PLC-RSC-120UC/21/SO46 - Relay Module


Notes | General: Separating plate PLC-ATP must be installed for voltages larger than 250ÃV (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or FBST 500.... The PLC-ATP separating plate should be installed for safe isolation between adjacent modules The PLC-ATP separating plate is required at the start and end of every PLC terminal strip. The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact. |
Product properties | Product type: Relay Module Product family: PLC-INTERFACE Application: Filter to prevent interference Operating mode: 100% operating factor Mechanical service life: 2x 107 cycles Insulation characteristics: Air clearances and creepage distances between the power circuits Insulation: Safe isolation, reinforced insulation Overvoltage category: III Pollution degree: 3 |
Electrical properties | Maximum power dissipation for nominal condition: 0.84 W Test voltage (Winding/contact): 4 kV AC (50ÃHz, 1Ãmin., winding/contact) Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 VÃAC Rated surge voltage: 6 kV |
Input data | Coil side Nominal input voltage UN: 120 VÃAC 110 VÃDC Input voltage range: 93.6 VÃAC ... 168 VÃAC (20ðC) 85.8 VÃDC ... 154 VÃDC (20ðC) Mains frequency: 50/60 Hz Drive and function: monostable Drive (polarity): polarized Typical input current at UN: 7 mA (50ÃHz) 8 mA (60ÃHz) Typical response time: 7 ms Typical release time: 20 ms Typical release voltage: 50 VÃAC Coil voltage: 60 VÃDC Protective circuit: Bridge rectifier RC element Status display: Yellow LED |
Output data | Switching Contact switching type: 1Ãchangeover contact Type of switch contact: Single contact Contact material: AgSnO Maximum switching voltage: 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...) Minimum switching voltage: 5 V (100 mA) Limiting continuous current: 6 A Maximum inrush current: 10 A (4 s) Min. switching current: 10 mA (12ÃV) Interrupting rating (ohmic load) max.: 140 W (24ÃVÃDC) 20 W (48ÃVÃDC) 18 W (60ÃVÃDC) 23 W (110ÃVÃDC) 40 W (220ÃVÃDC) 1500 VA (250ÃVÃAC) Switching capacity min.: 0.12 W Switching capacity: 2 A (at 24 V, DC13) 0.2 A (at 110 V, DC13) 0.1 A (at 220 V, DC13) 3 A (at 24 V, AC15) 3 A (at 120 V, AC15) 3 A (at 230 V, AC15) |
Connection data | Connection method: Screw connection Stripping length: 8 mm Screw thread: M3 Conductor cross section rigid: 0.14 mm² ... 2.5 mm² Conductor cross section flexible: 0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² (Single ferrule) 2x 0.5 mm² ... 1.5 mm² (TWIN ferrule) Conductor cross section AWG: 26 ... 14 Tightening torque: 0.6 Nm ... 0.8 Nm |
Dimensions | Width: 6.2 mm Height: 80 mm Depth: 94 mm |
Material specifications | Flammability rating according to UL 94: V0 (Housing) |
Environmental and real-life conditions | Ambient conditions Degree of protection (Relay): RT III (Relay) Degree of protection (Relay base): IP20 (Relay base) Degree of protection (Installation location): IP54 (Installation location) Ambient temperature (operation): -40°C ... 55°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ââ°¤ 2000 m |
Approvals | Corrosive gas test Identification: ISA-S71.04. G3 Harsh Group ENÃ60068-2-60 |
Standards and regulations | Standards/regulations Standards/regulations: ENÃ50178 ENÃ61810 Air clearances and creepage distances between the power circuits Standards/regulations: DINÃENÃ50178 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: in rows with zero spacing Mounting position: any |