Industrial Automation
Notes | General: A detailed circuit diagram can be found under Miscellaneous Downloads |
Product properties | Product type: Test terminal strip Number of positions: 19 Pitch: 8.2 mm Number of connections: 38 Number of rows: 1 Potentials: 19 Insulation characteristics Overvoltage category: III |
Electrical properties | Rated surge voltage: 4 kV Maximum power dissipation for nominal condition: 1.31 W Test surge voltage: 5 kV |
Connection data | Number of connections per level: 38 Nominal cross section: 6 mm² 1 level Stripping length: 12 mm Internal cylindrical gage: A5 Connection in acc. with standard: IEC 60947-7-1 Conductor cross section rigid: 0.5 mm² ... 10 mm² Cross section AWG: 20 ... 8 (converted acc. to IEC) Conductor cross section flexible: 0.5 mm² ... 6 mm² Conductor cross section, flexible [AWG]: 20 ... 10 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.5 mm² ... 6 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.5 mm² ... 6 mm² 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve: 0.5 mm² ... 1.5 mm² Maximum load current: 30 A (with 6 mm² conductor cross section) Nominal voltage: 400 V AC/DC Nominal cross section: 6 mm² 1 level Connection cross sections directly pluggable Conductor cross section rigid: 1 mm² ... 10 mm² Conductor cross-section flexible (ferrule without plastic sleeve): 1 mm² ... 6 mm² Flexible conductor cross section (ferrule with plastic sleeve): 1 mm² ... 6 mm² |
Dimensions | Width: 187.5 mm Height: 100 mm Depth: 56.5 mm Depth on NS35/7,5: 61.8 mm Depth on NS35/15: 69.3 mm Pitch: 8.2 mm |
Material specifications | Color: gray Flammability rating according to UL 94: V0 Insulating material group: I Insulating material: PA Static insulating material application in cold: -60°C Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)): 125°C Relative insulation material temperature index (Elec., UL 746 B): 130°C Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R26: HL 1 - HL 3 Calorimetric heat release NFPA 130 (ASTM E 1354): 27,5 MJ/kg Surface flammability NFPA 130 (ASTM E 162): passed Specific optical density of smoke NFPA 130 (ASTM E 662): passed Smoke gas toxicity NFPA 130 (SMP 800C): passed |
Mechanical properties | Mechanical data Open side panel: No |
Environmental and real-life conditions | Ambient conditions Ambient temperature (storage/transport): -25°C ... 60°C (for a short time, not exceeding 24h, -60°C to +70°C) Ambient temperature (assembly): -5°C ... 70°C Ambient temperature (actuation): -5°C ... 70°C Permissible humidity (storage/transport): 30 % ... 70 % |
Standards and regulations | Connection in acc. with standard: IEC 60947-7-1 |
Mounting | Mounting type: NS 35/7,5 NS35/15 |
ECLASS | ECLASS-11.0: 27141126 ECLASS-12.0: 27141126 ECLASS-13.0: 27250304 |
ETIM | ETIM 9.0: EC000902 |
UNSPSC | UNSPSC 21.0: 39121400 |
Description other products