Industrial Automation
Product properties | Product type: Coupling relay Product family: PSRclassic Application: Safe switch off High demand Low demand Mechanical service life: 10x 106 cycles Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN61810-3 |
Electrical properties | Maximum power dissipation for nominal condition: 2.4 W Nominal operating mode: 100% operating factor Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 VAC Rated surge voltage/insulation: Safe isolation, reinforced insulation 6kV between the control circuits (A1/A2), (31/32), (13/14, 23/24) |
Input data | General Rated control circuit supply voltage US: 24 VDC -15% / +10% Power consumption at US: typ. 1.32 W Rated control supply current IS: typ. 55 mA Input voltage range: 20.4 VDC ... 26.4 VDC Inrush current: max. 100 mA Filter time: max. 5 ms (at A1 in the event of voltage dips at Us) max. 2 ms (Test pulse width; high test pulse at A1/A2) ⥠100 ms (Test pulse width; high test pulse at A1/A2) Test pulse rate=80xTest pulse width max. 5 ms (Test pulse width; low test pulse at A1/A2) ⥠50 ms (Test pulse rate; low test pulse at A1/A2) Test pulse rate=15xTest pulse width Typ. starting time with Us: 50 ms Typical release time: 50 ms Recovery time: 1 s Maximum switching frequency: 0.5 Hz Protective circuit: Surge protection; Suppressor diode, 33 V (A1 - A2) Operating voltage display: 1 x yellow LED |
Output data | Contact switching type: 2 enabling current paths 1 confirmation current path Contact material: AgCuNi, + 0.2µm Au Maximum switching voltage: 250 V AC/DC (N/O contact / N/C contact, observe the load curve) Minimum switching voltage: 15 V AC/DC (N/O contact / N/C contact) Limiting continuous current: 5 A (N/O contact, pay attention to the derating) 100 mA (N/C contact) Maximum inrush current: 5 A (N/O contact) 100 mA (N/C contact) Inrush current, minimum: 5 mA (N/O contact / N/C contact) Sq. Total current: 50 A2 (observe derating) Interrupting rating (ohmic load) max.: 120 W (24 V DC, Ã = 0 ms, N/C contact: 2.4 W) 192 W (48 V DC, Ã = 0 ms, N/C contact: 4.8 W) 162 W (60 V DC, Ã = 0 ms, N/C contact: 6 W) 66 W (110 V DC, Ã = 0 ms, N/C contact: 11 W) 60 W (220 V DC, Ã = 0 ms, N/C contact: 22 W) 1250 VA (250 V AC, Ã = 0 ms, N/C contact: 25 VA) Maximum interrupting rating (inductive load): 72 W (24 V DC, Ã = 40 ms, N/C contact: 2.4 W) 43 W (48 V DC, Ã = 40 ms, N/C contact: 4.8 W) 41 W (60 V DC, Ã = 40 ms, N/C contact: 6 W) 35 W (110 V DC, Ã = 40 ms, N/C contact: 11 W) 48 W (220 V DC, Ã = 40 ms, N/C contact: 22 W) Switching capacity: min. 75 mW Switching capacity (3600/h cycles): 5 A (24V (DC13)) 5 A (230 V (AC15)) Output fuse: 10 A gL/gG (N/O contact) 4 A gL/gG (for low-demand applications) 150 mA Fast-blow (N/C contact) |
Connection data | Connection technology pluggable: yes Conductor connection Connection method: Screw connection Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross-section AWG: 24 ... 12 Stripping length: 7 mm Screw thread: M3 |
Dimensions | Width: 17.5 mm Height: 99 mm Depth: 114.5 mm |
Material specifications | Housing material: Polyamide |
Characteristics | Safety data Stop category: 0 Safety data: ENISO13849 Category: 1 (Diagnostic coverage (DC) of the control unit at A1/A2 must be â¥90%) Performance level (PL): c (Diagnostic coverage (DC) of the control unit at A1/A2 must be â¥90%) Safety data: EN50156 Safety Integrity Level (SIL): 2 Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): 2 (max.10%of the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be â¥90%) Safety data: IEC 61508 - Low demand Safety Integrity Level (SIL): 2 (max.10%of the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be â¥90%) Safety data: ENIEC 62061 Safety Integrity Level (SIL): 1 (max.10%of the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be â¥90%) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Min. degree of protection of inst. location: IP54 Ambient temperature (operation): -20°C ... 55°C (observe derating) Ambient temperature (storage/transport): -40°C ... 70°C Maximum altitude: ⤠2000 m (Above sea level) Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing) Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing) Shock: 15g Vibration (operation): 10Hz...150Hz, 2g |
Approvals | CE Certificate: CE-compliant |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: IEC 60664-1 |
Mounting | Mounting type: DIN rail mounting Mounting position: any Connection method: Screw connection |
ECLASS | ECLASS-11.0: 27371819 ECLASS-13.0: 27371819 ECLASS-12.0: 27371819 |
ETIM | ETIM 9.0: EC001449 |
UNSPSC | UNSPSC 21.0: 39122200 |
Description other products