Input data | AC operation Network type: Star network Input voltage range: 100 VÃAC ... 240 VÃAC -15Ã%Ã...Ã+10Ã% Derating: < 100 VÃAC ... 85 VÃAC (1Ã%/V) Typical national grid voltage: 120 VÃAC 230 VÃAC Voltage type of supply voltage: AC Inrush current: typ. 30 A (25ðC) Inrush current integral (I2t): typ. 0.35 A2s Frequency range (fN): 50 Hz ... 60 Hz ñ10Ã% Mains buffering time: typ. 25 ms (120ÃVÃAC) typ. 25 ms (230ÃVÃAC) Current consumption: 1 A (100ÃVÃAC) 0.45 A (240ÃVÃAC) Protective circuit: Transient surge protection; Varistor Switch-on time: typ. 2 s Device mains fuse: 4 A internal (device protection), slow-blow Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K) Discharge current to PE: < 0.25 mA DC operation Input voltage range: 110 VÃDC ... 250 VÃDC -20Ã%Ã...Ã+10Ã% Derating: < 110 VÃDC ... 88 VÃDC (1Ã%/V) Voltage type of supply voltage: DC Current consumption: 0.88 A (110ÃVÃDC) 0.38 A (250ÃVÃDC)
|
Output data | Efficiency: > 92.5 % (120ÃVÃAC) > 94 % (230 V AC) Nominal output voltage: 24 VÃDC Nominal output current (IN): 3.75 A Short-circuit-proof: yes No-load proof: yes Derating: > 50°C ... 70°C (2Ã%Ã/ÃK) Crest factor: typ. 1.78 typ. 1.87 Output power (PN): 90 W Connection in parallel: yes, for increasing power and redundancy with diode Connection in series: yes, for increased output voltage Feedback voltage resistance: ââ°¤ 35 VÃDC Protection against overvoltage at the output (OVP): < 35 VÃDC Residual ripple: typ. 100 mVPP Control deviation: < 0.5 % (Static load change 10Ã% ... 90Ã%) < 3 % (Dynamic load change 10Ã% ... 90Ã%, (10 Hz)) < 0.1 % (change in input voltage ñ10 %) Rise time: typ. 100 ms (UOutÃ=Ã10Ã%Ã...Ã90Ã%) Minimum no-load power dissipation: < 0.21 W (120ÃVÃAC) Maximum no-load power dissipation: < 0.21 W (230 V AC) Minimum nominal load power dissipation: < 7 W (120ÃVÃAC) Power loss nominal load max.: < 5.7 W (230 V AC) Integrated fuse protection: no
|
Connection data | Input Position: 1.x Connection technology Position marking: 1.1, 1.2Ã(L), 1.3, 1.4Ã(N) Conductor connection Connection method: Push-in connection rigid: 0.2 mm² ... 2.5 mm² 1 mm² (recommended) flexible: 0.2 mm² ... 2.5 mm² 1 mm² (recommended) flexible with ferrule without plastic sleeve: 0.5 mm² ... 1.5 mm² 1 mm² (recommended) flexible with ferrule with plastic sleeve: 0.2 mm² ... 1 mm² 1 mm² (recommended) rigid (AWG): 24 ... 14 (Cu) 17 (recommended) Stripping length: 10 mm (rigid/flexible) 10 mm (Ferrule) Output Position: 2.x Connection technologyââ¬Ã¢¹ Position marking: 2.1, 2.2, 2.3, 2.4 (+), 2.5, 2.6, 2.7, 2.8Ã(-) Conductor connectionââ¬Ã¢¹ Connection method: Push-in connection rigid: 0.2 mm² ... 2.5 mm² 1 mm² (recommended) flexible: 0.2 mm² ... 2.5 mm² 1 mm² (recommended) flexible with ferrule without plastic sleeve: 0.5 mm² ... 1.5 mm² 1 mm² (recommended) flexible with ferrule with plastic sleeve: 0.2 mm² ... 1 mm² 1 mm² (recommended) rigid (AWG): 24 ... 14 (Cu) 17 (recommended) Stripping length: 10 mm (rigid/flexible) 10 mm (Ferrule)
|
Signaling | LED signaling Types of signaling: LED DCÃOK ââ¬Ã¢ signal state operation (UN = 24ÃVÃDC, IOut = IN) Function: Visual operating state display Color: green LED off: Supply voltage input AC not present (Off) LED on (green), DC OK: UOutÃ>0.9 x UN (UN = 24ÃVÃDC) (on) Signal threshold: > 0,9 x UN (UN = 24ÃVÃDC) (LED lights up green) < 0,9 x UN (UN = 24ÃVÃDC) (LED off)
|
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 4 kV AC (type test) 3.75 kV AC (routine test)
|
Product properties | Product type: Power supply Product family: STEPÃPOWER MTBF (IEC 61709, SN 29500): > 2036000 h (25ðC) > 1175000 h (40ðC) > 777000 h (50ðC) Environmental protection directive: RoHS Directive 2011/65/EU WEEE Reach Insulation characteristics Protection class: II (in closed control cabinet) Degree of pollution: 2
|
Dimensions | Item dimensions Width: 72 mm Height: 90 mm Depth: 43 mm 37 mm (Device depth (DIN rail mounting)) Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/2699757412e688419cb0966ffa723a9a/-S204x204-FJPG Horizontal pitch: 4 Div. (DINÃ43880) Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 30 mm / 30 mm
