ROCKWELL AUTOMATION 140M-RC2E-B16
ROCKWELL AUTOMATION 140M-RC2E-B16
ROCKWELL AUTOMATION 140M-RC2E-B16
ROCKWELL AUTOMATIONNot available

MPCB, Standard Magnetic Trip (Fixed at 13 x le), 1 - 1.6 A, Std. Performance, Frame Size RC

MPCB, Standard Magnetic Trip (Fixed at 13 x le), 1 - 1.6 A, Std. Performance, Frame Size RC
Product Code: 140M-RC2E-B16
Partner cod.: 140M-RC2E-B16
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Tecnichal data
With integrated auxiliary switchNo
With integrated under voltage releaseNo
Rated short-circuit breaking capacity lcu at 400 V, AC100 kA
Rated operation power at AC-3, 400 V0.55 kW
Rated permanent current Iu1.6 A
Rated operation power at AC-3, 230 V0.25 kW
Rated operating voltage230 A
Type of control elementTurn button
Overload release current setting1 A
Type of electrical connection of main circuitScrew connection
Rated frequency60 Hz
Magnetic trip current21 A
Short circuit current for group motor, max65 kA @ 480V
Current range1 to 1.6 A
Hp rating, max1 Hp @ 575V, 3-phase
Rated supply current (Ie), max0.1…32 A rated Supply Current
Electrical life cycle(Ie max.) 100000 operations
Insulation voltageRated 690V per IEC, SEV, VDE0660
KW rating, max1.1 kW @ 690V (AC-3), 3-phase
Rated thermal current (Ith), max0.1...32 A @ 60 °C ambient temperature
Rated impulse withstand voltageFor main circuits (Uimp) /overvoltage category @ 6 kV/III
Magnetic release currentFixed setting 13...14 x Ie max. Ie max. = maximum values of setting ranges, (±20 %)
Number of poles3
With thermal protectionYes
Phase failure sensitiveYes
Switch off techniqueThermomagnetic
Switching frequency, max25 ops/h
Trip class10
Rated insulation voltage (Ui)690 V
Phase loss protectionDifferential release
Width45 mm
Depth70 mm
Height95 mm
Frame sizeFrame size C (spring clamp), 32 A
Device constructionBuilt-in device fixed built-in technique
Degree of protection (IP)IP2X
Mechanical life operations100000 /h
Breaking capacityStandard breaking capacity
Protection typeAdjustable thermal/fixed magnetic (13 x In)
Vibration resistanceOperation (60068-2-6): 5 G
Shock resistanceTransport (60068-2-27): 30 G, 11 ms, all axes
Site altitude2000 m (NN)
Moisture heat40 °C, relative humidity 93 %, 56 days, (60068-2-3)
Dry heat100 °C, relative humidity < 50 %, 7 days, (60086-2-2)
Dependence on temperatureNo current reduction @ 60 °C
Moisture change climate23 °C/83 % relative humidity and 40 °C/92 % relative humidity, 56 cycles, (600068-2-30)
Pollution degree3
Ambient storage temperature, max-40 °C
Ambient operating temperature, max-25 °C
Ambient temperature compensation, max-20 °C
Utilization categoryMotor starter: AC-3 (IEC60947-4-1)
Overload protection characteristicsIEC 60947-4-1 motor protection
Technical Specs
Specifications
Trip Range:1 - 1.6A
Type:Standard Breaking Capacity
System Voltage Data
Supply Voltage:480V 60Hz
Circuit Breaker
Circuit Breaker Type:Motor Protection Circuit Breaker
Adj. Thermal Current Range (A):1 - 1.6A
Application:Standard Magnetic Trip (Fixed at 13 x le)
Frame Size:Frame Size C with Spring Clamp Terminals
Breaking Capacity:Standard Breaking Capacity
UL Listed Application Ratings:UL 508 - Manual Motor Controller
Short Circuit Coordination
Coordination Type:Type 1