Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2941659
PHOENIX CONTACTNot available

DEK-OE-120AC/ 48DC/100 - Solid-state relay terminal block

Input solid-state relay terminal block, input: 120 V DC, output: 3 - 48 V DC/100 mA, terminal block width: 6.2 mm
Product Code: 2941659
Partner cod.: 2941659
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesGeneral: The housing is open on one side. The appropriate cover is D-DEK 1,5 GN (2716949).
Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place.
Product propertiesProduct type: Solid-state relay module
Product family: DEK
Application: Output function
Operating mode: 100% operating factor
Insulation characteristics
Insulation: Basic insulation
Insulation characteristics: Standards/regulations
Insulation: Basic insulation
Overvoltage category: III
Pollution degree: 2
Electrical propertiesTest voltage (Input/output): 2.5 kV AC (Input/output)
Input dataNominal input voltage UN: 120 VAC
Input voltage range in reference to UN: 0.9 ... 1.1
Input voltage range: 108 VAC ... 132 VAC
Switching threshold "0" signal in reference to UN: ≤ 0.4
Switching threshold "1" signal in reference to UN: ≥ 0.8
Typical input current at UN: 3.2 mA
Typical response time: 10 ms
Typical turn-off time: 20 ms
Operating voltage display: Yellow LED
Protective circuit: Reverse polarity protection
Surge protection
Transmission frequency: 3 Hz
Output dataContact switching type: 1 N/O contact
Design of digital output: electronic
Output voltage range: 3 VDC ... 48 VDC
Limiting continuous current: 100 mA
Voltage drop at max. limiting continuous current: ≤ 0.9 V
Output circuit: 2-conductor floating, 3-conductor ground-referenced
Protective circuit: Reverse polarity protection; Polarity protection diode
Freewheeling diode; Freewheeling diode
Output resistor: approx. 22 kΩ (for 3-conductor operation)
Connection dataConnection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm
DimensionsWidth: 6.2 mm
Height: 80 mm
Depth: 56 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -20°C ... 60°C
Ambient temperature (storage/transport): -20°C ... 70°C
Standards and regulationsStandards/regulations
Standards/regulations: IEC 60947-5-1
MountingMounting type: DIN rail mounting
Assembly instructions: in rows with zero spacing
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27371604
ECLASS-12.0: 27371604
ECLASS-13.0: 27371604
ETIMETIM 9.0: EC001504
UNSPSCUNSPSC 21.0: 39122300
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00006.pdf

Approvals_01560.pdf

Approvals_01561.pdf

Manufacturer_declaration_03578.pdf

Manufacturer_declaration_03579.pdf

Manufacturer_declaration_16703.pdf

Package_slip_00894.pdf

Product_information_00033.pdf

Product_information_00768.pdf

Technical_drawing_41232.pdf