PHOENIX CONTACT 2866310
PHOENIX CONTACTNon disponibile

TRIO-PS/1AC/24DC/ 5 - Power supply unit

Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/5 A
Cod. Articolo: 2866310
Cod. Fornitore: 2866310
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Input dataAC operation
Nominal input voltage range: 100 VAC ... 240 VAC
Input voltage range: 85 VAC ... 264 VAC (Derating < 90 V AC: 2,5 %/V)
Derating: < 90 VAC (2.5%/V)
Input voltage range AC: 85 VAC ... 264 VAC (Derating < 90 V AC: 2,5 %/V)
Electric strength, max.: 300 VAC
Voltage type of supply voltage: AC
Inrush current: < 15 A
Inrush current integral (I2t): 1.1 A2s
AC frequency range: 45 Hz ... 65 Hz
Mains buffering time: > 20 ms (120VAC)
> 110 ms (230 V AC)
Current consumption: 1.65 A (120VAC)
0.9 A (230 V AC)
Nominal power consumption: 189 VA
Protective circuit: Transient surge protection; Varistor
Power factor (cos phi): 0.72
Typical response time: < 1 s
Input fuse: 3.15 A (slow-blow, internal)
Permissible backup fuse: B6 B10 B16
Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: 89 % (for 230 V AC and nominal values)
Output characteristic: U/I
Nominal output voltage: 24 VDC ±1%
Setting range of the output voltage (USet): 22.5 VDC ... 29.5 VDC (> 24 VDC, constant capacity restricted)
Nominal output current (IN): 5 A (UOUT = 24 V DC)
Derating: 55°C ... 70°C (2.5%/K)
Feedback voltage resistance: 35 VDC
Protection against overvoltage at the output (OVP): < 35 VDC
Max. capacitive load: unlimited
Active current limitation: approx. 10A (for short-circuit)
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 20 mVPP
Output power: 120 W
Peak switching voltages nominal load: < 30 mVPP
Maximum no-load power dissipation: 1.1 W
Power loss nominal load max.: 18 W
Rise time: < 2 ms (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 9 mm
Screw thread: M2,5
Tightening torque, min: 0.4 Nm
Tightening torque max: 0.5 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 9 mm
Screw thread: M2,5
Tightening torque, min: 0.4 Nm
Tightening torque max: 0.5 Nm
SignalingTypes of signaling: LED
Operating voltage display: Green LED
Signal output
Status display: "DC OK" LED green
Note on status display: UOUT > 21.5 V: LED lights up
Electrical propertiesInsulation voltage input/output: 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE: 500 VDC (type test)
Insulation voltage input / PE: 2 kV AC (type test)
2 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: TRIO POWER
MTBF (IEC 61709, SN 29500): > 2031000 h
Insulation characteristics
Protection class: I (with PE connection)
Overvoltage category: III
Degree of pollution: 2
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/fecc2450a16fa84a8e25d1ee1b8e7ae1/-S204x204-FJPG
Width: 40 mm
Height: 130 mm
Depth: 115 mm
Installation dimensions
Installation distance right/left: 0 mm / 0 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingMounting type: DIN rail mounting
Assembly instructions: alignable: horizontally 0mm, vertically 50mm
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsHousing material: Metal
Type of housing: Steel sheet, zinc-plated
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 15g in all directions in acc. with IEC 60068-2-27
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsStandard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV)
Standard – Limitation of mains harmonic currents: EN61000-3-2
Standard - Electrical safety: EN60950-1/VDE0805 (SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment: EN50178
Standard – Safety extra-low voltage: EN60950-1 (SELV)
EN60204 (PELV)
Standard - Safe isolation: DINVDE0100-410
ApprovalsShipbuilding approval: DNVGL(EMCA)
UL approvals: UL/C-UL listed UL508
UL/C-UL Recognized UL60950-1
Conformity/Approvals
SIL in accordance with IEC 61508: 0
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 8 kV (Test Level 3)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 10 V/m
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 4 kV (Test Level 4 - asymmetrical)
Signal: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
Frequency range: 10 kHz ... 15 kHz
Comments: Criterion A
Voltage: 3 V (Test Level 2)
Conducted interference​​
Frequency range: 10 kHz ... 15 kHz
Comments: Criterion A
Voltage: 3 V (Test Level 2)
Voltage dips
Standards/regulations: EN61000-4-11
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Specifiche
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 8.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00153.pdf

Approvals_01848.pdf

Data_sheet_03632.pdf

Manufacturer_declaration_00469.pdf

Manufacturer_declaration_02996.pdf

Manufacturer_declaration_05508.pdf

Manufacturer_declaration_15306.pdf

Package_slip_02436.pdf

Technical_drawing_39038.pdf

Various_00006.pdf