Industrial Automation
Product properties | Product type: Single solid-state relay Operating mode: 100% operating factor Insulation characteristics Insulation: Basic insulation Insulation characteristics: Standards/regulations Insulation: Basic insulation Overvoltage category: III Pollution degree: 2 |
Electrical properties | Maximum power dissipation for nominal condition: 0.18 W Test voltage (Input/output): 2.5 kV (50Hz, 1min., input/output) |
Input data | Nominal input voltage UN: 60 VDC Input voltage range in reference to UN: 0.9 ... 1.1 Input voltage range: 54 VDC ... 66 VDC Switching threshold "0" signal, voltage: ⤠40 V Switching threshold "1" signal voltage: ⥠52 V Typical input current at UN: 3 mA Typical response time: 50 µs (at UN) Typical turn-off time: 800 µs (at UN) Transmission frequency: 100 Hz |
Output data | Contact switching type: 1 N/O contact Design of digital output: electronic Output voltage range: 3 VDC ... 48 VDC Limiting continuous current: 100 mA Voltage drop at max. limiting continuous current: ⤠1 V Output circuit: 2-conductor, floating Protective circuit: Reverse polarity protection; Polarity protection diode Surge protection |
Dimensions | Width: 5 mm Height: 28 mm Depth: 15 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection: RT III Ambient temperature (operation): -25°C ... 60°C Ambient temperature (storage/transport): -25°C ... 70°C |
Approvals | Corrosive gas test Identification: ISA-S71.04. G3 Harsh Group EN60068-2-60 |
Standards and regulations | Standards/regulations Standards/regulations: IEC 60664 EN50178 |
Mounting | Assembly instructions: in rows with zero spacing Mounting position: any |
ECLASS | ECLASS-11.0: 27371604 ECLASS-12.0: 27371604 ECLASS-13.0: 27371604 |
ETIM | ETIM 9.0: EC001504 |
UNSPSC | UNSPSC 21.0: 39122300 |