integrity Level (SIL, IEC 61508)
Identification: 2
Performance Level (ISO13849)
Identification: d
DNV GL data
Temperature: B
Humidity: B
Vibration: A
EMC: A
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Electromagnetic HF field
Designation: Electromagnetic RF field
Standards/regulations: EN61000-4-3
Typical deviation from the measuring range final value: 3 %
Fast transients (burst)
Designation: Fast transients (burst)
Standards/regulations: EN61000-4-4
Typical deviation from the measuring range final value: 3 %
Conducted interference
Designation: Conducted interferences
Standards/regulations: EN61000-4-6
Typical deviation from the measuring range final value: 3 %
Standards and regulationsElectrical isolation: 3-way isolation
MountingMounting type: DIN rail mounting
Technical Specs
ECLASSECLASS-11.0: 27210120
ECLASS-12.0: 27210120
ECLASS-13.0: 27210120
ETIMETIM 9.0: EC002653
UNSPSCUNSPSC 21.0: 39121000
Description
Measuring transducer repeater power supply and input signal conditioner, HART-transparent. Transmits supplied or active 0/4Â…20 mA electrically isolated signals from the field to two loads. 4-way electrical isolation, Push-in connection, SIL, PL.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00369.pdf

Approvals_01170.pdf

Approvals_01826.pdf

Data_sheet_03942.pdf

Manual_00026.pdf

Manufacturer_declaration_00636.pdf

Manufacturer_declaration_01577.pdf

Manufacturer_declaration_16594.pdf

Manufacturer_declaration_17787.pdf

Package_slip_01567.pdf

Technical_drawing_41125.pdf