Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 1110043
PHOENIX CONTACT 1110043
PHOENIX CONTACTNon disponibile

UNO2-PS/1AC/24DC/960W - Power supply unit

Primary-switched power supply unit, UNO POWER, Screw connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 40 A, adjustable from 24 V DC ... 28 V DC
Cod. Articolo: 1110043
Cod. Fornitore: 1110043
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Descrizione
Caratteristiche Tecniche
Input dataAC operation
Supply system configuration: Star network (TN, TT, IT (PE))
Nominal input voltage range: 100 V AC ... 240 V AC
Input voltage range: 100 V AC ... 240 V AC -15 % ... +10 %
110 V AC ... 240 V AC ±10 % (UL)
Derating: < 99 V AC (1 %/V)
Typical national grid voltage: 120 V AC
230 V AC
Voltage type of supply voltage: AC
Inrush current: typ. 15 A (at 25 °C)
Inrush current integral (I2t): < 0.5 A2s
Frequency range (fN): 50 Hz ... 60 Hz ±10 %
Mains buffering time: typ. 17 ms (120 V AC)
typ. 23 ms (230 V AC)
Current consumption: 10.5 A (100 V AC)
9 A (120 V AC)
4.7 A (230 V AC)
4.5 A (240 V AC)
9.5 A (110 V AC (UL))
4.5 A (240 V AC (UL))
Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester
Switch-on time: typ. 1 s
Device mains fuse: 20 A internal (device protection), slow-blow
Recommended breaker for input protection: 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: typ. 93.6 % (120 V AC)
typ. 94.8 % (230 V AC)
Nominal output voltage: 24 V DC
Setting range of the output voltage (USet): 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN): 40 A
Short-circuit-proof: yes
No-load proof: yes
Derating: 55 °C ... 70 °C
Crest factor: typ. 1.6 (120 V AC)
typ. 1.6 (230 V AC)
Output power (PN): 960 W
Connection in parallel: yes, for redundancy
Connection in series: yes, for increased output voltage
Feedback voltage resistance: ≤ 35 V DC
Protection against overvoltage at the output (OVP): ≤ 35 V DC
Residual ripple: typ. 150 mVPP (with nominal values)
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 3 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Rise time: < 1 s (UOut = 10 % ... 90 %)
Minimum no-load power dissipation: < 5 W (120 V AC)
Maximum no-load power dissipation: < 4 W (230 V AC)
Minimum nominal load power dissipation: < 67 W (120 V AC)
Power loss nominal load max.: < 53 W (230 V AC)
Signal relay 13/14
Connection level: 3.x
Connection labeling: 3.1 (13), 3.2 (14)
Switch contact (floating): OptoMOS
Switching voltage: max. 30 V AC/DC
max. 60 V DC
Current carrying capacity: max. 50 mA
State condition: DC OK (UOut > 0,9 x UN) (Contact closed)
UOUT < 0,9 x UN (Contact open)
Connection dataInput
Position: 1.x
Identification: 1.1 (), 1.2 (L), 1.3 (N)
Conductor connection
Connection method: Screw connection
rigid: 0.2 mm² ... 6 mm²
flexible: 0.2 mm² ... 4 mm²
flexible with ferrule without plastic sleeve: 0.25 mm² ... 4 mm²
flexible with ferrule with plastic sleeve: 0.25 mm² ... 4 mm²
rigid (AWG): 24 ... 10 (Cu)
Stripping length: 8 mm
Tightening torque: 0.5 Nm ... 0.6 Nm
4 lbf-in. ... 5 lbf-in.
Drive form screw head: Slotted L
Output
Position: 2.x
Identification: 2.1, 2.2 (+), 2.3, 2.4 (-)
Conductor connectionâۉ€¹
Connection method: Screw connection
rigid: 0.5 mm² ... 16 mm²
flexible: 0.5 mm² ... 16 mm²
flexible with ferrule without plastic sleeve: 0.5 mm² ... 16 mm²
flexible with ferrule with plastic sleeve: 0.5 mm² ... 16 mm²
rigid (AWG): 20 ... 6 (Cu)
Stripping length: 10 mm
Tightening torque: 1.2 Nm ... 1.5 Nm
10 lbf-in. ... 13 lbf-in.
Drive form screw head: Slotted L
Signal
Position: 3.x
Identification: 3.1 (13), 3.2 (14)
Conductor connectionâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Connection method: Screw connection
rigid: 0.5 mm² ... 16 mm²
flexible: 0.5 mm² ... 16 mm²
flexible with ferrule without plastic sleeve: 0.5 mm² ... 16 mm²
flexible with ferrule with plastic sleeve: 0.5 mm² ... 16 mm²
rigid (AWG): 20 ... 6 (Cu)
Stripping length: 10 mm
Tightening torque: 1.2 Nm ... 1.5 Nm
10 lbf-in. ... 13 lbf-in.
