Input data | AC operation Supply system configuration: Star network (TN, TT, IT (PE)) Nominal input voltage range: 220 VAC ... 240 VAC Input voltage range: 220 VAC ... 240 VAC -15%...+10% Switch-on voltage: typ. 70 VAC Shut-down voltage: typ. 50 VAC Electric strength, max.: ⤠300 VAC 15 s Typical national grid voltage: 230 VAC Voltage type of supply voltage: AC Inrush current integral (I2t): < 0.3 A2s Inrush current limitation: < 13.5 A (after 1ms) AC frequency range: 50 Hz ... 60 Hz ±10% Mains buffering time: > 20 ms (190VAC) > 20 ms (230 V AC) Current consumption: 1.3 A (230 V AC) Nominal power consumption: 285.7 VA Power factor (cos phi): 0.91 Input fuse: 3.15 A (internal (device protection)) Recommended breaker for input protection: 4 A ... 16 A (Characteristic B, C, Z) Discharge current to PE: < 3.5 mA < 1.7 mA (264VAC, 60Hz) POWER factor: > 0.9 (230 V AC) DC operation Nominal input voltage range: 220 VDC ... 400 VDC Input voltage range: 220 VDC ... 400 VDC -15%...+5% Derating: < 99 VDC (2 %/V) Switch-on voltage: typ. 95 VDC Shut-down voltage: typ. 50 VDC Electric strength, max.: ⤠420 VDC Voltage type of supply voltage: DC Mains buffering time: > 20 ms (185VDC) > 25 ms (400VDC) Current consumption: 1.3 A (220 VDC) 0.7 A (400VDC)
|
Output data | Efficiency: typ. 92.5 % (230 V AC) typ. 94 % (400VDC) Output characteristic: U/I with dynamic load reserve Nominal output voltage: 48.5 VDC ±1% Nominal output current (IN): 5 A Dynamic Boost (IDyn.Boost): 7.5 A (5 s) Derating: > 60°C ... 70°C (2.5%/K) POWER factor: > 0.9 (120VAC) > 0.9 (230 V AC) Feedback voltage resistance: ⤠60 VDC Protection against overvoltage at the output (OVP): ⤠58 VDC Control deviation: < 1.5 % (change in load, static 10 % ... 90 %) < 4 % (Dynamic load change 10 % ... 90 %, 10 Hz) < 0.1 % (change in input voltage ±10 %) Residual ripple: < 20 mVPP (with nominal values) Short-circuit-proof: yes No-load proof: yes Output power: 240 W 360 W Peak switching voltages nominal load: < 15 mVPP Maximum no-load power dissipation: typ. 4 W (230 V AC) typ. 4 W (400VDC) Power loss nominal load max.: typ. 20 W (230 V AC) typ. 15 W (400VDC) Short-circuit current: < 7 ADC (Permanent) Rise time: 20 ms (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Signal: DC OK Continuous load current: 100 mA Signal relay 13/14 Default: closed Digital: 30 VAC 30 VDC 100 mA
|
Connection data | Input Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 1.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Output Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 4 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 1.5 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 12 Signal Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 0.75 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 1.5 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 0.75 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm² Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 1 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 18
|
Signaling | Types of signaling: Floating signal contact Signal output: LED status indicator Signalization designation: DC OK Status display: LED Color: green DC OK: UOUT > 0.7 x UN (UN = 48VDC)
|
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 3.5 kV AC (type test) 1.5 kV AC (routine test)
|
Product properties | Product type: Power supply Product family: TRIO POWER MTBF (IEC 61709, SN 29500): > 2220000 h (25°C) > 1280000 h (40°C) > 560000 h (60°C) > 2220000 h (25°C) > 1280000 h (40°C) > 560000 h (60°C) Insulation characteristics Protection class: I (in closed control cabinet) Degree of pollution: 2
|
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/9240672528a5f64d9507d9acab7c1ea2/-S204x204-FJPG Width: 42 mm Height: 130 mm Depth: 160 mm Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 50 mm / 50 mm
|
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: horizontally 0 mm (⤠40°C) 10 mm (⤠70°C), vertically 50 mm Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No
|
Material specifications | Flammability rating according to UL94 (housing / terminal blocks): V0 Housing material: Metal Type of housing: Aluminum (AlMg3) Hood version: Polycarbonate
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>60°Cderating:1.6%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ⤠2000 m Climatic class: 3K3 (EN60721) Max. permissible relative humidity (operation): ⤠95 % (at 25°C, non-condensing) Shock: 20m/s² (2g), 11ms, ±100 Schocks (DINEN50125-3, DINEN60068-2-27) Vibration (operation): 5Hz...2kHz, 2.3m/s² (0.23g) (RMS) 5h (DIN EN 50125-3, DIN EN 60068-2-64)
|
Standards and regulations | Rail applications: EN50121-3-2 EN50121-4 EN50124-1 EN50125-3 IEC 62236-3-2 IEC 62236-4 IEC 62236-5 Standard â Limitation of mains harmonic currents: EN61000-3-2 Standard - Electrical safety: EN61010-1 VDE0805 (SELV) Standard â Safety extra-low voltage: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation: IEC 61010-2-201 IEC 61558-2-16 Standard - Safety of power supply units up to 1100 V (insulation distances): DINEN61558-2-16 Overvoltage category EN 62477-1: II(â¤2000m) III(â¤2000m)
|
Approvals | UL approvals: UL61010-1 UL 61010-2-201 Conformity/Approvals SIL in accordance with IEC 61508: 0
|
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC Interference emission: Interference emission in accordance with EN61000-6-3 (residential and commercial) and EN61000-6-4 (industrial) EMC requirements for noise immunity: EN61000-6-1 EN61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Conducted noise emission: EN55016 EN61000-6-3 (Class B) Noise emission: EN 55011 (EN 55022) EN55016 EN61000-6-3 (Class B) Harmonic currents Standards/regulations: EN61000-3-2 Frequency range: ClassA Flicker Standards/regulations: EN61000-3-3 Frequency range: 0 kHz ... 2 kHz Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: 6 kV (Test Level 4) Discharge in air: 8 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2 GHz 2 GHz ... 2.7 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level X) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 2 kV (Test Level 4 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: EN61000-4-5 Input: 2 kV (Test Level 4 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Voltage dips Standards/regulations: EN61000-4-11 Voltage: 230 VAC Frequency: 50 Hz Voltage dip: 70 % 40 % 0 % Number of periods: 25 periods 10 periods 1 period Additional text: Test Level 2 Comments: Criterion A Emitted interference Standards/regulations: EN61000-6-3 Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
|