ROCKWELL AUTOMATION 150-C43NCD
ROCKWELL AUTOMATION 150-C43NCD
ROCKWELL AUTOMATION 150-C43NCD
ROCKWELL AUTOMATIONNot available

Smart Motor Controller, 43A, 600V, 3-Phase, 50/60Hz, 100...240V AC, Open

SMC-3, 3-Wire, Open Type, 43A, 600V, 3-Phase, 50/60Hz Max, Control Voltage 100...240V AC
Product Code: 150-C43NCD
Partner cod.: 150-C43NCD
ROCKWELL AUTOMATION


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Tecnichal data
With displayNo
Voltage type for actuatingAC/DC
Rated operating voltage Ue200 V
Rated control supply voltage at AC 50 Hz100 V
Rated control supply voltage at AC 60 Hz100 V
Overload current14.3 A
Controller typeSMC-3
DV/DT protection1000V/µs for power circuit
Repetitive peak voltage1600V per UL/CSA/NEMA for power circuit
Operating frequency50/60 Hz per UL/CSA/NEMA for power circuit
Line connected motor power, max22 kW @ 500V AC, 50 Hz, 3-phase
Delta connected motor power, max20...60 Hp @ 575V AC, 60 Hz, 3-phase
Overvoltage categoryIII per IEC for side mount auxiliary contacts
Rated impulse voltage6 kV for power circuit
Dielectric withstand2500V AC per IEC for power circuit
Line connected motor current14.3...43 A @ 500/575V AC, 3-phase
Delta connected motor current25...74 A @ 500/575V AC, 3-phase
Insulation voltageRated 600V AC per UL/CSA/NEMA for power circuit
Rated operational voltage250V AC/30V DC per UL/CSA/NEMA for Side mount auxiliary contacts
Rated control power during start with fan200 mA @ 120V AC/100 mA @ 240V AC, 700 mA @ 24V AC/DC
Input OFF-state current<10 mA, <12 mA @ input off-state voltage (IN1, IN2) for control circuit
Short-circuit protection device listNon-time delay Thermal magnetic circuit breaker High capacity time delay class CC/J/L
Number of contactsTB-97, -98 (OVLD/Fault): 1 for auxiliary contacts
High capacity available fault current, max70 kA @ 600V, maximum current 90 A time delay Class J or Class L fuse for line connected motors
Type of currentTB-97, -98 (OVLD/Fault): AC/DC for auxiliary contacts
Conventional thermal current (Ith)TB-97, -98 (OVLD/Fault): 1 A for auxiliary contacts
Type of control circuitTB-97, -98 (OVLD/Fault): Electromagnetic relay for auxiliary contacts
Type of contactsTB-97, -98 (OVLD/Fault): Normally Open (N.O.) for auxiliary contacts
Utilization categoryTB-23, -24 (normal/up-to-speed), TB-33, -34 (normal/up-to-speed): C300/R150 per UL/CSA/NEMA for Side mount auxiliary contacts
Rated operational current, maxTB-97, -98 (OVLD/Fault): 0.6 A @ 120V AC and 0.3 A @ 240V AC for auxiliary contacts
Standard controller featureSoft stop
Standard available fault current, max10 kA @ maximum standard fuse 250 A for delta device operational current rating
Integrated motor overload protectionYes
Short circuit protection device performance (SCPD) typeType 1
Selectable overload trip classTrip Class 10, 15, or 20
Selectable start times2, 5, 10, 15, 20, 25, or 30 s
Input OFF-state voltage (IN1, IN2), max40V AC, 17V DC/12V AC for control circuit
Selectable current limit150%, 250%, 350%, and 450% of full load current
Input ON-state voltage, during start (IN1, IN2)85V AC, 19.2V DC/19.2V AC minimum for control circuit
Input ON-state current (IN1, IN2)9.8 mA @ 120V AC/19.6 mA @ 240V AC for control circuit, 7.3 mA @ 24V AC/DC for control circuit
Degree of protection (IP)IP2X
Weight2.25 kg
ShockOperational: 15 G
Width72 mm (2.83 inch)
Depth130 mm (5.12 inch)
Height206 mm (8.11 inch)
Cable size2.5...95 mm2 (14...3/0 AWG) for line power terminals
VibrationOperational: 1.0 G peak, 0.15 mm (0.006 inch) displacement
MakeTB-97, -98 (OVLD/Fault): 432VA for auxiliary contacts
BreakTB-97, -98 (OVLD/Fault): 72VA for auxiliary contacts
Tightening torque11.3...12.4 Nm (100...110 lb.inch) for load power terminals
Internal bypassYes
FunctionSingle direction
Selectable kick start - 450% FLA0, 0.5, 1.0, or 1.5 s
Selectable initial torque15%, 25%, 35%, and 65% of locked rotor torque
Selectable soft stopOff, 100%, 200%, or 300% of the start time setting when wired
Steady state heat dissipation34 W
Storage and transportation temperature-25 °C
Rated surrounding temperature range without derating-5 °C
Humidity5...95% noncondensing
Operating temperatureOpen: -5 to 50 °C (23 to 122 °F)
EMC emission levelsRadiated emission: Class A per IEC
EMC immunity levelsSurge transient: per EN/IEC 60947-4-2 per IEC
Altitude2000 m
Pollution degree2
Mounting hole size5.3 mm
Number of polesEquipment is designed for 3-phase only for power circuit
EnclosureOpen type