Drive form screw head: Slotted L
SignalingLED signaling
Types of signaling: LED DC OK âۉ€œ signal state operation (UN = 24 V DC, IOut = IN)
Function: Visual operating state display
Color: green
LED off: Supply voltage input AC not present (Off)
LED on (green), DC OK: UOUT > 0,9 x UN (On (green), DC OK)
LED on (flashing green) DC OK < 0.9 x UN: UOUT < 0,9 x UN (on (flashing green))
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
3 kV AC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2.4 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: UNO POWER
MTBF (IEC 61709, SN 29500): > 900000 h (25 °C)
> 530000 h (40 °C)
> 280000 h (55 °C)
Environmental protection directive: RoHS Directive 2011/65/EU
WEEE
Reach
Data management status
Article revision: 01
Insulation characteristics
Protection class: I
Degree of pollution: 2
DimensionsItem dimensions
Width: 126 mm
Height: 130 mm
Depth: 129 mm
125 mm (Device depth (DIN rail mounting))
Installation dimensions
Installation distance right/left (active, passive): 0 mm / 0 mm
Installation distance top/bottom (active, passive): 30 mm / 30 mm
MountingMounting type: DIN rail mounting
Assembly note: alignable: 0 mm horizontally, 30 mm vertically
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: no
Material specificationsFlammability rating according to UL 94: V0 (Housing, terminal blocks)
Housing material: Metal
Aluminum (AlMg3) / sheet steel, zinc-plated
Hood version: Stainless steel
Side element version: Aluminum
Foot latch material: Sheet steel, zinc-plated
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport): -40 °C ... 85 °C
Ambient temperature (start-up type tested): -40 °C
Maximum altitude: ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m)
Max. permissible relative humidity (operation): ≤ 95 % (at 25 °C, non-condensing)
Shock (operation): 18 ms, 30g, per spatial direction (IEC 60068-2-27)
Vibration (operation): < 13.2 Hz, amplitude ±1.0 mm (according to IEC 60068-2-6)
5 Hz ... 100 Hz, 0.7g (EN 60068-2-6)
Temp code: T4 (-25 °C ... +70 °C; >55 °C, derating: 2.5 %/K)
Standards and regulationsOvervoltage category
EN 61010-1: II (≤ 3000 m)
Overvoltage categoryâۉ€¹
EN 62477-1: III (≤3000 m)
Safety of power supply units up to 1100 V (insulation distances)
Standard designation: Safety of power supply units up to 1100 V (insulation distances)
Standards/specifications: DIN EN 61558-2-16
Electrical safety
Standard designation: Electrical safety
Standards/specifications: IEC 61010-2-201 (SELV)
Electronic equipment for use in power installations
Standard designation: Equipping high voltage installations with electronic equipment
Standards/specifications: EN 50178/VDE 0160 (PELV)
Safety for measurement, control, and laboratory equipment
Standard designation: Safety for equipment for measurement, control, and laboratory use
Standards/specifications: IEC 61010-1
Protective extra-low voltage
Standard designation: Protective extra-low voltage
Standards/specifications: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Safe isolation
Standard designation: Safe isolation
Standards/specifications: IEC 61558-2-16
IEC 61010-2-201
Limitation of harmonic line currents
Standard designation: Limitation of harmonic line currents
Standards/specifications: EN 61000-3-2
Mains voltage dips
Standard designation: Requirement of the semiconductor industry with regard to mains voltage dips
Standards/specifications: SEMI F47 - 0706 (180 V AC)
ApprovalsUL
Identification: UL/C-UL Listed UL 61010-1
ULâۉ€¹
Identification: UL/C-UL Listed UL 61010-2-201
ULâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Identification: UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
SIQ
Identification: CB scheme (IEC 61010-1, IEC 61010-2-201)
EMC dataElectromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
Interference emission: Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
EMC requirements for noise immunity: EN 61000-6-2
Conducted noise emission: EN 55016
EN 61000-6-3 (Class B)
Noise emission: EN 55016
EN 61000-6-3 (Class B)
Harmonic currents
Standards/regulations: EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Flicker
Standards/regulations: EN 61000-3-3
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: EN 61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 6 kV (Test Level 3)
Discharge in air: 8 kV (Test Level 3)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN 61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
Test field strength: 10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN 61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN 61000-4-5
Surge voltage load (surge)âۉ€¹
Input: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output: 0.5 kV (Test Level 2 - symmetrical)
1 kV (Test Level 2 - asymmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: EN 61000-4-6
Conducted interferenceâۉ€¹
Input/Output: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Voltage dips
Standards/regulations: EN 61000-4-11
Voltage: 230 V AC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 25 / 30 periods
12 periods
1 period
Comments: Criterion A
Criterion B
Additional text: Test Level 2
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Descrizione
UNO2-PS/1AC/24DC/960W Alimentatore