Industrial Automation
UK 35-PE/N - Installation ground terminal block
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | General: The NS 32... or NS 35... Cu DIN rail should be used for a connection cross section of 35 mm²/2 AWG. When aligned with a feed-through terminal block of the same shape, a cover must be used at insulation voltages > 630V. |
Product properties | Product type: Ground terminal block Number of connections: 4 Number of rows: 1 Potentials: 3 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Rated surge voltage: 8 kV Maximum power dissipation for nominal condition: 4.06 W |
Connection data | PEN function: yes Grounding foot: Yes Number of connections per level: 2 Nominal cross section: 35 mm² Rated cross section AWG: 2 Level 1 above 1 below 1 Screw thread: M6 Note: Please observe the current carrying capacity of the DIN rails. Tightening torque: 3.2 ... 3.7 Nm Stripping length: 16 mm Connection in acc. with standard: IEC 60947-7-1/IEC 60947-7-2 Conductor cross section rigid: 0.75 mm² ... 35 mm² Cross section AWG: 18 ... 2 (converted acc. to IEC) Conductor cross section flexible: 0.75 mm² ... 35 mm² Conductor cross section, flexible [AWG]: 18 ... 2 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.75 mm² ... 35 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.75 mm² ... 35 mm² Nominal current: 125 A Maximum load current: 125 A (with 35 mm² conductor cross section) Nominal voltage: 630 V (When aligned with a modular terminal block of the same shape, a separating disk must be used at voltages > 630V.) |
Dimensions | Width: 30.1 mm Height: 50 mm Depth on NS32: 67 mm Depth on NS35/7,5: 62 mm Depth on NS35/15: 69.5 mm |
Material specifications | Color: green-yellow-blue Flammability rating according to UL 94: V0 Insulating material group: I Insulating material: PA Static insulating material application in cold: -60°C Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)): 125°C Relative insulation material temperature index (Elec., UL 746 B): 130°C Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R26: HL 1 - HL 3 Calorimetric heat release NFPA 130 (ASTM E 1354): 27,5 MJ/kg Surface flammability NFPA 130 (ASTM E 162): passed Specific optical density of smoke NFPA 130 (ASTM E 662): passed Smoke gas toxicity NFPA 130 (SMP 800C): passed |
Mechanical properties | General Terminal block mounting: 2.5 Nm ... 3 Nm (PE foot with mounting screw, M5) Mechanical data Open side panel: No |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -60°C ... 105°C (max. short-term operating temperature RTI Elec.) Ambient temperature (storage/transport): -25°C ... 60°C (for a short time, not exceeding 24h, -60°C to +70°C) Ambient temperature (assembly): -5°C ... 70°C Permissible humidity (storage/transport): 30 % ... 70 % |
Standards and regulations | Connection in acc. with standard: IEC 60947-7-1/IEC 60947-7-2 |
Mounting | Mounting type: NS 35/7,5 NS35/15 NS32 Terminal block mounting: 2.5 Nm ... 3 Nm (PE foot with mounting screw, M5) |
ECLASS | ECLASS-11.0: 27141125 ECLASS-12.0: 27141125 ECLASS-13.0: 27250110 |
ETIM | ETIM 9.0: EC001329 |
UNSPSC | UNSPSC 21.0: 39121400 |