|
Mounting | Mounting type: DIN rail or direct mounting Assembly instructions: alignable: 0Ãmm horizontally, 30Ãmm vertically Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: PCB only yes
|
Material specifications | Flammability rating according to UL 94: V0 (Housing, terminal blocks, base latches) Housing material: Plastic Polycarbonate Foot latch material: Polyamid
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -10°C ... 70°C (Derating > 50°C: 2Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ââ°¤ 3000 m (> 2000Ãm, Derating: 10Ã%/1000Ãm) Max. permissible relative humidity (operation): ââ°¤ 95 % (non-condensing) Shock (operation): 18Ãms, 30g, per spatial direction (IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ñ2.5 mm (IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min.
|
Standards and regulations | Overvoltage category EN 61010-1: IIÃ(ââ°¤Ã3000Ãm) Overvoltage categoryââ¬Ã¢¹ EN 62477-1: IIIÃ(ââ°¤Ã2000Ãm) Electrical safety Standard designation: Electrical safety Standards/specifications: IEC 61010-1 (SELV) Protective extra-low voltage Standard designation: Protective extra-low voltage Standards/specifications: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Safe isolation Standard designation: Safe isolation Standards/specifications: IEC 61558-2-16 Low-voltage power supplies, DC output Standard designation: Low-voltage power supplies, DC output Standards/specifications: ENÃ61204-3 Safety requirements for electrical equipment for measurement, control, and laboratory use Standard designation: Safety requirements for electrical equipment for measurement, control, and laboratory use Standards/specifications: IEC 61010-1 Household and similar electrical appliances - Safety Standard designation: Safety of electrical devices for household use and similar purposes Standards/specifications: DINÃENÃ60335-1 Electric vehicle conductive charging system - PartÃ21-2: EMC requirements for off board electric vehicle charging systems Standard designation: Electric vehicle conductive charging system - PartÃ21-2: EMC requirements for off board electric vehicle charging systems Standards/specifications: IEC 61851-21-2 Note: ClassÃB
|
Approvals | UL Identification: ULÃ1310ÃClassÃ2 PowerÃUnits ULââ¬Ã¢¹ Identification: UL/C-UL Listed ULÃ61010-1 ULââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Identification: UL/C-UL Listed ULÃ61010-2-201 ULââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Identification: UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC Interference emission: Interference emission in accordance with ENÃ61000-6-3 (residential and commercial) and ENÃ61000-6-4 (industrial) Noise immunity: EN 61000-6-2:2005 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Conducted noise emission: ENÃ55016 ENÃ61000-6-3 (Class B) Noise emission: ENÃ55016 ENÃ61000-6-3 (Class B) Harmonic currents Standards/regulations: ENÃ61000-3-2 ENÃ61000-3-2 (Class A) Flicker Standards/regulations: ENÃ61000-3-3 Frequency range: 0 kHz ... 2 kHz Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 6 kV (Test Level 3) Discharge in air: 8 kV (Test Level 3) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 6 GHz Test field strength: 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: asymmetrical 4 kV (Test Level 4) Output: asymmetrical 2 kV (Test Level 3) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: symmetrical 2 kV (Test Level 4) asymmetrical 4 kV (Test Level 4) Output: symmetrical 1 kV (Test Level 3) asymmetrical 2 kV (Test Level 3) Comments: Criterion B Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ Input/Output: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Voltage dips Standards/regulations: ENÃ61000-4-11 Voltage: 230 VÃAC Frequency: 50 Hz Voltage dip: 70 % 40 % 0 % Number of periods: 25 periods 10 periods 1 period Additional text: ClassÃ3 Comments: Criterion A Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
|