Product properties | Product type: Single solid-state relay Operating mode: 100% operating factor Insulation characteristics Insulation: Basic insulation Insulation characteristicsâ Insulation: Basic insulation |
Electrical properties | Test voltage (Input/output): 4 kV (50Hz, 1min., input/output) |
Input data | Nominal input voltage UN: 24 VDC Input voltage range: 4.25 VDC ... 32 VDC Switching threshold "0" signal, voltage: < 1 VDC Switching threshold "1" signal voltage: > 3.3 VDC Typical input current at UN: 15 mA Typical response time: < 100 µs Typical turn-off time: < 250 µs Transmission frequency: 100 Hz |
Output data | Design of digital output: electronic Output voltage range: 1 VDC ... 350 VDC Limiting continuous current: 1 A (see derating curve) Min. load current: 1 mA Leakage current: 100 µA Surge current: 20 A (tp = 1s) Voltage drop at max. limiting continuous current: 0.5 V Output circuit: 2-conductor Protective circuit: Reverse polarity protection; Polarity protection diode |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/15f4a59003335b4e85722216e4a8f1e4/-S204x204-FJPG Width: 10.5 mm Height: 43 mm Depth: 25.4 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -20°C ... 80°C Ambient temperature (storage/transport): -20°C ... 80°C |
Approvals | UKCA Certificate: UKCA-compliant |
Standards and regulations | Standards/regulations: EN61000-4-2 EN61000-4-3 EN61000-4-4 EN55011 |
Mounting | Assembly instructions: Can be aligned with > 9 mm spacing Mounting position: any |
ECLASS | ECLASS-11.0: 27371604 ECLASS-12.0: 27371604 ECLASS-13.0: 27371604 |