Industrial Automation
Product properties | Product type: Ground terminal block Number of connections: 2 Number of rows: 1 Potentials: 1 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Rated surge voltage: 8 kV Maximum power dissipation for nominal condition: 4.73 W |
Connection data | PEN function: yes Grounding foot: Yes Number of connections per level: 2 Nominal cross section: 50 mm² Rated cross section AWG: 1/0 Level 1 above 1 below 1 Screw thread: M6 Note: Please observe the current carrying capacity of the DIN rails. Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area. Tightening torque: 6 ... 8 Nm Stripping length: 24 mm Connection in acc. with standard: IEC 60947-7-2 Conductor cross section rigid: 16 mm² ... 50 mm² Cross section AWG: 4 ... 2 (converted acc. to IEC) Conductor cross section flexible: 25 mm² ... 50 mm² Conductor cross section, flexible [AWG]: 2 ... 2 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 25 mm² ... 50 mm² Flexible conductor cross section (ferrule with plastic sleeve): 25 mm² ... 50 mm² Nominal current: 150 A Maximum load current: 150 A (with 50 mm² conductor cross section) Nominal voltage: 1000 V |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/70d41ed62ec4e24d831b3c37dc260671/-S204x204-FJPG Width: 40 mm Height: 70.5 mm Depth on NS32: 88.5 mm Depth on NS35/7,5: 83.5 mm Depth on NS35/15: 91 mm |
Material specifications | Color: green-yellow Flammability rating according to UL 94: V2 Insulating material group: I Insulating material: PA Static insulating material application in cold: -60°C Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)): 125°C Relative insulation material temperature index (Elec., UL 746 B): 130°C Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R26: HL 1 - HL 3 Calorimetric heat release NFPA 130 (ASTM E 1354): 27,5 MJ/kg Surface flammability NFPA 130 (ASTM E 162): passed Specific optical density of smoke NFPA 130 (ASTM E 662): passed Smoke gas toxicity NFPA 130 (SMP 800C): passed |
Mechanical properties | General Terminal block mounting: 6 Nm ... 8 Nm (PE foot with mounting screw, M6) Mechanical data Open side panel: No |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -60°C ... 105°C (max. short-term operating temperature RTI Elec.) Ambient temperature (storage/transport): -25°C ... 60°C (for a short time, not exceeding 24h, -60°C to +70°C) Ambient temperature (assembly): -5°C ... 70°C Permissible humidity (storage/transport): 30 % ... 70 % |
Standards and regulations | Connection in acc. with standard: IEC 60947-7-2 |
Mounting | Mounting type: NS 35/7,5 NS35/15 NS32 NS 35/15-2,3 Terminal block mounting: 6 Nm ... 8 Nm (PE foot with mounting screw, M6) |