Industrial Automation
Product properties | Product type: Panel feed-through terminal block Number of positions: 1 Pitch: 8.1 mm Number of connections: 2 Number of rows: 1 Potentials: 1 Number of potentials: 1 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Nominal current IN: 32 A Nominal voltage UN: 800 V Degree of pollution: 3 Rated voltage (III/3): 800 V Rated surge voltage (III/3): 8 kV |
Connection data | Connection technology Connector system: PW 4 Nominal cross section: 4 mm² Conductor connection exterior Connection method: Push-in spring connection Connection direction of the conductor to plug-in direction: 45° Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section flexible: 0.2 mm² ... 6 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 6 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 4 mm² 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve: 0.5 mm² ... 1 mm² Internal cylindrical gage: A4 Stripping length: 10 mm Conductor connection interior Connection method: Solder connection Connection direction of the conductor to plug-in direction: 0° |
Mounting | Plate thickness: 1 mm ... 4 mm Attachment to feed-through panel Tightening torque: 0.5 Nm ... 0.6 Nm (Mounting screw torque) |
Material specifications | Material data - contact Note: WEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201 Contact material: Cu alloy Surface characteristics: tin-plated Material data - housing Color (Housing): gray (7042) Insulating material: PA Insulating material group: I CTI according to IEC 60112: 600 Flammability rating according to UL 94: V0 Glow wire flammability index GWFI according to EN60695-2-12: 850 Glow wire ignition temperature GWIT according to EN60695-2-13: 775 Temperature for the ball pressure test according to EN60695-10-2: 125°C Material data â actuating element Insulating material: PA Insulating material group: I CTI according to IEC 60112: 600 Flammability rating according to UL 94: V0 |
Notes | Safety note Safety note: ⢠Only electrically qualified personnel may install and operate the product. To recognize and prevent danger, the qualified personnel must be familiar with the basics of electrical engineering. ⢠Observe the technical data provided here and refer to the documents listed under âDownloadsâ. The download area contains important information, such as installation notes, technical drawings, and 3D data. ⢠To maintain the nominal voltage, cast the terminals on the inside. |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/e840d33717330747ad0c7b5d4b264f71/-S204x204-FJPG Pitch: 8.1 mm Width [w]: 8.1 mm |
Mechanical tests | Test for conductor damage and slackening Specification: IEC 60947-7-1:2009-04 Result: Test passed Pull-out test Specification: IEC 60947-7-1:2009-04 Conductor cross section/conductor type/tractive force setpoint/actual value: 0.2 mm² / solid / > 10 N 0.2 mm² / flexible / > 10 N 4 mm² / solid / > 60 N 4 mm² / flexible / > 60 N |
Electrical tests | Temperature-rise test Specification: IEC 60512-5-1:2002-02 Requirement temperature-rise test: Increase in temperature â¤45K Short-time withstand current Specification: IEC 60947-7-1:2009-04 Air clearances and creepage distances | 1. Insulation coordination Application: Metal wall 1.0mm...4.0mm Specification: IEC 60664-1:2007-04 Insulating material group: I Comparative tracking index (IEC 60112): CTI 600 Rated insulation voltage (III/3): 800 V Rated surge voltage (III/3): 8 kV minimum clearance value - non-homogenous field (III/3): 8 mm minimum creepage distance (III/3): 10 mm |
Environmental and real-life conditions | Vibration test Specification: IEC 60068-2-6:2007-12 Frequency: 10Hz...150Hz Sweep speed: 1octave/min 5g (60.1Hz...150Hz) Amplitude: 0.35mm (10Hz...60.1Hz) Test duration per axis: 2.5 h Glow-wire test Specification: IEC 60695-2-11:2000-10 Temperature: 960°C Time of exposure: 30 s Ambient conditions Ambient temperature (operation): -40°C ... 100°C (Depending on the current carrying capacity/derating curve) Ambient temperature (storage/transport): -40°C ... 70°C Relative humidity (storage/transport): 30 % ... 70 % Ambient temperature (assembly): -5°C ... 100°C |
Packaging specifications | Type of packaging: packed in cardboard |
ECLASS | ECLASS-11.0: 27141134 ECLASS-13.0: 27141134 ECLASS-12.0: 27141134 |
ETIM | ETIM 9.0: EC001283 |
UNSPSC | UNSPSC 21.0: 39121400 |
Description other products